SYSMAC C200HS Programmable Controllers Installation Guide, pages 201 to 210

Pages 201 to 210 of 221

The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron C200H-OC225 and Omron C200HW-SLK23

Page 201

Appendix B

Specifications C200H-PS221/PS221-C/PS211 I/O Power Supply Unit

130

138

101 113

Backplane

130

W 17

Model

Width (W)

Weight

C200H-BC031-V2

260 mm

0.8 kg max.

C200H-BC051-V2

330 mm

1.0 kg max.

C200H-BC081-V2

435 mm

1.3 kg max.

C200H-BC101-V2

505 mm

1.5 kg max.

I/O Connecting Cables The dimensions shown below are for I/O Connecting Cables.

L

74 64 49

Cable

194

Length (L)

C200H-CN311

30 cm

C200H-CN711

70 cm

C200H-CN221

2m

C200H-CN521

5m

C200H-CN131

10 m

15

Page 202

Appendix B

Specifications C200H-PRO27 Programming Console The dimensions shown below are for the Programming Console.

192

96

(30) 48

C200H-CN222/CN422, C200HS-CN222/CN422 Connecting Cable

33

29

12

2000 (4000)

Standard I/O Units The dimensions shown below are for the three shapes of Standard I/O Units mentioned throughout these specifications. 10-terminal Terminal Block (A-shape I/O Units)

195

Page 203

Appendix B

Specifications 19-terminal Terminal Block (B-shape I/O Units)

130 x x x x

Backplane x x x x 128

35

145

10-terminal Terminal Block (E-shape I/O Units)

Backplane x x 130 x x 121 35

138

19-terminal Terminal Block (Extended B-shape I/O Units)

x x x x

Backplane

130 x x x x 152

35

196

169

Page 204

Appendix B

Specifications Terminal Dimensions M3.5

7.3 8.5

Group-2 High-density I/O Units The dimensions shown below are for the Group-2 High-density I/O Units. Dimensions with Unit Mounted

Backplane

Group-2 High-density I/O Units (C and D Types)

130

35

118

101

Approx. 143

High-density I/O Units (Special I/O Units) The dimensions shown below are for the High-density I/O Units classified as Special I/O Units.

130

35

101

197

Page 205

Appendix B

Specifications Dimensions with Unit Mounted

Connecting cable

G79-jC Connecting Cable is Used

G79-jC Connecting Cable

Backplane

Backplane

Fujitsu’s Connector is Used

118

118 145

Approx. 163

Backplane

Interrupt Input Unit The dimensions shown below are for the Interrupt Input Unit classified as Special I/O Units.

x x 130 x x 35

101 118

Backplane

Standard B7A Interface Unit The dimensions shown below are for the B7A Interface Unit classified as Special I/O Units.

130

35

101 118

198

Page 206

Appendix B

Specifications

The dimensions shown below are for the Group-2 B7A Interface Units.

Backplane

Group-2 B7A Interface Units

Backplane

Analog Timer Unit The dimensions shown below are for the Analog Timer Unit classified as Special I/O Units.

130

35

101 118

199

Page 207

Appendix B

Specifications Mounting Dimensions Four (five), M4

A±0.2 B ± 0.2

Backplane

130

118±0.2

68 to 108

80 to 120

130

Four (five), M4

118±0.2

Backplane

W

Model

A±0.2

B±0.2

W

C200H-BC031-V2

246 mm

---

260 mm

C200H-BC051-V2

316 mm

---

330 mm

C200H-BC081-V2

421 mm

---

435 mm

C200H-BC101-V2

491 mm

270.5 mm

505 mm

Panel Mounting of C200H-PRO27 Programming Console

Bracket Two screws

Panel thickness (t = 1.0 to 3.2)

200

Page 208

Appendix B

Specifications

The following is the standard panel cut dimensions for the Programming Console (conforming to DIN 43700).

186 +1.1 0

92 +0.8 0

Use the C200H-ATT01 Mounting Bracket (sold separately) to mount the C200H-PRO27 Programming Console to panels.

75.5

116

9.1

14.1

Take the space required for the cable into consideration when mounting the Programming Console to panels. 37 15

Approximately 80 mm is required. Use either one of the connectors.

Approximately 70 mm is required.

201

Page 209

Appendix B

Specifications

RS-232C Port Specifications RS-232C Specifications

The specifications for the RS-232C port are given below. Devices that meet these specifications can be connected. Connector Pin Assignments Pin assignments for the RS-232C port are given in the following table. Pin

1

6

9 5

Abbreviation

Name

Direction

1

FG

Field ground

---

2

SD (TXD)

Send data

Output

3

RD (RXD)

Receive data

Input

4

RS (RTS)

Request to send

Output

5

CS (CTS)

Clear to send

Input

6

---

Not used.

---

7

---

Not used.

---

8

---

Not used.

---

9

SG

Signal ground

---

Connector fitting

FG

Field ground

---

System Configurations

IBM PC/AT or compatible (9-pin male connector)

C200HS CPU Unit

Plug: XM2D-0901 (9-pin female)

Hood: XM2S-0913

Recommended cable

RS-232C port

Hood: XM2S-0911-E

Plug: XM2A–0901 (9-pin male)

Provided with CPU Unit

Connections The connections between the C200HS and a personal computer are illustrated below as an example. C200HS

Personal Computer

Signal

Pin No.

Pin No.

Signal

FG

1

1

CD

SD

2

2

RD

RD

3

3

SD

RS

4

4

ER

CS

5

5

SG

–

6

6

DR

–

7

7

RS

–

8

8

CS

SG

9

9

CI

D-sub, 9-pin connector Male connector on cable

202

Shielded cable

D-SUB, 9-pin connector Female connector on cable

Page 210

Appendix B

Specifications

Applicable Connectors The following connectors are applicable. One plug and one hood are included with the CPU. CPU Unit Connector Item

Model

Plug Hood

XM2A-0901 XM2S-0911-E

Specifications Used together (One of each provided with CPU Unit.)

9-pin male 9-pin, millimeter screws, static-resistant

Personal Computer Connector Item

Model

Plug Hood

XM2D-0901 XM2S-0913

Specifications Used together

9-pin female 9-pin, inch screws

Port Specifications Item

Specification

Communications method

Half duplex

Sync

Start-stop

Baud rate

1,200, 2,400, 4,800, 9,600, or 19,200 bps

Transmission method

Point to point

Transmission distance

15 m max.

Interface

EIA RS-232C

One-to-one Link Connections The RS-232C port on the C200HS can be connected to the same port on another C200HS. Wire the cable as shown in the diagram below. C200HS

C200HS

Signal Abb.

Pin No.

Pin No.

Signal Abb.

FG

1

1

FG

SD

2

2

SD

RD

3

3

RD

RS

4

4

RS

CS

5

5

CS

–

6

6

–

–

7

7

–

–

8

8

–

SG

9

9

SG

XM2A–0901

XM2A–0901

Ground the FG terminals of C200HS Units at a resistance of less than 100 Ω.

203