For the Omron C200H-OC225 and Omron C200HW-SLK23

Page 181

Appendix B

Specifications

Pin 3: Minimum Pulse Width Setting of Pulse Input Response Use pin 3 only when pin 2 of the C200H-ID501, C200H-ID215, C200H-MD501, C200H-MD115, and C200HMD215 is set to ON (i.e., when pulse input is set). Pin 3

Minimum response input pulse width

OFF

1 ms

ON

4 ms

Pin 4: Input Response Time Setting Use pin 4 for the C200H-ID501, C200H-ID215, C200H-MD501, C200H-MD115, and C200H-MD215 only. Pin 4

Input response time

OFF

2.5 ms max.

ON

15 ms max.

Pin 5: Dynamic Data Output Logic Setting Use pin 5 only when the C200H-OD501 or C200H-OD215 is in dynamic output mode (i.e., when pin 1 is set to ON). Pin 5

Data output

OFF

Negative logic output

ON

Positive logic output

DIP Switch Settings for High-density I/O Unit (Special I/O Unit) Model

Pin 1

Pin 2

Pin 3

Pin 4

Pin 5

Pin 6

C200H-ID501/215

Setting is not required

Must be set

Set when pulse input is used

Must be set

Setting is not required

Setting is not required

C200H-OD501/215

OFF

Setting is not required Setting is not required Must be set

Setting is not required Setting is not required Set when pulse input is used

Setting is not required Setting is not required Must be set

Setting is not required Must be set Setting is not required

Setting is not required Setting is not required Setting is not required

Setting is not required

Setting is not required

Setting is not required

Setting is not required

Setting is not required

ON C200H-MD501/115/215

OFF

ON

174

Page 182

Appendix B

Specifications

Analog Timer Unit C200H-TM001 Item

Specifications

Oscillation Method

CR oscillation

Time Setting Range

Use the DIP switch to set any of the following four ranges, according to the chart shown on the next page. 0.1 to 1 second (typical) 1 to 10 seconds (typical) 10 to 60 seconds (typical) 1 to 10 minutes (typical)

Timer Pause Function Number of Timer Points

The timing operation can be paused if so specified by the program. Therefore, the timers can also be used as cumulative registers. 4

Indicators

SET and TIME UP

External Variable Resistor Bit Allocation

External variable resistors can be used to set the time value when the IN/EXT selector is set to OFF (EXT). Use 20 kW variable resistors. The word is determined by the system configuration.

Bit

Function

00

T0 start output

01

T1 start output

02

T2 start output

03

T3 start output

04

T0 pause output

05

T1 pause output

0

Operates

06

T2 pause output

1

Stops

07

T3 pause output

08

T0 time-up input

09

T1 time-up input

10

T2 time-up input

11

T3 time-up input

“1” when time is running

“1” when time is up

12 13 Cannot be used 14 15 Programming and Timing Chart

Timer start input word n bits 08 through 11

Timer setting (word n bits 00 through 03) Time-up output

Time-up flag Internal Current Consumption

Timer start input

Time-up output Timer set value

60 mA 5 VDC max.

175

Page 183

Appendix B

Specifications Internal variable resistors These variable resistors are used to set the timers. The settings of these resistors are effective only when the corresponding IN/EXT selector is ON. To set or adjust the time, use the screwdriver supplied with the Unit. Turn the variable resistor clockwise to increase the time value. The numbers 0 through 3 correspond to T0 through T3, respectively.

TM001

Indicators The SET indicators in the top row light when the corresponding timer is operating. The TIME UP indicators in the bottom row light when the corresponding timer (T0 through T3) turns ON.

0

1

2

3

Time range setting

Min. 0 1

Max.

External variable resistor connectors External variable resistors can also be used to set the timers. The IN/EXT selector pin must be set to the OFF position. Numbers 0 through 3 correspond to T0 through T3, respectively. Use 20-kW variable resistors and AWG 22 to 28 lead wires. The connector has solderless terminals and must be wired as shown below.

2 3

IN/EXT selectors When the internal variable resistor is used, set the corresponding pin to ON; when an external variable resistor is used, set the corresponding pin to OFF. Pin numbers 4 through 1 correspond to T0 through T3, respectively.

Timers

Pin

0.1 to 1 s

0.1 to 10 s

10 to 60 s

1 to 10 m

T0

8

0

1

0

1

7

0

0

1

1

6

0

1

0

1

5

0

0

1

1

4

0

1

0

1

3

0

0

1

1

2

0

1

0

1

1

0

0

1

1

T1 T2 T3

(0: OFF 1: ON)

176

Page 184

Appendix B

Specifications External variable resistor connector

External variable resistor

! Caution

Ensure that the external variable resistor connectors are open when using the internal variable resistor.

Standard B7A Interface Unit C200H-B7AI1/B7AO1 The Standard B7A Interface Unit used with the B7A Link Terminal allows the transmission and reception of 16-point I/O data over two wires. The following Standard B7A Interface Unit and B7A Link Terminal models are available. B7A Interface Unit 16-point input: C200H-B7AI1 16-point output: C200H-B7AO1

B7A Link Terminals B7A-T6j1 (Screw terminal models) B7A-T6D2 (Modular models) B7A-R6jj1 (Screw terminal models) B7A-R6A52 (Modular models)

Mount the B7A Interface Unit to the C200H-BCjj1-V1 or C200H-BCjj1-V2 Backplane. Note If the B7A Interface Unit is connected to the C200HS-CPU03/CPU23-E/CPU33-E or C200H-PS211, supply 24 VDC from an independent power supply to the B7A Interface Unit or use a transformer to separate the power supply line to the B7A Interface Unit from the power supply lines to the CPU and I/O Power Supply Unit.

I/O indicator ERR indicator

Connection terminals Connection terminals for the B7A Link Terminal: Connect this terminal to the SIG terminal of the B7A Link Terminal. Connect this terminal to the negative power terminal of the B7A Link Terminal. Supply 12 to 24 VDC. 12 to 24 VDC

177

Page 185

Appendix B

Specifications

I/O Indicator Indicates the ON or OFF status of input from the B7A Link Terminal or the ON and OFF status of output to the B7A Link Terminal. ERR Indicator Incorporated by the B7AI1 and lit when the B7AI1’s data transmission or reception is abnormal. Connection Terminals SIG: Connects to the SIG terminal of the B7A Link Terminal. V–: Connects to the negative power terminal of the B7A Link Terminal. ! Caution

If the terminals are not connected correctly, the internal circuitry of the B7A Link Terminal will be damaged.

Note 1. The transmission cable must be a VCTF cable with a thickness of 0.75 mm2 minimum. 2. Do not wire power lines or high-tension lines along with the transmission cable in the same conduit. Input Mode Selector The B7AI1 incorporates an input mode selector on the back panel of the Unit, with which the following modes can be set. Input mode

15 points + 1 error

16 points

Function

Fifteen-point input from the B7A Link Terminal is effective. Bit 15 is used as transmission error bit.

Sixteen-point input from the B7A Link Terminal is effective.

Switch setting Bit no. allocation

Upper side

Lower side

00 to 14 15 Status of input indicator lamp 15 Status of the ERR indicator

Input 00 to input 14 Transmission error bit Not used

Input 00 to input 14 Input 15 Lit when input 15 is ON. Not lit when input 15 is OFF. Lit when there is a transmission error and OFF during normal transmission

The ERR indicator is lit when an error occurs. If the error is corrected, the ERR indicator is OFF at the next transmission cycle. When there is a transmission error, the B7A Link Terminal will hold the data just before the occurrence of the transmission error. If there is a transmission error because the B7A Link Terminal is turned off, however, data 0 is transmitted in the first transmission cycle when the B7A Link Terminal is turned on again. Transmission errors between the C200H-B7AO1 and B7A Link Terminal are detected by the B7A Link Terminal only. Check the ERR indicator and error bit for any error. Performance Specifications Item I/O points

C200H-B7AI1

C200H-B7AO1

Transmission distance

16 points or 15 points and 1 error 16 output points input 500 m max. if power is supplied to the Interface Unit and B7A Link Terminal separately. 100 m max. if power is supplied to the Interface Unit and B7A Link Terminal from a single power supply. (24 VDC±10%)

Transmission delay

Typ. 19.2 ms, 31 ms max.

Minimum input time (see note 1)

---

Internal current consumption

5 VDC, 100 mA max.

External power supply (see note 2)

12 to 24 VDC ±10%, 10 mA min.

Weight

200 g max.

16 ms 12 to 24 VDC ±10%, 30 mA min.

Note 1. The minimum input time refers to the minimum time required for reading the input signals from the CPU. The ON/OFF width of the signal transmitted from the CPU to the output relay of the B7A Interface Unit should be set to a value larger than the minimum input time. 2. The value of the external power supply does not include the value required by the B7A Link Terminal.

178

Page 186

Appendix B

Specifications

Group-2 B7A Interface Units (C200H-B7Ajj) A Group-2 B7A Interface Unit used with two or four B7A Link Terminals allows the transmission and reception of 32-point or 64-point I/O data over two-conductor cables. Group-2 B7A Interface Unit

C200HS CPU

Input B7A Link Terminal

Sensor Switch

Transmission distance: 500 m max.

Output B7A Link Terminal

Lamps and other loads

Group-2 B7A Interface Units can be mounted to a CPU Rack or an Expansion I/O Rack. They cannot be mounted to Slave Racks or to Racks controlled by any other CPUs. The words allocated to Group-2 B7A Interface Units are determined by I/O number set on the Units. Units with 32 I/O points are allocated two words; Units with 64 I/O points are allocated four words. Refer to the B7A Link Terminals Datasheet for more information on B7A Link Terminals.

Models The following Group-2 B7A Interface Units are available. B7A Interface Unit

Inputs

Outputs

C200H-B7A12

32 points

None

C200H-B7A02

None

32 points

C200H-B7A21

16 points

16 points

C200H-B7A22

32 points

32points

179

Page 187

Appendix B

Specifications

Connectable B7A Link Terminals Only 16-point B7A Link Terminals can be connected to a B7A Interface Unit. Input Terminals Type Screw terminals

Modular PC connectors

Model B7A-T6j1 B7AS-T6j1 B7A-T6j6 B7AS-T6j6 B7A-T6D2 B7A-T6D7 B7A-TjE3 B7A-TjE8

Transmission delay Standard (19.2 ms) High-speed (3 ms) Standard (19.2 ms) High-speed (3 ms) Standard (19.2 ms) High-speed (3 ms)

Output Terminals Type Screw terminals

Modular PC connectors

Model B7A-R6jj1 B7AS-R6jj1 B7A-R6jj6 B7AS-R6jj6 B7A-R6A52 B7A-R6A57 B7A-RjAj3 B7A-RjAj8

Transmission delay Standard (19.2 ms) High-speed (3 ms) Standard (19.2 ms) High-speed (3 ms) Standard (19.2 ms) High-speed (3 ms)

Note 1. Do not connect Terminals with different transmission delays to the same Interface Unit. Doing so will cause a transmission error. 2. The 10-point B7A Link Terminals and mixed-I/O B7A Link Terminals with 8 inputs and 8 outputs cannot be connected to B7A Interface Units. Use 16-point B7A Link Terminals. The 16-point B7A Link Terminals include 16-point (non-mixed) Terminals, 32-point Terminals configured with two 16-point circuits, and mixed-I/O Terminals with 16 inputs and 16 outputs.

Comparison between Standard and Group-2 B7A Interface Units Type

Standard

Models

C200H-B7AI1 C200H-B7AO2

Group-2

C200H-B7A12 C200H-B7A02 C200H-B7A21 C200H-B7A22

Word allocations

Same as I/O Units (in order mounted). Words 030 to 049 allocated according to I/O number setting (same as Group-2 High-density I/O Units)

Connectable B7A Link Terminals Transmission Transmission Points delay errors Standard Input status 16-point types only held Terminals only automatically (see note 2) (19.2 ms) Standard (19.2 ms) and high-speed (3 ms) types (set via switch)

Switch setting to hold or reset Input status.

Note 1. Mount the C200H-B7AO1 B7A Interface Unit to the C200H-BCjj1-V1 or C200H-BCjj1-V2 Backplane. 2. The 10-point B7A Link Terminals and mixed-I/O B7A Link Terminals with 8 inputs and 8 outputs cannot be connected to B7A Interface Units. The 16-point (non-mixed) Terminals, 32-point Terminals configured with the two 16-point circuits, and mixed-I/O Terminals with 16 inputs and 16 outputs can be connected.

180

Page 188

Appendix B

Specifications

Parts and Names (C200H-B7A22 shown below) Front

I/O number switch This switch determines the words allocated to the Unit. Status indicators The indicators depend on the model of B7A Interface Unit.

Connection terminals Connect to the SIG terminal of the B7A Link Terminal and to the negative power terminal of the B7A Link Terminal. The actual use of these terminals depends on the B7A Interface Unit.

External Power Supply Terminals Supply 12 to 24 VDC.

12 VDC 12toto2424 VDC

Back

DIP switch Used to set the transmission delay, transmission error processing mode, input mode, and ERROR indicator operation.

181

Page 189

Appendix B

Specifications

Indicator Operation The indicators depend on the model of B7A Interface Unit, as shown below.

Name

Color

Function

ERROR 1 ERROR 2 ERROR

Input transmission error

Red

Lights when an error occurs in transmissions from an Input B7A Link Terminal. For the B7A12/22, ERROR 1 is for the first word allocated to the B7A Interface Unit; ERROR 2 is for the second word.

3ms

Transmission delay setting

Orange

Lit when the transmission delay is set to the high-speed setting (3 ms).

Transmission error process

Orange

Input mode setting

Orange

LOAD OFF 15IN+ERR

Not lit when the transmission delay is set to the standard setting (19.2 ms). Lit when the processing for transmission errors is set to reset input status. Not lit when the processing for transmission errors is set to hold input status. Lit when the input mode mode is set to use 15 inputs and 1 error input. Not lit when the input mode mode is set to use 16 inputs.

I/O Number Setting The setting of the I/O number determines the words allocated to the Interface Unit. Set the I/O number to between 0 and 9.

Setting in direction of notch

Note 1. Turn off the power supply to the PC before changing the I/O number setting. Any new setting will not be effective until the next time the power supply is turned on. 2. Use a flat-blade screw driver to change the I/O number setting. Be careful not to leave the switch halfway between settings and be careful not to damage the switch. The following table shows the words allocated according to the I/O number. The 32-point Units are the C200H-B7A12, C200H-B7A02, and C200H-B7A21. The 64-point Unit is the C200H-B7A22. Words

I/O No. 0

32-point Units IR 030 and IR 031

64-point Unit IR 030 to IR 033

1

IR 032 and IR 033

IR 032 to IR 035

2

IR 034 and IR 035

IR 034 to IR 037

3

IR 036 and IR 037

IR 036 to IR 039

4

IR 038 and IR 039

IR 038 to IR 041

5

IR 040 and IR 041

IR 040 to IR 043

6

IR 042 and IR 043

IR 042 to IR 045

7

IR 044 and IR 045

IR 044 to IR 047

8

IR 046 and IR 047

IR 046 to IR 049

9

IR 048 and IR 049

Do not use.

Note 1. Be sure that the same words are not allocated to more than one Unit. For example, if you set a 64-point Unit to I/O number 0, you cannot use I/O number 1 for any Unit. 2. The above words are also allocated to Group-2 High-density I/O Units. Be sure that the same words are not allocated to more than one Unit.

182

Page 190

Appendix B

Specifications

DIP Switch Settings Set the DIP switch as described before for the various models of B7A Interface Units. C200H-B7A22/12 Pin

Factory setting (pins 4 and 5 ON)

Function

OFF

ON

1

Transmission delay

Standard (19.2 ms)

High-speed (3 ms)

2

Transmission error process

Hold status

Reset Inputs

3

Input mode

16 inputs

15 inputs + error input

4

ERROR 1 indicator enable

Disabled

Enabled

5

ERROR 2 indicator enable

Disabled

Enabled

6

Not used.

NA

NA

C200H-B7A21 Pin

Factory setting (pin 5 ON)

Function

OFF

ON

1

Transmission delay

Standard (19.2 ms)

High-speed (3 ms)

2

Transmission error process

Hold status

Reset Inputs

3

Input mode

16 inputs

15 inputs + error input

4

ERROR indicator enable

Disabled

Enabled

5

Not used.

NA

NA

6

Not used.

NA

NA

C200H-B7A02 Pin

Factory setting (all pins OFF)

Function

OFF

ON

1

Transmission delay

Standard (19.2 ms)

High-speed (3 ms)

2

Not used.

NA

NA

3

Not used.

NA

NA

4

Not used.

NA

NA

5

Not used.

NA

NA

6

Not used.

NA

NA

Transmission Delay Pin 1 is used to set the transmission delay. The same delay is used for all words allocated to the Unit. Set the transmission delay to match that of the B7A Link Terminal. A transmission error will occur if the same transmission delay is not set. The “3ms” indicator will be lit whenever the high-speed (3 ms) transmission delay is set. Transmission Error Process Pin 2 is used to turned ON to specify resetting input status when transmission errors occur. If pin 2 is turned OFF, input status will be held when transmission errors occur. The LOAD OFF indicator will be lit whenever pin 2 is turned ON. Input Mode Pin 3 is turned ON to specify use of only 15 inputs and the use of bit 15 as a Transmission Error Flag. If pin 3 is OFF, 16 normal inputs can be used. The “15IN+ERR” indicator will be lit whenever pin 3 is turned ON. ERROR Indicators Pin 4 or pins 4 and 5 are turned ON to enable the ERROR, ERROR 1, and/or ERROR 2 indicators. These indicators will not light even if a transmission error occurs if the corresponding pin is turned OFF.

183