Page 191
Specifications
Appendix B
Transmission Error Precautions Startup The Transmission Error Flag for the B7A Interface Unit will be OFF when power is turned on to the C200HS. If normal transmissions with the B7A Link Terminal are not possible within about 10 ms, the Transmission Error Flag (bit 15) will turn ON (i.e., if its operation is enabled by the input mode setting). All input bits will remain OFF until normal transmissions are achieved. Inputs When a transmission error occurs, input status will be either held or all inputs will be reset according to the setting for the transmission error process, and the Transmission Error Flag (bit 15) will turn ON (i.e., if its operation is enabled by the input mode setting). The Transmission Error Flag will go OFF and the input status will return to normal when normal transmissions are achieved again. Outputs Transmission errors for Output B7A Link Terminals are not detected at the B7A Interface Unit and must be confirmed using the error indicators or error outputs on the Link Terminal.
184
Page 192
Appendix B
Specifications
Wiring Terminal Names and Allocations The use of the terminals depends on the model of the B7A Interface Unit. “m” indicates the first word allocated to the Unit according to the I/O number setting and can be calculated as follows: m = 030 + (2 x I/O number) C200H-B7A22 Terminal
Name
Function
B0 B1
SIG OUT1 – OUT1
B2 B3
SIG OUT2 – OUT2
B4 B5
SIG IN1 – IN1
B6 B7
SIG IN2 – IN2
B8 A0 to A7 B9 A8
NC
Connect to SIG terminal on Output B7A Link Terminal. Connect to – power supply terminal on Output B7A Link Terminal. Connect to SIG terminal on Output B7A Link Terminal. Connect to – power supply terminal on Output B7A Link Terminal. Connect to SIG terminal on Input B7A Link Terminal. Connect to – power supply terminal on Input B7A Link Terminal. Connect to SIG terminal on Input B7A Link Terminal. Connect to – power supply terminal on Input B7A Link Terminal. Not used.
+V –V
Connect to + terminal on external power supply. Connect to – terminal on external power supply.
Word m m+1 m+2 m+3
NA
C200H-B7A21 Name
Function
B0 B1
Terminal
SIG OUT1 – OUT1
B2, B3
NC
Connect to SIG terminal on Output B7A Link Terminal. Connect to – power supply terminal on Output B7A Link Terminal. Not used.
B4 B5
SIG IN1 – IN1
B6 to B8 A0 to A7 B9 A8
NC
Connect to SIG terminal on Input B7A Link Terminal. Connect to – power supply terminal on Input B7A Link Terminal. Not used.
+V –V
Connect to + terminal on external power supply. Connect to – terminal on external power supply.
Word m
NA m+1
NA
C200H-B7A12 Terminal
Name
Function
B0 B1
SIG IN1 – IN1
Connect to SIG terminal on Input B7A Link Terminal. Connect to – power supply terminal on Input B7A Link Terminal. Not used.
B2, B3
NC
B4 B5
SIG IN2 – IN2
B6 to B8 A0 to A7 B9 A8
NC
Connect to SIG terminal on Input B7A Link Terminal. Connect to – power supply terminal on Input B7A Link Terminal. Not used.
+V –V
Connect to + terminal on external power supply. Connect to – terminal on external power supply.
Word m
NA m+1
NA
185
Page 193
Appendix B
Specifications C200H-B7A02 Terminal
Name
Function
B0 B1
SIG OUT1 – OUT1
B2, B3
NC
Connect to SIG terminal on Output B7A Link Terminal. Connect to – power supply terminal on Output B7A Link Terminal. Not used.
B4 B5
SIG OUT2 – OUT2
B6 to B8 A0 to A7 B9 A8
NC
Connect to SIG terminal on Output B7A Link Terminal. Connect to – power supply terminal on Output B7A Link Terminal. Not used.
+V –V
Connect to + terminal on external power supply. Connect to – terminal on external power supply.
Word m
NA m+1
NA
Recommended Cables and Transmission Distance The following cables are recommended to connect the B7A Interface Unit to B7A Link Terminals. The wiring method and transmission distance depend on the transmission delay and on whether or not a common power supply is being used for the B7A Link Terminal and the Interface Unit. Standard Transmission Delays (19.2 ms): Cab-tire Cable Power supply
Cable
Transmission distance
Common
VCTF, 0.75 mm2 x 3 conductors
100 m max.
Separate
VCTF ,0.75 mm2 x 2 conductors
500 m max.
High-speed Transmission Delays (3 ms): Shielded Cable Power supply
Cable
Transmission distance
Common
Shielded cable, 0.75 mm2 x 3 conductors
50 m max.
Separate
Shielded cable, 0.75 mm2 x 2 conductors
100 m max.
Terminal Construction Use hook-type crimp connectors with a line thickness of 0.25 to 1.65 mm2. The construction of the terminals is shown in the illustration.
Wiring Method Standard Transmission Delays (19.2 ms) Common Power Supply B7A Link Terminal
B7A Interface Unit
Transmission distance: 100 m max. B7A Link Terminal
Transmission cable: VCTF 0.75 mm2 or higher 24 VDC±10%
186
Page 194
Appendix B
Specifications Separate Power Supplies
B7A Link Terminal
B7A Interface Unit 12 to 24 VDC Transmission distance: 500 m max.
B7A Link Terminal 12 to 24 VDC
Transmission cable: VCTF 0.75 mm2 or higher 12 to 24 VDC
High-speed Transmission Delays (3 ms): Shielded Cable B7A Link Terminal
Common Power Supply B7A Interface Unit
Transmission distance: 50 m max.
B7A Link Terminal Shielded cable: 0.75 mm2 or higher GND
Shielded cable: 0.75 mm2 or higher 24 VDC±10%
GND
Separate Power Supplies
B7A Link Terminal
B7A Interface Unit 12 to 24 VDC Transmission distance: 100 m max.
Shielded cable: 0.75 mm2 or higher
B7A Link Terminal
GND 12 to 24 VDC
12 to 24 VDC
Shielded cable: 0.75 mm2 or higher GND
Note 1. We recommend grounding the shielded cable. 2. If shielded cable is not used, the maximum transmission distance is 10 m regardless of whether a common or separate power supplies are used. Use 0.75 mm2 or higher VCTF cable. 3. To prevent noise on the transmission cable, do not lay it near power cables or high-voltage lines.
187
Page 195
Appendix B
Specifications
Specifications Item
C200H-B7A12
C200H-B7A02
I/O points
32 input points or 30 input points and 2 error inputs
32 output points
Transmission method Transmission distance (see note 1)
One-way distributed multiplex transmission Standard:
500 m max.
High-speed:
100 m max.
Transmission delay
Standard:
Typ. 19.2 ms, 31 ms max.
High-speed:
Typ. 3 ms, 5 ms max.
Minimum input time (see note 2)
Standard:
16 ms
High-speed:
2.4 ms
Internal current consumption External power supply (see note 3)
5 VDC, 100 mA max.
Weight
300 g max.
Dimensions
35 x 130 x 128 mm (W x H x D)
C200H-B7A21
C200H-B7A22
16 output points and 16 input points or 15 input points + 1 error input
32 output points and 32 input points or 30 input points + 2 error inputs
0.05 A min.
0.08 A min.
12 to 24 VDC ±10% 0.05 A min.
0.06 A min.
Note 1. The transmission distance also depends on whether a common or separate power supplies are used. 2. The minimum input time refers to the minimum time required for reading the input signals from the CPU. The ON/OFF width of the signal transmitted from the CPU to the output relay of the B7A Interface Unit should be set to a value larger than the minimum input time. 3. The capacity of the external power supply does not include the capacity required by the B7A Link Terminal.
Maximum Current and Power Supplied There are limits to the current and power that can be supplied to each Rack and Unit. When designing the system, take the current consumption into account. Follow the chart below and be careful that the total current consumption does not exceed the maximum current and maximum total power supplied. Current Supplied Name
Model number
Max. current supplied 5V (internal logic current)
CPU Rack
Expansion I/O Rack Slave Rack
188
26 V (relay drive current)
Maximum power supplied
24 V (No-voltage contact current)
C200HS-CPU01-E/ CPU01-EC/CPU21-E/ CPU21-EC/CPU31-E
3.9 A
0.6 A
0.8 A
23.5 to 26.5 W (See conditions below.)
C200HS-CPU03-E/ CPU23-E/CPU33-E C200H-PS221/ PS221-C C200H-PS211 C200H-RT001-P
2.3 A
0.6 A
---
21.5 W
2.7 A
0.6 A
0.8 A
28 W
0.6 A
--0.8 A
23 W 28 W
C200H-RT002-P
---
23 W
C200H-RT201
0.8 A
28 W
C200H-RT202
---
23 W
2.7 A
Page 196
Appendix B
Specifications
Note The figures shown in the “maximum current supplied” and “maximum power supplied” columns are computed with the power consumed by the Backplanes, CPU, Memory Cassettes, Peripheral Devices, I/O Power Supply Units, and Slave Units already calculated. Design the system so that the following conditions are satisfied. Condition 1 (1) (Total current consumption of all Units in the 5-V system) ≤ (the figure in the 5-V column) (2) (Total current consumption of all Units in the 26-V system) ≤ (the figure in the 26-V column) (3) (Total current consumption of all Units in the 24-V system) ≤ (the figure in the 24-V column) Condition 2 (1) x 5 V + (2) x 26 V + (3) x 24 ≤ (maximum power supplied) In the C200HS-CPU01-E/CPU01-EC/CPU21-E/CPU21-EC/CPU31-E, the maximum power drawn from the 5-V power supply depends upon the current consumption, as shown below. Max. Power vs. Current Supplied C200HS-CPU01-E/CPU01-EC/CPU21-E/CPU21-EC/CPU31-E (W)
Total Power Consumption (W)
26.5 23.5
0 0
2.3
3.9 (A)
Current Drawn from 5-V Supply (A)
Calculating Current and Power Consumption The method of calculating current and power consumption is demonstrated here using the following Unit combinations as examples. Example 1: Units Mounted to C200HS-CPU01-E CPU Rack OC221 Contact Output Units: 4 Units ID001 No-voltage Input Units: 3 Units LK202 Host Link Unit: 1 Unit External power supply used: 0.3 A Current Consumption Power Consumption Power Supply 5-V system 0.001 x 7 + 0.25 = 0.32 A (≤ 3.9 A) 0.32 A x 5 V = 1.6 W 26-V system 0.075 x 4 = 0.30 A (≤ 0.6 A) 0.30 A x 26 V = 7.8 W 24-V system 0.06 x 3 + 0.3 = 0.48 A (≤ 0.8 A) 0.48 A x 24 V = 11.52 W Total = 20.92 W (≤ 26.5 W) Example 2: Units Mounted to C200H-PS221 Expansion I/O Rack ID212 DC Input Units: 6 Units CT002 High-speed Counter Units: 2 Units External power supply used (for ID212): 0.8 A Current Consumption Power Consumption Power Supply 5-V system 0.01 x 6 + 0.3 x 2 = 0.66 A (≤ 2.7 A) 0.66 A x 5 V = 3.3 W 26-V system 0 0 24-V system Ext. power supply = 0.8 A (≤ 0.8 A) 0.8 A x 24 V = 19.2 W
189
Page 197
Appendix B
Specifications Total = 22.5 W (≤ 28 W) Example 3: Units Mounted to C200HS-CPU01-E CPU Rack OC221 Contact Output Units: 4 Units ID217 High-density Input Unit: 1 Unit OD219 High-density Output Unit: 1 Unit CT002 High-speed Counter Unit: 1 Unit External power supply used (for ID217): 0.3 A Current Consumption 0.01 x 4 + 0.12 + 0.27 +0.3 = 0.73 A (≤ 3.9 A) 0.075 x 4 = 0.30 A (≤ 0.6 A) Ext. power supply = 0.8 A (≤ 0.8 A)
Power Supply 5-V system 26-V system 24-V system
Power Consumption 0.73 A x 5 V = 3.65 W 0.3 A x 26 V = 7.8 W 0.8 A x 24 V = 19.2 W
Total = 18.65 W (≤ 26.5 W) Calculating Power Consumption for Racks The total power consumption (primary power input) for an individual Rack can be broadly calculated as shown in the following examples. Example 1: CPU Rack
Total power consumption of Units + 3.5 0.6 x 0.55 (1) (VA) 3.5 = CPU power consumption 0.6 = 60% efficiency 0.55 (1) = Power rate (Number in parentheses: when CPU03 is used.) Example 2: All Other Racks
Total power consumption of Units + 2 0.6 x 0.55 (1) (VA) 2 = I/O Power Supply Unit (Remote I/O Slave Unit) power consumption 0.6 = 60% efficiency 0.55 (1) = Power rate (Number in parentheses: when PS211, RT002-P or RT202 is used.) Current Drawn from 5-V Supply (Standard I/O Units)
Unit DC Input
Model number C200H-ID211
Current consumption 0.01 A each
C200H-ID212 No-Voltage Contact
C200H-ID001
Input
C200H-ID002
AC Input
C200H-IA121 C200H-IA122/IA122V C200H-IA221 C200H-IA222/IA222V
AC/DC Input
C200H-IM211 C200H-IM212
Contact Output
C200H-OC221 C200H-OC222 C200H-OC223 C200H-OC224
190
C200H-OC225
0.05 A
C200H-OC222V
0.008 A
C200H-OC224V
0.01 A
C200H-OC226
0.03 A
Page 198
Appendix B
Specifications Unit Transistor Output
Model number C200H-OD411
Current consumption 0.14 A
C200H-OD211
0.16 A
C200H-OD212
0.18 A
C200H-OD213
0.14 A
C200H-OD214 C200H-OD216
0.01 A each
C200H-OD217 C200H-OD21A
0.16 A
Analog Timer
C200H-OA121-E C200H-OA122-E C200H-OA221 C200H-OA223 C200H-OA222V C200H-OA224 C200H-TM001
0.14 A 0.18 A 0.14 A 0.18 A 0.20 A 0.27 A 0.06 A
Standard B7A Interface
C200H-B7AI1
0.10 A
Triac Output
C200H-B7AO1 Interrupt Input
Current Drawn from 5-V Supply for Group-2 High-density I/O Units
Unit DC Input
Transistor Output
Current Drawn from 5-V Supply for Group-2 B7A Interface Units
Unit B7A Interface Unit (Group-2 Units)
Current Drawn from 5-V Supply for Special I/O Units
Unit
C200HS-INT01 Model number C200H-ID111 C200H-ID216 C200H-ID217 C200H-ID218 C200H-ID219 C200H-OD218 C200H-OD219 C200H-OD21B Model number C200H-B7A12/02 C200H-B7A21/22 Model number
TTL Input
C200H-ID501
DC Input
C200H-ID215
TTL Output
C200H-OD501
Transistor Output
C200H-OD215
TTL I/O
C200H-MD501
DC Input/Transistor
C200H-MD115
Output
C200H-MD215
High-speed Counter
C200H-CT001-V1
0.02 A Current consumption 0.12 A 0.1 A 0.12 A 0.1 A 0.12 A 0.18 A 0.27 A 0.18 A Current consumption 0.10 A
Current consumption 0.13 A 0.22 A 0.18 A
0.30 A
C200H-CT002 Position Control
Analog Input
C200H-NC111 C200H-NC112 C200H-NC211
0.15 A
C200H-AD001
0.55 A
C200H-AD002
0.45 A
0.50 A
191
Page 199
Appendix B
Specifications Unit Analog Output Temperature Control
Model number C200H-DA001
Current consumption 0.65 A
C200H-DA002
0.60 A
C200H-TC001 C200H-TC002 C200H-TC003
0.33 A
C200H-TC101 C200H-TC102 C200H-TC103 Heat/Cool Temperature Control
C200H-TV001 C200H-TV002 C200H-TV003
0.33 A
C200H-TV101 C200H-TV102 C200H-TV103 PID Control
C200H-PID01 C200H-PID02 C200H-PID03
0.33 A
Temperature Sensor Input ASCII
C200H-TS001/TS002 C200H-TS101/TS102 C200H-ASC02
0.45 A
Voice Output
C200H-OV001
0.30 A
ID Sensor
C200H-IDS01-V1
0.25 A
0.20 A
C200H-IDS21 Fuzzy Logic
C200H-FZ001
0.30 A
Cam Positioner
C200H-CP114
0.30 A
Current Drawn from 5-V Supply for Other Units
Unit
C200H-LK101-PV1
Current consumption 0.25 A
C200H-LK201-V1
0.15 A
C200H-LK202-V1
0.25 A
PC Link
C200H-LK401
0.35 A
Remote Master
C200H-RM001-PV1
0.20 A
C200H-RM201
0.25 A 0.80 A
SYSMAC NET Link
C200HW-SLK13/SLK14/SLK23/ SLK24 C200HS-SNT32
Power Supply Adapter
C200H-APS01/APS02/APS03
0A
CompoBus/S Master
C200HW-SRM21
0.15 A
DeviceNet Master
C200HW-DRM21
0.25 A
Host Link
SYSMAC LINK
192
Model number
1.00 A
Page 200
Appendix B
Specifications Current Drawn from 26-V Supply
Unit
Model number
Contact Output
C200H-OC221/OC222/OC223/ OC224/OC225
Current consumption 0.075 A/8 points that turn ON simultaneously
C200H-OC222V/OC224V/ OC226
0.09 A/8 points that turn ON simultaneously
Transistor Output
C200H-OD216/OD217
0.075 A/8 points that turn ON simultaneously
ID Sensor
C200H-IDS01-V1/IDS21
0.12 A
Current Drawn from 24-V Supply
Unit
Model number
No-Voltage Contact Input
Current consumption 0.06 A each
C200H-ID001/ID002
Dimensions Racks The dimensions shown below are for both the CPU Rack and Expansion I/O Rack. The C dimension for the Programming Console will increase by 30mm when the Programming Console Adapter C200H-BP001 is used, and will increase by 50 mm when the Programming Console Adapter C200H-BP002 is used. CPU
130
A B
138
Model C200HS-CPU01-E/CPU01-EC/ CPU03-E C200HS-CPU21-E/CPU21-EC/ CPU23-E/CPU31-E/CPU33-E
A (mm)
B (mm)
Weight (kg)
101
113
1.4
126
138
1.5
Memory Cassette
73.2
44
9.1
193