Page 21
Section 1-4
New C200HS Features
1-4-2 Faster Execution Times Instruction Execution Time
Basic instructions in the C200HS are executed in as little as !@2 of the time required in the C200H. Other instructions are executed in just !@3 to !@8 of the time.
END Processing Time
The time required for the cycle’s overhead processes depend on the system configuration, but these processes are executed in about !@4 of the time required in the C200H.
I/O Refreshing Time
The I/O refreshing time has been reduced for all units, as shown in the following table. I/O Unit
Time Required for Refreshing
Standard I/O Units
!@3 of the C200H I/O refreshing time
Group-2 High-density I/O Units
!@3 of the C200H I/O refreshing time
Special I/O Units
$@5 of the C200H I/O refreshing time
1-4-3 Larger Instruction Set Advanced programming is facilitated by the 225 special instructions available with the C200HS-CPU01-E, C200HS-CPU01-EC, C200HS-CPU03-E, C200HS-CPU21-E, C200HS-CPU21-EC, and C200HS-CPU23-E, or the 229 special instructions available with the C200HS-CPU31-E and C200HSCPU33-E. In addition, programming has been simplified by the addition of convenient instructions and macro functions. The new instructions and functions are covered in detail in the C200HS Operation Manual (W235).
1-4-4 Expanded Number of I/O Points Two Expansion I/O Racks can be connected to a CPU Rack to comprise a total of three Racks. This allows for a total of 240 I/O points, for example, when 8-point I/O Units are used, or 480 I/O points when 16-point I/O Units are used. In addition, a Remote I/O System can provide a maximum of 800 points with Slave Units or 512 points with Optical I/O Units.
1-4-5 Wide Selection of Special I/O Units C200HS Systems can be configured in a variety of ways, using High-density I/O Units, High-speed Counters, Position Control Units, Analog I/O Units, Temperature Sensor Units, ASCII Units, Voice Units, ID Sensor Units, Fuzzy Logic Units, Cam Positioner Units, and so on.
1-4-6 Improved Interrupt Functions Scheduled Interrupts
The C200HS’s scheduled interrupt function has been improved so that the interrupt interval can be set in 1 ms units rather than the 10 ms units in the C200H. When the interrupt mode is set to C200HS mode, the interrupt response time is only 1 ms max. (excluding the input ON/OFF delays). When a Communications Unit is used with the C200HS-CPU31-E/CPU33-E CPU, the interrupt response time is 10 ms max.
Input Interrupts
Up to 8 interrupt subroutines can be executed by inputs to a C200HS-INT01 Interrupt Input Unit mounted to the C200HS. When the interrupt mode is set to C200HS mode, the interrupt response time is only 1 ms max. (excluding the input ON/OFF delays). When a Communications Unit is used with the C200HSCPU31-E/CPU33-E CPU, the interrupt response time is 10 ms max.
9
Page 22
Section 1-4
New C200HS Features
1-4-7 SYSMAC NET Link and SYSMAC LINK Capabilities The SYSMAC NET Link and SYSMAC LINK Systems are high-speed FA networks which can be used with the C200HS-CPU31-E and C200HS-CPU33-E CPUs and the following Units: SYSMAC NET Link Unit:
C200HS-SNT32
SYSMAC LINK Units:
C200HW-SLK13/SLK14 (optical fiber cable) C200HW-SLK23/SLK24 (coaxial cable)
Data can be exchanged with the PCs in a SYSMAC NET Link or SYSMAC LINK System using the SEND and RECV instructions.
1-4-8 Built-in RS-232C Connector Host link communications are possible using the RS-232C connector built into the C200HS-CPU21-E/CPU21-EC/CPU23-E/CPU31-E/CPU33-E CPU. By using the TXD and RXD instructions, RS-232C communications is possible without using time-consuming procedures. A 1-to-1 link using the LR Area or an NT link with the Programmable Terminal (PT) allows high-speed communications.
1-4-9 More Flexible PC Settings With its default settings, the C200HS can be used like a C200H PC, but the C200HS’s new settings provide more flexibility and allow it to be adjusted to fit particular applications. These new settings are described below. DIP Switch Settings
The 6 pins on the C200HS’s DIP switch are used to write-protect part of UM, set the CPU to automatically transfer Memory Card data to UM, and other functions.
UM Area Allocation
Portions of the UM area can be allocated for use as the Expansion DM Area and I/O Comment Area. (Most of the UM area is used to store the ladder program.)
PC Setup
DM 6600 to DM 6655 is set aside for PC Setup data. The PC Setup determines many operating parameters, including the startup mode and initial Special I/O Unit area.
1-4-10 Debugging and Maintenance New functions such as data trace and differential monitor have been added, making it easier to check status changes. These and other new functions are covered in detail in the C200HS Operation Manual (W235).
1-4-11 Peripheral Devices Peripheral Device Connection
With the C200H, Peripheral Devices had to be connected through a Peripheral Interface Unit or Host Link Unit, but with the C200HS Peripheral Devices can be connected to the PC through a CQM1-CIF02 Connecting Cable.
I/O Comments Stored in PC
By allocating a part of UM as the I/O Comment area, it is no longer necessary to read I/O Comments from a Peripheral Device’s floppy disk. If the Peripheral Device is connected to the C200HS online, the ladder diagram can be viewed with I/O comments.
Online Editing
A “CYCLE TIME OVER” error will no longer be generated when the program in the PC itself is being edited online.
10
Page 23
Section 1-5
Comparisons Between C200HS and C200H
1-5
Comparisons Between C200HS and C200H The following table outlines the main upgrades that have been made, and the differences in functions and performance between the C200HS and the C200H. Model
Function C200HS
C200H
Memory Built-in UM capacity
RAM: 16K words (Program capacity: 15.2K words)
None (Memory Unit used.)
Optional memory
Memory Cassette (backup, storage)
Memory Unit (for loading, storing UM)
EEPROM
C200HS-ME 16K (16K words)
C200H-ME431/2 (4K words) C200H-ME831/2 (8K words)
EPROM
C200HS-MP 16K (16K words)
C200H-MP831 (8K words)
RAM
---
C200H-MR431/2/3 (4K words) C200H-MR831/2/3 (8K words)
I/O memory IR memory
3,296 bits (03000 to 23515) 3,392 bits (30000 to 51115)
3,296 bits (03000 to 23515)
SR memory
312 bits (23600 to 25507) 704 bits (25600 to 29915)
312 bits (23600 to 25507)
Normal DM
6,144 words (DM 0000 to DM 6143)
1,000 words (DM 0000 to DM 0999)
Fixed DM
512 words (DM 6144 to DM 6655)
1,000 words (DM 1000 to DM 1999)
Expansion DM
0 to 3,000 words (DM 7000 to DM 9999)
---
Data Memory
Standard for all models.
Standard for CPU11-E/31-E. Included in Memory Unit for C200HSCPU21-E/22-E/23-E.
Basic instructions
0.375 to 1.125 µs
0.75 to 2.25 µs
Special instructions
Approx. 1/4 that of the C200H.
34 to 724 µs
0.7 ms
2.8 ms
Basic I/O
Approx. 1/3 that of the C200H.
0.04 to 0.07 ms/8 bits
High-density I/O (Group 2)
Approx. 1/3 that of the C200H.
0.34 to 0.86 ms/Unit
Special I/O
Approx. 4/5 that of the C200H.
0.8 to 6.5 ms/Unit
Clock function Execution time Instruction execution time
Common processing time (END processing time) I/O refresh time
Instructions Number of instructions
225 (229 for the CPU31-E/CPU33-E)
168 (172 for the CPU31-E)
Basic instructions
14 (SET/RSET added)
12
Special instructions
211 (215 for the CPU31-E/CPU33-E)
156 (160 for the CPU31-E)
UM area arrangement
---
Setting functions
PC operation setting switch Special instruction settings PC Setup
11
Page 24
Section 1-5
Comparisons Between C200HS and C200H Function
Model C200HS
C200H
Interrupt function Scheduled interrupts Interrupt period
10 ms x SV or 1 ms x SV
10 ms x SV
Interrupt response time
10 ms max. (C200H common mode, Communications Unit connected) 1 ms (C200HS mode, Communications Unit not connected)
10 ms max.
Input interrupts
8 points max.
Interrupt Input Unit
C200HS-INT01 (8 points)
No interrupt input function
Backplane
C200H-BCjj1-V2 (corresponding to Interrupt Input Unit)
C200H-BCjj1-V1 (Interrupt Input Unit not possible.)
Interrupt response time
1 ms max. (10 ms max. when Communications Unit connected)
Debugging and maintenance
Forced set/reset Data trace Differential monitor
Programming Console operations
Decimal display of binary data
Forced set/reset
Continuation of display when modes are switched Terminal mode and expansion terminal mode
Terminal mode
Connection method
Direct connection to C200HS.
Connection via Peripheral Interface Unit or Host Link Unit.
Cable for personal computer
CQM1-CIF02
Peripheral Devices
SYSMAC Support Software (SSS) C500-ZL3AT1-E I/O comments
Can be stored in C200HS
Online editing
Cycle time over non-detection setting possible. For C200HS-CPU31-E/CPU33-E
Communications Units
C500-ZL3AT1-E
SYSMAC NET Link
C200HS-SNT32
C200H-SNT31
SYSMAC LINK
C200HW-SLK13/SLK14 (Optical) C200HW-SLK23/SLK24 (Coaxial) RS-232C connector built into the C200HS-CPU21-E/CPU21-EC/ CPU23-E/CPU31-E/CPU33-E
C200H-SLK11 C200H-SLK21-V1 ---
Built-in Host Link
1-to-1 link
LR Area is shared by connecting RS-232C connectors.
NT link
High-speed communications with Programmable Terminal (PT) via RS-232C connector.
Host Link Units Added function
12
Transmission possible by means of TXD instruction.
Optical cable
C200H-LK101-PV1
C200H-LK101-P
RS-232C
C200H-LK201-V1
C200H-LK201
RS-422
C200H-LK202-V1
C200H-LK202
Page 25
Section 1-6
Compatibility of C200HS and C200H Devices
1-6
Compatibility of C200HS and C200H Devices Completely compatible: C200H devices can be used with the C200HS as is. Replacement Units: These Units were developed for the C200HS and can be used for both the C200H and the C200HS. C200HS only: These devices can only be used with the C200HS.
Classification CPU Rack
Type of Unit
Completely compatible
Replacement Units
CPU
Backplane
C200HS only
Remarks
Yes
C200HS-CPU01-E/01-EC /03-E/21-E/21-EC/23-E/ 31-E/33-E
Yes
Memory Cassette
C200H-BC031-V2/051-V2 /081-V2/101-V2 (Existing Backplanes can be used if Interrupt Input Units are not used.) Yes
C200HS-ME16K/MP16K
Expansion I/O Rack
Yes
Configured based on Backplane and I/O Power Supply Unit.
I/O Connecting Cable
Yes
One cable is required to connect one Expansion I/O Rack.
I/O Unit
8/12/16-pt. I/O Units Standard B7A Interface Units Group-2 High-density I/O Unit and Group-2 B7A Interface Units
Yes
Special I/O Unit
Yes
16 pts.
Yes
32 pts. or 64 pts.
Yes
High-speed Counters, Position Control Units, High-density I/O Units, Analog I/O Units, Temperature Sensor Units, ASCII Units, etc. When mounting an Interrupt Input Unit, use the C200H-BCjj1-V2.
Interrupt Unit
Yes
Remote I/O (Optical)
Master Unit Slave Unit
Yes Yes
C200H-RM001-PV1 C200H-RT001-P/002-P
Remote I/O (Wired)
Master Unit Slave Unit
Yes Yes
C200H-RM201 C200H-RT201/201-C/202
Link
Host Link Unit
PC Link Unit
Peripheral Device
Yes
Yes
C200H-LK401
SYSMAC LINK
Yes
SYSMAC NET Link Programming Console SSS
Yes Yes Yes
C200H-LK101-PV1 C200H-LK201-V1 C200H-LK202-V1 C200HW-SLK13/SLK14 C200HW-SLK23/SLK24 C200HS-SNT32 C200H-PRO27-E CQM1-PRO01-E C500-ZL3AT1-E
13
Page 26
SECTION 2 System Configuration and Unit Description This section provides information about the Racks and individual Units that make up a C200HS PC System. The names of all the parts of a Unit are given, followed by any details that apply to that Unit alone. For a description of how the Units fit together to become a PC, refer to Section 3 Assembly Instructions. For information about the model numbers of any of the parts described in this section, refer to Appendix A Standard Models. For specifications, refer to Appendix B Specifications. 2-1
2-2
2-3 2-4 2-5
System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1-1 CPU Racks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1-2 Expansion I/O Racks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1-3 Slave Racks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPUs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2-1 CPU Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2-2 CPU Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2-3 Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2-4 DIP Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2-5 Peripheral Device Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2-6 Operation Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2-7 Memory Cassettes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Expansion I/O Racks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Supply Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5-1 Standard I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5-2 Group-2 High-density I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5-3 High-density I/O Units Classified as Special I/O Units . . . . . . . . . . . . . . . . . . . .
16 16 17 17 18 18 19 20 22 22 23 23 24 25 26 27 28 30
15
Page 27
Section 2-1
System Configuration
2-1
System Configuration A variety of system configurations can be achieved by using different combinations of Racks and Units. Before ordering specific Units, carefully consider which system configuration will best meet your control requirements. In a C200HS PC System, a maximum of two Expansion I/O Racks and five Remote I/O Slave Racks can be connected to a CPU Rack.
2-1-1 CPU Racks A CPU Rack consists of the CPU, I/O Units, and other Units mounted to a CPU Backplane. An example is shown below. (8)
(4)
(3) (1)
(2)
(10) (9)
(6), (7)
(5)
1. Backplane There are backplanes available with 3, 5, 8, or 10 slots. The same backplanes can be used for CPU Racks, Expansion I/O Racks, or Slave Racks. 2. CPU There are eight CPU models available: CPU01-E, CPU01-EC, CPU03-E, CPU21-E, CPU21-EC, CPU23-E, CPU31-E, and CPU33-E. 3. Battery and DIP Switch Compartment An optional Memory Cassette can also be added here. EPROM and EEPROM Memory Cassettes are both available. 4. Standard I/O Unit The Units can have 5, 8, 12, or 16 points. In this illustration the I/O Unit cover is mounted. This is the terminal block cover for Units with 10P terminal blocks. 5. Interrupt Input Unit One Interrupt Input Unit can be used at the CPU Rack. 6. and 7. SYSMAC NET Link/SYSMAC LINK Unit, Host Link Unit, PC Link Unit Remote I/O Master Unit A maximum of two Units can be used of each of these Units, either on the CPU Rack or on an Expansion I/O Rack. SYSMAC NET Link/SYSMAC LINK Units can be mounted only to C200HS-CPU31-E/CPU33-E CPUs. Bus Connection Units are required to connect to the CPU and a Power Supply Adapter/Auxiliary Power Supply Unit must be mounted next to the Unit. 8. Standard I/O Unit Terminal blocks have either 10 or 19 terminals. This is a 19P terminal block. 9. High-density I/O Unit (Group 2) or Group-2 B7A Interface Unit A maximum of ten Units can be used if they are all 32-point Units, and five if they are all 64-point Units. They cannot be used on Slave Racks. 10. Special I/O Unit Up to ten Special I/O Units can be used (including PC Link). They can be used on any Rack.
16
Page 28
Section 2-1
System Configuration
2-1-2 Expansion I/O Racks An Expansion I/O Rack consists of an I/O Power Supply Unit and I/O Units mounted to a Backplane. A maximum of two Expansion I/O Racks can be connected. The same Expansion I/O Racks can be connected to either C200H or C200HS CPU Racks via an I/O Connecting Cable. (2)
(3)
(1)
1. I/O Power Supply Unit 2. Backplane There are backplanes available with 3, 5, 8, or 10 slots. The same backplanes can be used for CPU Racks, Expansion I/O Racks, or Slave Racks. 3. I/O Connecting Cable There are five types of cable, from 30 cm to 10 m. A maximum total of 12 m can be used.
2-1-3 Slave Racks A Slave Rack consists of an Remote I/O Slave Unit and I/O Units mounted to a Backplane. A maximum of five Slave Racks can be connected. Slave Racks are connected via either optical or wire cables to a Remote I/O Master Unit mounted to the CPU Rack.
(2)
(1)
1. Slave Unit Either Optical or Wired Slaves can be used. 2. Fiber-optic Cable
17
Page 29
Section 2-2
CPUs
2-2
CPUs There are two groups of CPUs available, one that uses an AC power supply, and one that uses a DC power supply. Select one of the models shown below according to requirements of your control system. CPU model
Power supply voltage
C200HS-CPU01-E/CPU01-EC/CPU21-E 100 to 120 VAC or 200 to 240 VAC /CPU21-EC/CPU31-E (voltage selector) C200HS-CPU03-E/CPU23-E/CPU33-E 24 VDC
The CPU21-E, CPU23-E, CPU31-E, and CPU33-E CPUs have an RS-232C connector. The CPU31-E and CPU33-E CPUs support the SYSMAC NET Link Unit and SYSMAC LINK Unit. The C200HS-CPU01-EC CPU and C200HSCPU03-E CPU with lot number jjZ5 (Dec. 1995) or later conform to EC directives. The C200HS-CPU21-EC CPU conforms to EC directives. ! Caution
Be sure to check the power supply used by the CPU. Absolutely do not apply an AC power supply to a DC-type CPU.
2-2-1 CPU Components C200HS-CPU01-E/CPU01-EC/CPU03-E Indicators
Power fuse (MF51NR, 5.2 dia. x 20 mm): C200HS-CPU01-E/CPU01-EC: 2 A, 250 V C200HS-CPU03-E: 5 A, 125 V
Removable terminal block
Battery/Switch compartment: The backup lithium battery (C200H-BAT09) and the DIP switch for setting C200HS operations are contained. An optional Memory Cassette can also be mounted.
18
Cable connector for peripheral devices (Peripheral device connector)
Page 30
Section 2-2
CPUs C200HS-CPU21-E/CPU21-EC/CPU23-E/CPU31-E/CPU33-E
Indicators
Power fuse (MF51NR, 5.2 dia. x 20 mm): C200HS-CPU21-E/CPU21-EC/CPU31-E: 2 A, 250 V C200HS-CPU23-E/CPU33-E: 5 A, 125 V
Memory Casette compartment
Bus connector: Available only with the CPU31-E and CPU33-E. Use this connector when SYSMAC NET Link Unit or SYSMAC LINK Unit is used.
Removable terminal block
Cable connector for RS-232C connector peripheral devices Battery/Switch compartment
2-2-2 CPU Indicators The following table shows the indicators that are located on the front panel of the CPUs. COMM1 (orange) (Note “COMM” on CPU01-E/CPU01-EC/CPU03-E): Lights when a peripheral device is in operation.
RUN (green): Lights when the PC is operating normally.
COMM2 (orange): Available only with the CPU21-E, CPU21-EC, CPU23-E, CPU31-E, and CPU33-E. Lights when the CPU is communicating via the RS-232C connector. POWER (green): Lights when power is supplied to the CPU.
COMM 1 COMM 2
ALM (blinking red): Blinks if an error occurs that does not stop the CPU.
OUT INHIBIT (red): Lights when the Load OFF flag (SR bit 25215) turns ON, at which time all the outputs are turned OFF.
ERR (solid red): Lights if an error occurs that stops the CPU, at which time the RUN indicator turns OFF and the outputs are turned OFF.
19