160 SSC Variable Speed Drive (Series C) User Manual: Appendix A
Pages 63 to 66 of 88, from 160 SSC Variable Speed Drive (Series C) User Manual
The original document is the PDF (2.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Allen-Bradley 160-BMB2 and Allen-Bradley 160-DM-PS1
Page 63
Appendix A
Specifications Tables A.A and A.B contain information that is unique to each Bulletin 160 Drive rating. Table A.C contains information that applies to all drive ratings. 200-240VAC – 1-Phase & 3-Phase Input Drive Ratings
Table A.1
Drive Catalog Number 1-Phase Input 3-Phase Input
160S-AA02 160S-AA03 160S-AA04 160S-AA08, 160-AA02 160-AA03 160-AA04 160-AA08 160-AA12, 160-AA18
Output Ratings 3-Phase Motor Rating, kW (HP) Maximum Output Amps Power Dissipation, Watts
0.37 (1/2) 2.3 20
0.55 (3/4) 3.0 25
3.7 (5) 18.0 137
Input Ratings Input Voltage, Frequency Operational Input Voltage Range Input kVA 1-Phase Input Current ➊ 3-Phase Input Current ➊
1.1 4.8 2.8
200/240VAC, 1-Phase and 3-Phase, 50/60 Hz 180-265VAC 1.4 2.2 3.7 5.7 6.2 9.4 16.3, 3.6 5.4 9.4 14.2
Environmental Specifications Cooling Method
Convection Cooled
Dynamic Braking Torque ➋ With External Dynamic Brake Module, Without External Dynamic Brake Module 100, 100
0.75 (1) 4.5 35
1.5 (2) 8.0 74
2.2 (3) 12.0 107
8.4, 21.1
Fan Cooled
200 100
150 50
115 50
380-460VAC – 3-Phase Input Drive Ratings
100 20
Table A.2
Drive Catalog Number 3-Phase Input
160-BA01
160-BA02
160-BA03
160-BA04
160-BA06
160-BA10
Output Ratings 3-Phase Motor Rating, kW (HP) Maximum Output Amps Power Dissipation, Watts
0.37 (1/2) 1.2 25
0.55 (3/4) 1.7 30
0.75 (1) 2.3 37
1.5 (2) 4.0 50
2.2 (3) 6.0 77
3.7 (5) 10.5 120
Input Ratings Input Voltage, Frequency Operational Input Voltage Range Input kVA Input Current ➊
1.1 1.4
Environmental Specifications Cooling Method
Convection Cooled
Dynamic Braking Torque ➋ With External Dynamic Brake Module, Without External Dynamic Brake Module 100
380/460VAC, 3-Phase, 50/60 Hz 340-506VAC 2.2 3.7 5.6 2.8 4.6 7.0
1.6 2.0, 100
Fan Cooled
200 100
150 50
115 50
➊ Input current ratings are calculated based on a nominal input voltage of 230V and 460V respectively. ➋ Estimated – Actual value depends upon motor characteristics.
9.7 12.2
100 20
Page 64
A-2
Specifications
All Drive Ratings
Table A.3
Input/Output Ratings Output Voltage Output Frequency Efficiency Transient Protection
Adjustable from 0 to Input Voltage Programmable from 0 to 240 Hz 97.5% Typical Standard 6 kV
Environmental Specifications Enclosure Ambient Temperature Storage Temperature Relative Humidity Vibration Shock Altitude
IP20 0°C to 50°C –40°C to 85°C 0 to 95% Non-Condensing 1.0 G Operational, 2.5 G Non-Operational 15 G Operational, 30 G Non-Operational 1,000 m (3,300 ft) without Derating
Control Inputs Control Input Type
Dry Contact Inputs, Drive has an internal 12V power supply that provides 10 mA typical current flow.
Alternate Inputs, Accepts open collector/solid state inputs (sinking into the drive) with maximum leakage current of 50 µA.
24V Inputs, An optional 24V DC interface module allows use of 24VDC sinking inputs (see ).
Start, Stop, Fwd/Rev SW1, SW2, SW3
Configurable Inputs for Two- or Three-Wire Control Configurable Inputs for Control of 8 Preset Speeds and 2 Accel/Decel Times
Preset Speed Model Only
Programmable Input
TB3-8 Can Be Configured to Select: • Accel/Decel Times • Frequency Select • External Coast to Rest • Preset Speed ➊ • TB3 Control/Keypad or Communication Control
Approvals and Standards Compliance Approvals LIST
ED 966X
LIST
UL UL508C ®
IN D
CONT EQ
C
ED 966X
UL CSA 22.2 ®
IN D
AS/NZS 2064.1:1992
CONT EQ
EMC Directive 89/336 LV: EN 50178, EN 60204 EMC: EN 61800-3, EN 50081-1, EN 50082-2 Designed to Meet These Standards
FCC Class A ➋ and B ➋, IEC 146-1-1, VDE 0871 and VDE 0875
Control Inputs, Analog Signal Follower Only External Speed 1K to 10K Ohms, 2 Watts Minimum Potentiometer 4 – 20 mA Analog Input 250 Ohms Input Impedance –10 to +10VDC Analog Input Control Output Programmable Output (Form C Relay Contact) ➊ Analog Signal Follower only. ➋ With external components.
100K Ohms Input Impedance
Resistive Rating: 0.4A at 125VAC, 0.2A at 230VAC, 2A at 30VDC Inductive Rating: 0.2A at 125VAC, 0.1A at 230VAC, 1A at 30VDC
Page 65
Specifications Control Features PWM Algorithm Switching Device V/Hz Ratio Carrier Frequency DC Boost Current Limiting
A-3
Motor Protection
Sine Weighted PWM with Harmonic Compensation IGBT Programmable Adjustable from 2 to 8kHz in 100 Hz Increments (Factory Default is 4kHz) Adjustable, Select from a Family of Boost Curves Software Controlled, Coordinated for Drive and Motor Protection, Programmable from 1 to 180% of Drive Output Current I2t Overload Protection, 150% for 60 Seconds, 200% for 30 Seconds
Overload Pattern #0 Overload Pattern #1 Overload Pattern #2
Flat Response Over Speed Range (No Speed Compensation) Speed Compensation Below 25% of Base Speed Speed Compensation Below 100% of Base Speed
Accel/Decel Time(s) S-Curve Accel/Decel Time(s) Stopping Modes
0.1 to 600 Seconds 0 to 100% of Accel/Decel Time, Not to Exceed 60 Seconds 4 Programmable Modes: Ramp to Stop, 0.1 to 600 Seconds Coast to Stop, Stops All PWM Output DC Injection Braking, Applies DC Voltage to the Motor for 0 to 25 Seconds DC Injection Braking with Auto Stop
Protective Features Overcurrent Excessive Temperature Over/Under Voltage
Programmable limit, 200% of Hardware Limit, 300% of Instantaneous Fault Embedded Temperature Sensor Trips if Heatsink Temperature Exceeds 95°C DC bus voltage is monitored for safe operation. • For 200-240VAC input drives, the overvoltage trip occurs at a bus voltage of 400VDC (equivalent to a 290VAC incoming line voltage). • For 380-460VAC input drives, the overvoltage trip occurs at a bus voltage of 800VDC (equivalent to a 575VAC incoming line voltage). • For 200-240VAC input drives, the undervoltage trip occurs at a bus voltage of 210VDC (equivalent to a 150VAC incoming line voltage). • For 380-460VAC input drives, the undervoltage trip occurs at a bus voltage of 390VDC (equivalent to a 275VAC incoming line voltage).
Control Ride Through Ground Short Faultless Ride Through Output Short Circuit Programming Programmer Display Type Keypad Controls
Minimum Ride Through is 0.5 Seconds, Typical Value is 2 Seconds Any Output Phase to Ground Short 100 Milliseconds Any Output Phase to Phase Short
Optional, Removable Program Keypad Module 6 Character LED, Two Digit Parameter Number and Four Digit Value Speed, Run, Stop and Direction
Page 66
A-4
Specifications