The text of a manual · part 16 of 23
SYSMAC C200HS Programmable Controllers Installation Guide, pages 151 to 160
Pages 151 to 160 of 221
The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron C200H-OC225 and Omron C200HW-SLK23
Page 151
Appendix B
Specifications Terminal Connections I/O word “m” 0 1 2 3
24 VDC
4
+
5 6 7 COM
8 9 10 11
24 VDC
12
+
I/O word “m+1” A
B
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
0 1 2 3
6 7 COM
8 9 10 11
14 15
16
16
17
17
18
18
NC
19
19
NC
NC
20
20
NC
15 COM
24 VDC
12
15
14
+
5
14
13
24 VDC
4
+
13 14 15 COM
Note 1. I/O word “m” is determined by the I/O number setting (m = IR 030 + 2 × I/O number). 2. The power can be supplied in either polarity, but the same polarity must be used for all COM terminals. Connect power supply wiring to every COM terminal, even though the COM terminals are connected internally.
DC Input Unit C200H-ID217 (64 Points)
144
Rated Input Voltage
24 VDC
Operating Input Voltage
20.4 to 26.4 VDC
Input Impedance
5.6 kW
Input Current
4.1 mA (at 24 VDC)
ON Voltage
14.4 VDC min.
OFF Voltage
5.0 VDC max.
ON Response Time
1.0 ms max.
OFF Response Time
1.0 ms max.
No. of Circuits
2 (32 points/common)
Internal Current Consumption
All 64 points cannot be turned ON simultaneously at high temperatures. Refer to the following graph. 120 mA 5 VDC max.
Weight
250 g max.
Dimensions
D-shape
Page 152
Appendix B
Specifications Circuit Configuration and Simultaneously Usable Points COM 1000 pF Internal Circuit
IN00
CN1
IN07 COM IN08
680 W CN1
IN07 COM IN08
Indicator switch circuit
Input indicator
1000 pF
IN07 COM IN08
Internal Circuit
680 W
50 40 30 20 10
5.6 kW IN15 COM IN00
CN2
Input Voltage: 26.4 VDC
SW
CN2
IN15 COM IN00 A
64 60
5.6 kW
IN15 COM IN00 B
Input Voltage: 24.0 VDC
Simultaneously Usable Points
A
0 0
B
10
IN07 COM IN08
20 30 40 50 55 60 Ambient Temperature (°C)
IN15
Terminal Connections CN1 I/O word “m+1” NC NC COM
15 24 VDC
+
A
20
20
19
19
18
18
17
I/O word “m+2” 0
NC
1
NC
2
COM
17
15
4
16
16
13
15
15
13
24 VDC
14
14
12
+
13
11
12
13
10
12
12
10
9
11
11
9
8
10
10
8
7
9
9
8
8
7
6
6
5
24 VDC
5
5
4
+
3
4
4
3
2
3
3
2
1
2
2
1
1
0
1
3
3
4
4
1 2 3
8
9
9
10
10
11
11
12
12
13
13
14
14
15
15
16
16
17
17
18
18
NC
19
19
NC
NC
20
20
NC
13 14 15 COM
24 VDC
4
8
11
+
2
7
12
5
2
0
7
9
7
1
6
10
7
1
5
8
24 VDC
B
6
COM
COM
I/O word “m+3” A
5
5
7
6
0
+
6
6
4
3
24 VDC
14
COM
+
I/O word “m” B
14
11
24 VDC
CN2
5
+
6 7 COM
8 9 10 11
24 VDC
12 13
+
14 15 COM
Note 1. I/O word “m” is determined by the I/O number setting (m = IR 030 + 2 × I/O number).
145
Page 153
Appendix B
Specifications
2. The power can be supplied in either polarity, but the same polarity must be used for all COM terminals in each connector. Connect power supply wiring to every COM terminal, even though the COM terminals in each connector are connected internally.
DC Input Unit C200H-ID218 Rated Input Voltage
24 VDC +10%/–15%
Input Impedance
3.9 kΩ
Input Current
6 mA (at 24 VDC)
ON Voltage/ON Current
15.4 VDC min./3.5 mA min.
OFF Voltage/OFF Current
5.0 VDC max./1 mA max.
ON Response Time
1.0 ms max.
OFF Response Time
1.0 ms max.
No. of Circuits
32 (32 points/common) Note The number of points that can be ON simultaneously is limited according to the ambient temperature. Refer to the following diagram for details.
Internal Current Consumption
100 mA 5 VDC max.
Weight
180 g max.
Circuit Configuration Ambient Temperature for Simultaneously ON Points 0.01 µF
Input voltage: 24.0 VDC to Input LED indicator 0.01 µF to 470 Ω
Internal circuit
470 Ω 3.9 kΩ
Simultaneously ON points to
Input voltage: 26.4 VDC
3.9 kΩ to Input LED indicator Ambient temperature
146
Page 154
Appendix B
Specifications Terminal Connections m words m + 1 words (m = 030 + 2 × I/O number)
24 VDC
24 VDC
24 VDC
24 VDC
Note 1. The polarity of the input power supply can be either positive or negative. The polarity of all commons, however, must be the same. 2. COM terminals must all be wired even though they are connected internally.
DC Input Unit C200H-ID219 Rated Input Voltage
24 VDC +10%/–15%
Input Impedance
3.9 kΩ
Input Current
6 mA (at 24 VDC)
ON Voltage/ON Current
15.4 VDC min./3.5 mA min.
OFF Voltage/OFF Current
5.0 VDC max./1 mA max.
ON Response Time
1.0 ms max.
OFF Response Time
1.0 ms max.
No. of Circuits
64 (32 points/common) Note The number of points that can be ON simultaneously is limited according to the ambient temperature. Refer to the following diagram for details.
Internal Current Consumption
120 mA 5 VDC max.
Weight
250 g max.
147
Page 155
Appendix B
Specifications
470 Ω 3.9 kΩ to to
Input LED indicator 0.01 µF to 470 Ω to
3.9 kΩ
Internal circuit to
Input LED indicator Ambient Temperature for Simultaneously ON Points Input voltage: 20.4 VDC
Input voltage: 24.0 VDC
Simultaneously ON points
0.01 µF to
Internal circuit
Circuit Configuration
Input voltage: 26.4 VDC to to
Ambient temperature
Terminal Connections (m + 1) words
(m = 030 + 2 × I/O number) (m + 1) words (m + 2) words
24 VDC
24 VDC
24 VDC
24 VDC
24 VDC
24 VDC
(m + 3) words
24 VDC
24 VDC
Note 1. The polarity of the input power supply can be either positive or negative. The polarity of all commons for CN1 and CN2, however, must be the same. 2. COM terminals for CN1 and CN2 must all be wired even though they are connected internally.
148
Page 156
Appendix B
Specifications
Transistor Output Unit C200H-OD218 (32 Points) Max. Switching Capacity
16 mA 4.5 VDC to 100 mA 26.4 VDC (see below)
Min. Switching Capacity
None
Leakage Current
0.1 mA max.
Residual Voltage
0.8 V max.
ON Response Time
0.1 ms max.
OFF Response Time
0.4 ms max.
No. of Circuits
1 (32 points/common)
Internal Current Consumption
180 mA 5 VDC max.
Fuse Rating
3.5 A (The fuse is not user-replacable.)
Power for External Supply Weight
110 mA 5 to 24 VDC-10% min. (3.4 mA × number of ON pts) 180 g max.
Dimensions
C-shape
Circuit Configuration and Maximum Switching Capacity 4.5 to 26.4 VDC OUT00 OUT07 COM Internal Circuit
A
Output indicator 4.5 to 26.4 VDC OUT08 OUT15 Output indicator
Fuse blowout detection circuit
F indicator
Fuse (3 A)
COM 4.5 to 26.4 VDC OUT00 OUT07 COM 4.5 to 26.4 VDC OUT08
Max. Switching Capacity (mA/pt)
100
50
16 0 0
B
4.5
10 20.4 26.4 Power Supply Voltage (V)
OUT15 COM
149
Page 157
Appendix B
Specifications Terminal Connections
I/O word “m” L L L L
+
L L L L
I/O word “m+1” 0 1 2 3 4 5 6 7
COM
L L L L
+
L L L L
8 9 10 11 12 13 14 15
COM
A
B
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
15 16
15 16
17
17
18
18
19
19
20
20
0 1 2 3 4 5 6 7
L L L L L
+
4.5 to 26.4 VDC
L L L COM
8 9 10 11 12 13 14 15
L L L L L
+
L L L COM
Note 1. I/O word “m” is determined by the I/O number setting (m = IR 030 + 2 × I/O number). 2. When the fuse blows, the F indicator lights and the error flag in AR 02 corresponding to the I/O number is turned ON. I/O numbers 0 to 9 correspond to AR 0205 to AR 0214. 3. The interruption of power from the external power supply is treated the same as a fuse blowout. 4. Connect power supply wiring to every COM terminal, even though the COM terminals are connected internally.
Transistor Output Unit C200H-OD219 (64 Points) Max. Switching Capacity
16 mA 4.5 VDC to 100 mA 26.4 VDC (see below)
Min. Switching Capacity
None
Leakage Current
0.1 mA max.
Residual Voltage
0.8 V max.
ON Response Time
0.1 ms max.
OFF Response Time
0.4 ms max.
No. of Circuits
2 (32 points/common)
Internal Current Consumption
270 mA 5 VDC max.
Fuses
Weight
Two 3.5 A fuses (1 fuse/common) The fuses are not user-replacable. 220 mA 5 to 24 VDC-10% min. (3.4 mA × number of ON pts) 250 g max.
Dimensions
D-shape
Power for External Supply
150
Page 158
Appendix B
Specifications Circuit Configuration 4.5 to 26.4 VDC OUT00 OUT07 Internal Circuit
COM
SW Indicator switch/ fuse blowout detection circuit
Output indicator
CN1
4.5 to 26.4 VDC OUT08
Fuse
OUT15 COM
CN1 CN2
F indicator
4.5 to 26.4 VDC OUT00 OUT07 Internal Circuit
COM
CN2
4.5 to 26.4 VDC OUT08
Fuse
OUT15 COM
100
50
16 0 0
4.5
10
20.4 26.4
Power Supply Voltage (V)
Max. Switching Capacity (A/unit)
Max. Switching Capacity (mA/pt)
Maximum Switching Capacity 6.4 6.0 5.0 4.0 3.0 2.0 1.0 0 0
10
20
30
40
505560
Ambient Temperature (°C)
151
Page 159
Appendix B
Specifications Terminal Connections CN1 I/O word “m+1”
COM L L L
+
L L L L L
15 14 13 12 11 10 9 8
COM L L L
+
L L L L L
7 6 5 4 3 2 1 0
CN2 I/O word “m”
B
A
20
20
19
19
18
18
17
17
16
16
15
15
14
14
13
13
12
12
11
11
10
10
9
9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1
1
I/O word “m+2” L
COM
15 14 13 12 11 10 9 8
L
L
L
L
L
+
L L
+
L L
L
L
L
L
L
5 4 3 2 1 0
2 3 4 5 6 7
L
COM
6
1
COM
L
7
0
L L
L
L
L
+
L L
+
L L L
L L L L
8 9 10 11 12 13 14 15
COM
L
I/O word “m+3” A
B
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
15
15
16
16
17
17
18
18
19
19
20
20
0
L
1
L
2
L
3
L
4
L
5
+
4.5 to 26.4 VDC
L
6
L
7
L COM
8
L
9
L
10
L
11
L
12
L
13
+
L
14
L
15
L COM
Note 1. I/O word “m” is determined by the I/O number setting (m = IR 030 + 2 × I/O number). 2. When either fuse blows, the F indicator lights and the error flag in AR 02 corresponding to the I/O number is turned ON. I/O numbers 0 to 9 correspond to AR 0205 to AR 0214. 3. The interruption of power from the external power supply is treated the same as a fuse blowout. 4. Connect power supply wiring to every COM terminal, even though the COM terminals in each connector are connected internally.
Transistor Output Unit C200H-OD21B (32 Points) (Load Short-circuit Protection Provided) Max. Switching Current
0.5 A 24 VDC +10%/–15% (5 A/Unit)
Min. Switching Current
None
Leakage Current
0.1 mA max.
Residual Voltage
0.8 V max.
ON Response Time
0.1 ms max.
OFF Response Time
0.3 ms max.
No. of Circuits
32 (32 points/common)
Internal Current Consumption
180 mA 5 VDC max.
Fuses
Weight
One 7 A fuse (1 fuse/common) The fuses are not user-replacable. 160 mA 24 VDC +10%/–15% min. (5 mA × number of ON pts) 180 g max.
Alarm Indicator
Lamp F lights (unless fuse is broken).
Load Short-circuit Prevention (see note 1) Dimensions
Detection current: 0.7 to 2.5 A Automatic restart after error clearance. C-shape
Power for External Supply
152
Page 160
Appendix B
Specifications
Note When the short-circuit/overload protection is activated for a contact point, the output for that point is turned OFF. At the same time, lamp “F” lights up, and the alarm from AR0205 to AR0214 corresponding to the I/O number turns ON. After the cause of the error has been removed, the alarm will be cleared automatically when the internal temperature of the element drops.
to 0V
Output LED indicator to Alarm LED indicator
0V
Short-circuit protection circuit
Internal circuit
Short-circuit protection circuit
Circuit Configuration to 0V
Output LED indicator to 0V
Terminal Connections I/O word “m”
I/O word “m+1”
24 VDC
24 VDC
24 VDC
24 VDC
153