Page 181
Appendix B
Specifications
Pin 3: Minimum Pulse Width Setting of Pulse Input Response Use pin 3 only when pin 2 of the C200H-ID501, C200H-ID215, C200H-MD501, C200H-MD115, and C200HMD215 is set to ON (i.e., when pulse input is set). Pin 3
Minimum response input pulse width
OFF
1 ms
ON
4 ms
Pin 4: Input Response Time Setting Use pin 4 for the C200H-ID501, C200H-ID215, C200H-MD501, C200H-MD115, and C200H-MD215 only. Pin 4
Input response time
OFF
2.5 ms max.
ON
15 ms max.
Pin 5: Dynamic Data Output Logic Setting Use pin 5 only when the C200H-OD501 or C200H-OD215 is in dynamic output mode (i.e., when pin 1 is set to ON). Pin 5
Data output
OFF
Negative logic output
ON
Positive logic output
DIP Switch Settings for High-density I/O Unit (Special I/O Unit) Model
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Pin 6
C200H-ID501/215
Setting is not required
Must be set
Set when pulse input is used
Must be set
Setting is not required
Setting is not required
C200H-OD501/215
OFF
Setting is not required Setting is not required Must be set
Setting is not required Setting is not required Set when pulse input is used
Setting is not required Setting is not required Must be set
Setting is not required Must be set Setting is not required
Setting is not required Setting is not required Setting is not required
Setting is not required
Setting is not required
Setting is not required
Setting is not required
Setting is not required
ON C200H-MD501/115/215
OFF
ON
174
Page 182
Appendix B
Specifications
Analog Timer Unit C200H-TM001 Item
Specifications
Oscillation Method
CR oscillation
Time Setting Range
Use the DIP switch to set any of the following four ranges, according to the chart shown on the next page. 0.1 to 1 second (typical) 1 to 10 seconds (typical) 10 to 60 seconds (typical) 1 to 10 minutes (typical)
Timer Pause Function Number of Timer Points
The timing operation can be paused if so specified by the program. Therefore, the timers can also be used as cumulative registers. 4
Indicators
SET and TIME UP
External Variable Resistor Bit Allocation
External variable resistors can be used to set the time value when the IN/EXT selector is set to OFF (EXT). Use 20 kW variable resistors. The word is determined by the system configuration.
Bit
Function
00
T0 start output
01
T1 start output
02
T2 start output
03
T3 start output
04
T0 pause output
05
T1 pause output
0
Operates
06
T2 pause output
1
Stops
07
T3 pause output
08
T0 time-up input
09
T1 time-up input
10
T2 time-up input
11
T3 time-up input
“1” when time is running
“1” when time is up
12 13 Cannot be used 14 15 Programming and Timing Chart
Timer start input word n bits 08 through 11
Timer setting (word n bits 00 through 03) Time-up output
Time-up flag Internal Current Consumption
Timer start input
Time-up output Timer set value
60 mA 5 VDC max.
175
Page 183
Appendix B
Specifications Internal variable resistors These variable resistors are used to set the timers. The settings of these resistors are effective only when the corresponding IN/EXT selector is ON. To set or adjust the time, use the screwdriver supplied with the Unit. Turn the variable resistor clockwise to increase the time value. The numbers 0 through 3 correspond to T0 through T3, respectively.
TM001
Indicators The SET indicators in the top row light when the corresponding timer is operating. The TIME UP indicators in the bottom row light when the corresponding timer (T0 through T3) turns ON.
0
1
2
3
Time range setting
Min. 0 1
Max.
External variable resistor connectors External variable resistors can also be used to set the timers. The IN/EXT selector pin must be set to the OFF position. Numbers 0 through 3 correspond to T0 through T3, respectively. Use 20-kW variable resistors and AWG 22 to 28 lead wires. The connector has solderless terminals and must be wired as shown below.
2 3
IN/EXT selectors When the internal variable resistor is used, set the corresponding pin to ON; when an external variable resistor is used, set the corresponding pin to OFF. Pin numbers 4 through 1 correspond to T0 through T3, respectively.
Timers
Pin
0.1 to 1 s
0.1 to 10 s
10 to 60 s
1 to 10 m
T0
8
0
1
0
1
7
0
0
1
1
6
0
1
0
1
5
0
0
1
1
4
0
1
0
1
3
0
0
1
1
2
0
1
0
1
1
0
0
1
1
T1 T2 T3
(0: OFF 1: ON)
176
Page 184
Appendix B
Specifications External variable resistor connector
External variable resistor
! Caution
Ensure that the external variable resistor connectors are open when using the internal variable resistor.
Standard B7A Interface Unit C200H-B7AI1/B7AO1 The Standard B7A Interface Unit used with the B7A Link Terminal allows the transmission and reception of 16-point I/O data over two wires. The following Standard B7A Interface Unit and B7A Link Terminal models are available. B7A Interface Unit 16-point input: C200H-B7AI1 16-point output: C200H-B7AO1
B7A Link Terminals B7A-T6j1 (Screw terminal models) B7A-T6D2 (Modular models) B7A-R6jj1 (Screw terminal models) B7A-R6A52 (Modular models)
Mount the B7A Interface Unit to the C200H-BCjj1-V1 or C200H-BCjj1-V2 Backplane. Note If the B7A Interface Unit is connected to the C200HS-CPU03/CPU23-E/CPU33-E or C200H-PS211, supply 24 VDC from an independent power supply to the B7A Interface Unit or use a transformer to separate the power supply line to the B7A Interface Unit from the power supply lines to the CPU and I/O Power Supply Unit.
I/O indicator ERR indicator
Connection terminals Connection terminals for the B7A Link Terminal: Connect this terminal to the SIG terminal of the B7A Link Terminal. Connect this terminal to the negative power terminal of the B7A Link Terminal. Supply 12 to 24 VDC. 12 to 24 VDC
177
Page 185
Appendix B
Specifications
I/O Indicator Indicates the ON or OFF status of input from the B7A Link Terminal or the ON and OFF status of output to the B7A Link Terminal. ERR Indicator Incorporated by the B7AI1 and lit when the B7AI1’s data transmission or reception is abnormal. Connection Terminals SIG: Connects to the SIG terminal of the B7A Link Terminal. V–: Connects to the negative power terminal of the B7A Link Terminal. ! Caution
If the terminals are not connected correctly, the internal circuitry of the B7A Link Terminal will be damaged.
Note 1. The transmission cable must be a VCTF cable with a thickness of 0.75 mm2 minimum. 2. Do not wire power lines or high-tension lines along with the transmission cable in the same conduit. Input Mode Selector The B7AI1 incorporates an input mode selector on the back panel of the Unit, with which the following modes can be set. Input mode
15 points + 1 error
16 points
Function
Fifteen-point input from the B7A Link Terminal is effective. Bit 15 is used as transmission error bit.
Sixteen-point input from the B7A Link Terminal is effective.
Switch setting Bit no. allocation
Upper side
Lower side
00 to 14 15 Status of input indicator lamp 15 Status of the ERR indicator
Input 00 to input 14 Transmission error bit Not used
Input 00 to input 14 Input 15 Lit when input 15 is ON. Not lit when input 15 is OFF. Lit when there is a transmission error and OFF during normal transmission
The ERR indicator is lit when an error occurs. If the error is corrected, the ERR indicator is OFF at the next transmission cycle. When there is a transmission error, the B7A Link Terminal will hold the data just before the occurrence of the transmission error. If there is a transmission error because the B7A Link Terminal is turned off, however, data 0 is transmitted in the first transmission cycle when the B7A Link Terminal is turned on again. Transmission errors between the C200H-B7AO1 and B7A Link Terminal are detected by the B7A Link Terminal only. Check the ERR indicator and error bit for any error. Performance Specifications Item I/O points
C200H-B7AI1
C200H-B7AO1
Transmission distance
16 points or 15 points and 1 error 16 output points input 500 m max. if power is supplied to the Interface Unit and B7A Link Terminal separately. 100 m max. if power is supplied to the Interface Unit and B7A Link Terminal from a single power supply. (24 VDC±10%)
Transmission delay
Typ. 19.2 ms, 31 ms max.
Minimum input time (see note 1)
---
Internal current consumption
5 VDC, 100 mA max.
External power supply (see note 2)
12 to 24 VDC ±10%, 10 mA min.
Weight
200 g max.
16 ms 12 to 24 VDC ±10%, 30 mA min.
Note 1. The minimum input time refers to the minimum time required for reading the input signals from the CPU. The ON/OFF width of the signal transmitted from the CPU to the output relay of the B7A Interface Unit should be set to a value larger than the minimum input time. 2. The value of the external power supply does not include the value required by the B7A Link Terminal.
178
Page 186
Appendix B
Specifications
Group-2 B7A Interface Units (C200H-B7Ajj) A Group-2 B7A Interface Unit used with two or four B7A Link Terminals allows the transmission and reception of 32-point or 64-point I/O data over two-conductor cables. Group-2 B7A Interface Unit
C200HS CPU
Input B7A Link Terminal
Sensor Switch
Transmission distance: 500 m max.
Output B7A Link Terminal
Lamps and other loads
Group-2 B7A Interface Units can be mounted to a CPU Rack or an Expansion I/O Rack. They cannot be mounted to Slave Racks or to Racks controlled by any other CPUs. The words allocated to Group-2 B7A Interface Units are determined by I/O number set on the Units. Units with 32 I/O points are allocated two words; Units with 64 I/O points are allocated four words. Refer to the B7A Link Terminals Datasheet for more information on B7A Link Terminals.
Models The following Group-2 B7A Interface Units are available. B7A Interface Unit
Inputs
Outputs
C200H-B7A12
32 points
None
C200H-B7A02
None
32 points
C200H-B7A21
16 points
16 points
C200H-B7A22
32 points
32points
179
Page 187
Appendix B
Specifications
Connectable B7A Link Terminals Only 16-point B7A Link Terminals can be connected to a B7A Interface Unit. Input Terminals Type Screw terminals
Modular PC connectors
Model B7A-T6j1 B7AS-T6j1 B7A-T6j6 B7AS-T6j6 B7A-T6D2 B7A-T6D7 B7A-TjE3 B7A-TjE8
Transmission delay Standard (19.2 ms) High-speed (3 ms) Standard (19.2 ms) High-speed (3 ms) Standard (19.2 ms) High-speed (3 ms)
Output Terminals Type Screw terminals
Modular PC connectors
Model B7A-R6jj1 B7AS-R6jj1 B7A-R6jj6 B7AS-R6jj6 B7A-R6A52 B7A-R6A57 B7A-RjAj3 B7A-RjAj8
Transmission delay Standard (19.2 ms) High-speed (3 ms) Standard (19.2 ms) High-speed (3 ms) Standard (19.2 ms) High-speed (3 ms)
Note 1. Do not connect Terminals with different transmission delays to the same Interface Unit. Doing so will cause a transmission error. 2. The 10-point B7A Link Terminals and mixed-I/O B7A Link Terminals with 8 inputs and 8 outputs cannot be connected to B7A Interface Units. Use 16-point B7A Link Terminals. The 16-point B7A Link Terminals include 16-point (non-mixed) Terminals, 32-point Terminals configured with two 16-point circuits, and mixed-I/O Terminals with 16 inputs and 16 outputs.
Comparison between Standard and Group-2 B7A Interface Units Type
Standard
Models
C200H-B7AI1 C200H-B7AO2
Group-2
C200H-B7A12 C200H-B7A02 C200H-B7A21 C200H-B7A22
Word allocations
Same as I/O Units (in order mounted). Words 030 to 049 allocated according to I/O number setting (same as Group-2 High-density I/O Units)
Connectable B7A Link Terminals Transmission Transmission Points delay errors Standard Input status 16-point types only held Terminals only automatically (see note 2) (19.2 ms) Standard (19.2 ms) and high-speed (3 ms) types (set via switch)
Switch setting to hold or reset Input status.
Note 1. Mount the C200H-B7AO1 B7A Interface Unit to the C200H-BCjj1-V1 or C200H-BCjj1-V2 Backplane. 2. The 10-point B7A Link Terminals and mixed-I/O B7A Link Terminals with 8 inputs and 8 outputs cannot be connected to B7A Interface Units. The 16-point (non-mixed) Terminals, 32-point Terminals configured with the two 16-point circuits, and mixed-I/O Terminals with 16 inputs and 16 outputs can be connected.
180
Page 188
Appendix B
Specifications
Parts and Names (C200H-B7A22 shown below) Front
I/O number switch This switch determines the words allocated to the Unit. Status indicators The indicators depend on the model of B7A Interface Unit.
Connection terminals Connect to the SIG terminal of the B7A Link Terminal and to the negative power terminal of the B7A Link Terminal. The actual use of these terminals depends on the B7A Interface Unit.
External Power Supply Terminals Supply 12 to 24 VDC.
12 VDC 12toto2424 VDC
Back
DIP switch Used to set the transmission delay, transmission error processing mode, input mode, and ERROR indicator operation.
181
Page 189
Appendix B
Specifications
Indicator Operation The indicators depend on the model of B7A Interface Unit, as shown below.
Name
Color
Function
ERROR 1 ERROR 2 ERROR
Input transmission error
Red
Lights when an error occurs in transmissions from an Input B7A Link Terminal. For the B7A12/22, ERROR 1 is for the first word allocated to the B7A Interface Unit; ERROR 2 is for the second word.
3ms
Transmission delay setting
Orange
Lit when the transmission delay is set to the high-speed setting (3 ms).
Transmission error process
Orange
Input mode setting
Orange
LOAD OFF 15IN+ERR
Not lit when the transmission delay is set to the standard setting (19.2 ms). Lit when the processing for transmission errors is set to reset input status. Not lit when the processing for transmission errors is set to hold input status. Lit when the input mode mode is set to use 15 inputs and 1 error input. Not lit when the input mode mode is set to use 16 inputs.
I/O Number Setting The setting of the I/O number determines the words allocated to the Interface Unit. Set the I/O number to between 0 and 9.
Setting in direction of notch
Note 1. Turn off the power supply to the PC before changing the I/O number setting. Any new setting will not be effective until the next time the power supply is turned on. 2. Use a flat-blade screw driver to change the I/O number setting. Be careful not to leave the switch halfway between settings and be careful not to damage the switch. The following table shows the words allocated according to the I/O number. The 32-point Units are the C200H-B7A12, C200H-B7A02, and C200H-B7A21. The 64-point Unit is the C200H-B7A22. Words
I/O No. 0
32-point Units IR 030 and IR 031
64-point Unit IR 030 to IR 033
1
IR 032 and IR 033
IR 032 to IR 035
2
IR 034 and IR 035
IR 034 to IR 037
3
IR 036 and IR 037
IR 036 to IR 039
4
IR 038 and IR 039
IR 038 to IR 041
5
IR 040 and IR 041
IR 040 to IR 043
6
IR 042 and IR 043
IR 042 to IR 045
7
IR 044 and IR 045
IR 044 to IR 047
8
IR 046 and IR 047
IR 046 to IR 049
9
IR 048 and IR 049
Do not use.
Note 1. Be sure that the same words are not allocated to more than one Unit. For example, if you set a 64-point Unit to I/O number 0, you cannot use I/O number 1 for any Unit. 2. The above words are also allocated to Group-2 High-density I/O Units. Be sure that the same words are not allocated to more than one Unit.
182
Page 190
Appendix B
Specifications
DIP Switch Settings Set the DIP switch as described before for the various models of B7A Interface Units. C200H-B7A22/12 Pin
Factory setting (pins 4 and 5 ON)
Function
OFF
ON
1
Transmission delay
Standard (19.2 ms)
High-speed (3 ms)
2
Transmission error process
Hold status
Reset Inputs
3
Input mode
16 inputs
15 inputs + error input
4
ERROR 1 indicator enable
Disabled
Enabled
5
ERROR 2 indicator enable
Disabled
Enabled
6
Not used.
NA
NA
C200H-B7A21 Pin
Factory setting (pin 5 ON)
Function
OFF
ON
1
Transmission delay
Standard (19.2 ms)
High-speed (3 ms)
2
Transmission error process
Hold status
Reset Inputs
3
Input mode
16 inputs
15 inputs + error input
4
ERROR indicator enable
Disabled
Enabled
5
Not used.
NA
NA
6
Not used.
NA
NA
C200H-B7A02 Pin
Factory setting (all pins OFF)
Function
OFF
ON
1
Transmission delay
Standard (19.2 ms)
High-speed (3 ms)
2
Not used.
NA
NA
3
Not used.
NA
NA
4
Not used.
NA
NA
5
Not used.
NA
NA
6
Not used.
NA
NA
Transmission Delay Pin 1 is used to set the transmission delay. The same delay is used for all words allocated to the Unit. Set the transmission delay to match that of the B7A Link Terminal. A transmission error will occur if the same transmission delay is not set. The “3ms” indicator will be lit whenever the high-speed (3 ms) transmission delay is set. Transmission Error Process Pin 2 is used to turned ON to specify resetting input status when transmission errors occur. If pin 2 is turned OFF, input status will be held when transmission errors occur. The LOAD OFF indicator will be lit whenever pin 2 is turned ON. Input Mode Pin 3 is turned ON to specify use of only 15 inputs and the use of bit 15 as a Transmission Error Flag. If pin 3 is OFF, 16 normal inputs can be used. The “15IN+ERR” indicator will be lit whenever pin 3 is turned ON. ERROR Indicators Pin 4 or pins 4 and 5 are turned ON to enable the ERROR, ERROR 1, and/or ERROR 2 indicators. These indicators will not light even if a transmission error occurs if the corresponding pin is turned OFF.
183