SYSMAC C200HS Programmable Controllers Installation Guide, pages 191 to 200

Pages 191 to 200 of 221

The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron C200H-OC225 and Omron C200HW-SLK23

Page 191

Specifications

Appendix B

Transmission Error Precautions Startup The Transmission Error Flag for the B7A Interface Unit will be OFF when power is turned on to the C200HS. If normal transmissions with the B7A Link Terminal are not possible within about 10 ms, the Transmission Error Flag (bit 15) will turn ON (i.e., if its operation is enabled by the input mode setting). All input bits will remain OFF until normal transmissions are achieved. Inputs When a transmission error occurs, input status will be either held or all inputs will be reset according to the setting for the transmission error process, and the Transmission Error Flag (bit 15) will turn ON (i.e., if its operation is enabled by the input mode setting). The Transmission Error Flag will go OFF and the input status will return to normal when normal transmissions are achieved again. Outputs Transmission errors for Output B7A Link Terminals are not detected at the B7A Interface Unit and must be confirmed using the error indicators or error outputs on the Link Terminal.

184

Page 192

Appendix B

Specifications

Wiring Terminal Names and Allocations The use of the terminals depends on the model of the B7A Interface Unit. “m” indicates the first word allocated to the Unit according to the I/O number setting and can be calculated as follows: m = 030 + (2 x I/O number) C200H-B7A22 Terminal

Name

Function

B0 B1

SIG OUT1 – OUT1

B2 B3

SIG OUT2 – OUT2

B4 B5

SIG IN1 – IN1

B6 B7

SIG IN2 – IN2

B8 A0 to A7 B9 A8

NC

Connect to SIG terminal on Output B7A Link Terminal. Connect to – power supply terminal on Output B7A Link Terminal. Connect to SIG terminal on Output B7A Link Terminal. Connect to – power supply terminal on Output B7A Link Terminal. Connect to SIG terminal on Input B7A Link Terminal. Connect to – power supply terminal on Input B7A Link Terminal. Connect to SIG terminal on Input B7A Link Terminal. Connect to – power supply terminal on Input B7A Link Terminal. Not used.

+V –V

Connect to + terminal on external power supply. Connect to – terminal on external power supply.

Word m m+1 m+2 m+3

NA

C200H-B7A21 Name

Function

B0 B1

Terminal

SIG OUT1 – OUT1

B2, B3

NC

Connect to SIG terminal on Output B7A Link Terminal. Connect to – power supply terminal on Output B7A Link Terminal. Not used.

B4 B5

SIG IN1 – IN1

B6 to B8 A0 to A7 B9 A8

NC

Connect to SIG terminal on Input B7A Link Terminal. Connect to – power supply terminal on Input B7A Link Terminal. Not used.

+V –V

Connect to + terminal on external power supply. Connect to – terminal on external power supply.

Word m

NA m+1

NA

C200H-B7A12 Terminal

Name

Function

B0 B1

SIG IN1 – IN1

Connect to SIG terminal on Input B7A Link Terminal. Connect to – power supply terminal on Input B7A Link Terminal. Not used.

B2, B3

NC

B4 B5

SIG IN2 – IN2

B6 to B8 A0 to A7 B9 A8

NC

Connect to SIG terminal on Input B7A Link Terminal. Connect to – power supply terminal on Input B7A Link Terminal. Not used.

+V –V

Connect to + terminal on external power supply. Connect to – terminal on external power supply.

Word m

NA m+1

NA

185

Page 193

Appendix B

Specifications C200H-B7A02 Terminal

Name

Function

B0 B1

SIG OUT1 – OUT1

B2, B3

NC

Connect to SIG terminal on Output B7A Link Terminal. Connect to – power supply terminal on Output B7A Link Terminal. Not used.

B4 B5

SIG OUT2 – OUT2

B6 to B8 A0 to A7 B9 A8

NC

Connect to SIG terminal on Output B7A Link Terminal. Connect to – power supply terminal on Output B7A Link Terminal. Not used.

+V –V

Connect to + terminal on external power supply. Connect to – terminal on external power supply.

Word m

NA m+1

NA

Recommended Cables and Transmission Distance The following cables are recommended to connect the B7A Interface Unit to B7A Link Terminals. The wiring method and transmission distance depend on the transmission delay and on whether or not a common power supply is being used for the B7A Link Terminal and the Interface Unit. Standard Transmission Delays (19.2 ms): Cab-tire Cable Power supply

Cable

Transmission distance

Common

VCTF, 0.75 mm2 x 3 conductors

100 m max.

Separate

VCTF ,0.75 mm2 x 2 conductors

500 m max.

High-speed Transmission Delays (3 ms): Shielded Cable Power supply

Cable

Transmission distance

Common

Shielded cable, 0.75 mm2 x 3 conductors

50 m max.

Separate

Shielded cable, 0.75 mm2 x 2 conductors

100 m max.

Terminal Construction Use hook-type crimp connectors with a line thickness of 0.25 to 1.65 mm2. The construction of the terminals is shown in the illustration.

Wiring Method Standard Transmission Delays (19.2 ms) Common Power Supply B7A Link Terminal

B7A Interface Unit

Transmission distance: 100 m max. B7A Link Terminal

Transmission cable: VCTF 0.75 mm2 or higher 24 VDC±10%

186

Page 194

Appendix B

Specifications Separate Power Supplies

B7A Link Terminal

B7A Interface Unit 12 to 24 VDC Transmission distance: 500 m max.

B7A Link Terminal 12 to 24 VDC

Transmission cable: VCTF 0.75 mm2 or higher 12 to 24 VDC

High-speed Transmission Delays (3 ms): Shielded Cable B7A Link Terminal

Common Power Supply B7A Interface Unit

Transmission distance: 50 m max.

B7A Link Terminal Shielded cable: 0.75 mm2 or higher GND

Shielded cable: 0.75 mm2 or higher 24 VDC±10%

GND

Separate Power Supplies

B7A Link Terminal

B7A Interface Unit 12 to 24 VDC Transmission distance: 100 m max.

Shielded cable: 0.75 mm2 or higher

B7A Link Terminal

GND 12 to 24 VDC

12 to 24 VDC

Shielded cable: 0.75 mm2 or higher GND

Note 1. We recommend grounding the shielded cable. 2. If shielded cable is not used, the maximum transmission distance is 10 m regardless of whether a common or separate power supplies are used. Use 0.75 mm2 or higher VCTF cable. 3. To prevent noise on the transmission cable, do not lay it near power cables or high-voltage lines.

187

Page 195

Appendix B

Specifications

Specifications Item

C200H-B7A12

C200H-B7A02

I/O points

32 input points or 30 input points and 2 error inputs

32 output points

Transmission method Transmission distance (see note 1)

One-way distributed multiplex transmission Standard:

500 m max.

High-speed:

100 m max.

Transmission delay

Standard:

Typ. 19.2 ms, 31 ms max.

High-speed:

Typ. 3 ms, 5 ms max.

Minimum input time (see note 2)

Standard:

16 ms

High-speed:

2.4 ms

Internal current consumption External power supply (see note 3)

5 VDC, 100 mA max.

Weight

300 g max.

Dimensions

35 x 130 x 128 mm (W x H x D)

C200H-B7A21

C200H-B7A22

16 output points and 16 input points or 15 input points + 1 error input

32 output points and 32 input points or 30 input points + 2 error inputs

0.05 A min.

0.08 A min.

12 to 24 VDC ±10% 0.05 A min.

0.06 A min.

Note 1. The transmission distance also depends on whether a common or separate power supplies are used. 2. The minimum input time refers to the minimum time required for reading the input signals from the CPU. The ON/OFF width of the signal transmitted from the CPU to the output relay of the B7A Interface Unit should be set to a value larger than the minimum input time. 3. The capacity of the external power supply does not include the capacity required by the B7A Link Terminal.

Maximum Current and Power Supplied There are limits to the current and power that can be supplied to each Rack and Unit. When designing the system, take the current consumption into account. Follow the chart below and be careful that the total current consumption does not exceed the maximum current and maximum total power supplied. Current Supplied Name

Model number

Max. current supplied 5V (internal logic current)

CPU Rack

Expansion I/O Rack Slave Rack

188

26 V (relay drive current)

Maximum power supplied

24 V (No-voltage contact current)

C200HS-CPU01-E/ CPU01-EC/CPU21-E/ CPU21-EC/CPU31-E

3.9 A

0.6 A

0.8 A

23.5 to 26.5 W (See conditions below.)

C200HS-CPU03-E/ CPU23-E/CPU33-E C200H-PS221/ PS221-C C200H-PS211 C200H-RT001-P

2.3 A

0.6 A

---

21.5 W

2.7 A

0.6 A

0.8 A

28 W

0.6 A

--0.8 A

23 W 28 W

C200H-RT002-P

---

23 W

C200H-RT201

0.8 A

28 W

C200H-RT202

---

23 W

2.7 A

Page 196

Appendix B

Specifications

Note The figures shown in the “maximum current supplied” and “maximum power supplied” columns are computed with the power consumed by the Backplanes, CPU, Memory Cassettes, Peripheral Devices, I/O Power Supply Units, and Slave Units already calculated. Design the system so that the following conditions are satisfied. Condition 1 (1) (Total current consumption of all Units in the 5-V system) ≤ (the figure in the 5-V column) (2) (Total current consumption of all Units in the 26-V system) ≤ (the figure in the 26-V column) (3) (Total current consumption of all Units in the 24-V system) ≤ (the figure in the 24-V column) Condition 2 (1) x 5 V + (2) x 26 V + (3) x 24 ≤ (maximum power supplied) In the C200HS-CPU01-E/CPU01-EC/CPU21-E/CPU21-EC/CPU31-E, the maximum power drawn from the 5-V power supply depends upon the current consumption, as shown below. Max. Power vs. Current Supplied C200HS-CPU01-E/CPU01-EC/CPU21-E/CPU21-EC/CPU31-E (W)

Total Power Consumption (W)

26.5 23.5

0 0

2.3

3.9 (A)

Current Drawn from 5-V Supply (A)

Calculating Current and Power Consumption The method of calculating current and power consumption is demonstrated here using the following Unit combinations as examples. Example 1: Units Mounted to C200HS-CPU01-E CPU Rack OC221 Contact Output Units: 4 Units ID001 No-voltage Input Units: 3 Units LK202 Host Link Unit: 1 Unit External power supply used: 0.3 A Current Consumption Power Consumption Power Supply 5-V system 0.001 x 7 + 0.25 = 0.32 A (≤ 3.9 A) 0.32 A x 5 V = 1.6 W 26-V system 0.075 x 4 = 0.30 A (≤ 0.6 A) 0.30 A x 26 V = 7.8 W 24-V system 0.06 x 3 + 0.3 = 0.48 A (≤ 0.8 A) 0.48 A x 24 V = 11.52 W Total = 20.92 W (≤ 26.5 W) Example 2: Units Mounted to C200H-PS221 Expansion I/O Rack ID212 DC Input Units: 6 Units CT002 High-speed Counter Units: 2 Units External power supply used (for ID212): 0.8 A Current Consumption Power Consumption Power Supply 5-V system 0.01 x 6 + 0.3 x 2 = 0.66 A (≤ 2.7 A) 0.66 A x 5 V = 3.3 W 26-V system 0 0 24-V system Ext. power supply = 0.8 A (≤ 0.8 A) 0.8 A x 24 V = 19.2 W

189

Page 197

Appendix B

Specifications Total = 22.5 W (≤ 28 W) Example 3: Units Mounted to C200HS-CPU01-E CPU Rack OC221 Contact Output Units: 4 Units ID217 High-density Input Unit: 1 Unit OD219 High-density Output Unit: 1 Unit CT002 High-speed Counter Unit: 1 Unit External power supply used (for ID217): 0.3 A Current Consumption 0.01 x 4 + 0.12 + 0.27 +0.3 = 0.73 A (≤ 3.9 A) 0.075 x 4 = 0.30 A (≤ 0.6 A) Ext. power supply = 0.8 A (≤ 0.8 A)

Power Supply 5-V system 26-V system 24-V system

Power Consumption 0.73 A x 5 V = 3.65 W 0.3 A x 26 V = 7.8 W 0.8 A x 24 V = 19.2 W

Total = 18.65 W (≤ 26.5 W) Calculating Power Consumption for Racks The total power consumption (primary power input) for an individual Rack can be broadly calculated as shown in the following examples. Example 1: CPU Rack

Total power consumption of Units + 3.5 0.6 x 0.55 (1) (VA) 3.5 = CPU power consumption 0.6 = 60% efficiency 0.55 (1) = Power rate (Number in parentheses: when CPU03 is used.) Example 2: All Other Racks

Total power consumption of Units + 2 0.6 x 0.55 (1) (VA) 2 = I/O Power Supply Unit (Remote I/O Slave Unit) power consumption 0.6 = 60% efficiency 0.55 (1) = Power rate (Number in parentheses: when PS211, RT002-P or RT202 is used.) Current Drawn from 5-V Supply (Standard I/O Units)

Unit DC Input

Model number C200H-ID211

Current consumption 0.01 A each

C200H-ID212 No-Voltage Contact

C200H-ID001

Input

C200H-ID002

AC Input

C200H-IA121 C200H-IA122/IA122V C200H-IA221 C200H-IA222/IA222V

AC/DC Input

C200H-IM211 C200H-IM212

Contact Output

C200H-OC221 C200H-OC222 C200H-OC223 C200H-OC224

190

C200H-OC225

0.05 A

C200H-OC222V

0.008 A

C200H-OC224V

0.01 A

C200H-OC226

0.03 A

Page 198

Appendix B

Specifications Unit Transistor Output

Model number C200H-OD411

Current consumption 0.14 A

C200H-OD211

0.16 A

C200H-OD212

0.18 A

C200H-OD213

0.14 A

C200H-OD214 C200H-OD216

0.01 A each

C200H-OD217 C200H-OD21A

0.16 A

Analog Timer

C200H-OA121-E C200H-OA122-E C200H-OA221 C200H-OA223 C200H-OA222V C200H-OA224 C200H-TM001

0.14 A 0.18 A 0.14 A 0.18 A 0.20 A 0.27 A 0.06 A

Standard B7A Interface

C200H-B7AI1

0.10 A

Triac Output

C200H-B7AO1 Interrupt Input

Current Drawn from 5-V Supply for Group-2 High-density I/O Units

Unit DC Input

Transistor Output

Current Drawn from 5-V Supply for Group-2 B7A Interface Units

Unit B7A Interface Unit (Group-2 Units)

Current Drawn from 5-V Supply for Special I/O Units

Unit

C200HS-INT01 Model number C200H-ID111 C200H-ID216 C200H-ID217 C200H-ID218 C200H-ID219 C200H-OD218 C200H-OD219 C200H-OD21B Model number C200H-B7A12/02 C200H-B7A21/22 Model number

TTL Input

C200H-ID501

DC Input

C200H-ID215

TTL Output

C200H-OD501

Transistor Output

C200H-OD215

TTL I/O

C200H-MD501

DC Input/Transistor

C200H-MD115

Output

C200H-MD215

High-speed Counter

C200H-CT001-V1

0.02 A Current consumption 0.12 A 0.1 A 0.12 A 0.1 A 0.12 A 0.18 A 0.27 A 0.18 A Current consumption 0.10 A

Current consumption 0.13 A 0.22 A 0.18 A

0.30 A

C200H-CT002 Position Control

Analog Input

C200H-NC111 C200H-NC112 C200H-NC211

0.15 A

C200H-AD001

0.55 A

C200H-AD002

0.45 A

0.50 A

191

Page 199

Appendix B

Specifications Unit Analog Output Temperature Control

Model number C200H-DA001

Current consumption 0.65 A

C200H-DA002

0.60 A

C200H-TC001 C200H-TC002 C200H-TC003

0.33 A

C200H-TC101 C200H-TC102 C200H-TC103 Heat/Cool Temperature Control

C200H-TV001 C200H-TV002 C200H-TV003

0.33 A

C200H-TV101 C200H-TV102 C200H-TV103 PID Control

C200H-PID01 C200H-PID02 C200H-PID03

0.33 A

Temperature Sensor Input ASCII

C200H-TS001/TS002 C200H-TS101/TS102 C200H-ASC02

0.45 A

Voice Output

C200H-OV001

0.30 A

ID Sensor

C200H-IDS01-V1

0.25 A

0.20 A

C200H-IDS21 Fuzzy Logic

C200H-FZ001

0.30 A

Cam Positioner

C200H-CP114

0.30 A

Current Drawn from 5-V Supply for Other Units

Unit

C200H-LK101-PV1

Current consumption 0.25 A

C200H-LK201-V1

0.15 A

C200H-LK202-V1

0.25 A

PC Link

C200H-LK401

0.35 A

Remote Master

C200H-RM001-PV1

0.20 A

C200H-RM201

0.25 A 0.80 A

SYSMAC NET Link

C200HW-SLK13/SLK14/SLK23/ SLK24 C200HS-SNT32

Power Supply Adapter

C200H-APS01/APS02/APS03

0A

CompoBus/S Master

C200HW-SRM21

0.15 A

DeviceNet Master

C200HW-DRM21

0.25 A

Host Link

SYSMAC LINK

192

Model number

1.00 A

Page 200

Appendix B

Specifications Current Drawn from 26-V Supply

Unit

Model number

Contact Output

C200H-OC221/OC222/OC223/ OC224/OC225

Current consumption 0.075 A/8 points that turn ON simultaneously

C200H-OC222V/OC224V/ OC226

0.09 A/8 points that turn ON simultaneously

Transistor Output

C200H-OD216/OD217

0.075 A/8 points that turn ON simultaneously

ID Sensor

C200H-IDS01-V1/IDS21

0.12 A

Current Drawn from 24-V Supply

Unit

Model number

No-Voltage Contact Input

Current consumption 0.06 A each

C200H-ID001/ID002

Dimensions Racks The dimensions shown below are for both the CPU Rack and Expansion I/O Rack. The C dimension for the Programming Console will increase by 30mm when the Programming Console Adapter C200H-BP001 is used, and will increase by 50 mm when the Programming Console Adapter C200H-BP002 is used. CPU

130

A B

138

Model C200HS-CPU01-E/CPU01-EC/ CPU03-E C200HS-CPU21-E/CPU21-EC/ CPU23-E/CPU31-E/CPU33-E

A (mm)

B (mm)

Weight (kg)

101

113

1.4

126

138

1.5

Memory Cassette

73.2

44

9.1

193