Page 59

Chapter 6

Troubleshooting Fault Information This chapter provides information to guide you in troubleshooting the drive. Included is a list and description of drive faults and problems that may occur. Program Keypad Module Fault Display

Figure 6.1 Active Fault If a fault occurs, P07 - [Active Fault] is displayed.

Fault Code Number Controllers equipped with a Program Keypad Module will flash the display when a fault is present.

Ready/Fault Indicating Panel

FAULT READY

Figure 6.2 Fault LED Controllers without a Program Keypad Module come equipped with a Ready/Fault Indicating Panel. When the Fault LED is illuminated, a fault exists. The optional Remote Programming Adapter is equipped with the same Ready/Fault indication system.

How to Clear a Fault When a fault occurs, the cause must be corrected before the fault can be cleared. After corrective action has been taken, any of the following actions will clear the fault. • Press the Program Keypad Module’s Stop button. • Disconnect power to the drive, wait one minute, reapply power. • Cycle the input signal at TB3-8 to the drive. • Set P54 - [Clear Fault] to 1.

Page 60

6-2

Troubleshooting

Bulletin 160 Fault Descriptions Fault No.

Fault Name

03

Power Loss Fault

04➊

UnderVoltage Fault

05➊

OverVoltage Fault

06➊

Table 6.A

Fault Description

Corrective Action Monitor the incoming AC line for low voltage or line power interruptions. Monitor the incoming AC line for low voltage or line power interruptions.

Motor Stall Fault

The DC Bus voltage remains below 85% nominal on power up for longer than 5 seconds. The DC Bus voltage fell below the minimum rated voltage. For 200-240VAC input drives, the undervoltage trip occurs at a bus voltage of 210VDC (equivalent to a 150VAC incoming line voltage). For 380460VAC rated drives, the undervoltage trip occurs at a bus voltage of 390VDC (equivalent to a 275VAC incoming line voltage). The maximum DC Bus voltage has been exceeded. For 200-240VAC input drives, the overvoltage trip occurs at a bus voltage of 400VDC (equivalent to a 290VAC incoming line voltage). For 380-460VAC input drives, the overvoltage trip occurs at a bus voltage of 800VDC (equivalent to a 575VAC incoming line voltage). The motor has stalled due to an excessive motor load.

07➊

Motor Overload Fault

An internal electronic overload trip has occurred. An excessive motor load exists.

08➊

Excessive heat has been detected.

11

Over Temperature Fault Operator Fault

Reduce the motor load until the drive output current does not exceed the current set by P42 - [Motor Overload Current]. Reduce P38 - [Boost Select]. Clear blocked or dirty heat sink fins. Check ambient temperature. Check for a blocked or non-operating fan. Clear the fault. Do not remove the keypad under power.

12➊

Overcurrent Fault

13➊

Software Over Current Fault Drive Overload Fault

20➊

The keypad has been removed while the drive is powered. An overcurrent has been detected in the hardware trip circuit. Motor current exceeded value set in parameter 79. An internal electronic overload trip has occurred. The drive is over heating.

32

EEPROM Fault

The EEPROM has invalid data.

33

Max Retries Fault

36

Incompatible Fault

The drive failed to reset within the number of retries set in P50 - [Restart Tries]. Incompatible communication module installed.

38

Phase U Fault

A phase to ground fault has been detected between the drive and the motor in phase U.

39

Phase V Fault

40

Phase W Fault

41

UV Short Fault

42

UW Short Fault

43

VW Short Fault

46

Intermittent Phase Fault Reprogram Fault

A phase to ground fault has been detected between the drive and the motor in phase V. A phase to ground fault has been detected between the drive and the motor in phase W. Excessive current has been detected between these two drive output terminals. Excessive current has been detected between these two drive output terminals. Excessive current has been detected between these two drive output terminals. An external short occurred while running diagnostics.

Motor regeneration has caused a bus overvoltage. Monitor the incoming AC line for excessive voltage. Extend the decel time or install a dynamic brake module or external capacitor module (See Appendix A).

A longer acceleration time or a reduced load is required.

Check for a short circuit at the drive output or for excessive load conditions at the motor. A longer acceleration time, reduced load, or removal of motor shaft blockage is required. Clear blocked or dirty heat sink fins. Check ambient temperature. Check for blocked or non-operating fan. Reduce motor load current. Reset EEPROM using P56 - [Reset Functions], Set to 1 and cycle power. Repair the system fault. Verify compatibility of communication module. Check the wiring between the drive and the motor. Check the motor for a grounded phase. Check that ground is not connected to U. Check the wiring between the drive and the motor. Check the motor for a grounded phase. Check the wiring between the drive and the motor. Check the motor for a grounded phase. Check the motor and external wiring to the drive output terminals for a shorted condition. Check the motor and external wiring to the drive output terminals for a shorted condition. Check the motor and external wiring to the drive output terminals for a shorted condition. Check wiring between the drive and the motor. Check for more than one shorted output. Clear the fault.

Occurs when the drive parameters are reset to default. 48 ➊ These faults have an auto reset feature. This feature automatically clears overvoltage, undervotage, and overtemperature faults

1 second after the fault condition is removed. Refer to P51 - [Restart Time].

Page 61

Troubleshooting

Possible Problems and Corrective Actions Problem The motor does not start, No output voltage to the motor.

6-3

Table 6.B

Corrective Action 1. Check the power circuit. • Check the supply voltage. • Check all fuses and disconnects. 2. Check the motor. • Verify that the motor is connected properly. 3. Check the control input signals. • Verify that the Start signal is present. • Verify that the contact closure signal is present at TB3-8. • Verify that either the Run Forward or Run Reverse signal is active, but not both. 4. Check P46 - [Input Mode]. • If P46 - [Input Mode] is set to 2, only the program keypad module Start button will start the motor.

The drive is started but the motor is not rotating. P01 - [Output Frequency] displays 0.0.

5. Cycle power or use P56 - [Reset Functions] if you changed P46 - [Input Mode]. 1. Check the motor. • Verify that the motor is connected properly. 2. Check the frequency source P06 - [Frequency Command]. • Verify that a frequency signal is present at terminal block TB3, Either a -10 to +10V signal or a 4-20 mA signal. • Verify that the Preset Frequencies are set properly. 3. Check the control input signals. • Verify that SW1, SW2 and SW3 are correct. (Refer to the chart in Chapter 5.) 4. Check the following parameter settings. • Verify that P59 - [Frequency Select] is showing the desired frequency source. • Verify that P58 - [Internal Frequency] is set to the desired frequency.

The motor is not accelerating properly.

Drive will not operate in the run/forward or run reverse modes.

5. Cycle power or use P56 - [Reset Functions] if you changed P46 - [Input Mode]. 1. Check the motor. • Verify that the motor is connected properly. • Verify that no mechanical problems exist. 2. Check the following parameter settings. • Verify that P30 - [Accel Time 1] or P69 - [Accel Time 2], whichever is currently used, is set properly. • Verify that P43 - [Current Limit] is set properly. • Verify that P38 - [Boost Volts] is set properly. 1. Verify that P46 - [Input Mode] is set to 1. 2. Verify that neither P73 - [Reverse Disable] nor P74 - [Analog Select] is set to 1. 3. Verify that the power has been cycled for 1and 2 to take effect. 4. Verify that both the Run Forward and Run Reverse switches are not closed simultaneously.

Display is dark.

5. Cycle power or use P56 - [Reset Functions] if you changed P46 - [Input Mode]. 1. Verify that the module is firmly seated. 2. Remove module and inspect connector pins. If pins are not damaged, reinstall and firmly seat the module.

Page 62

6-4

Troubleshooting

Block Diagram of Bulletin 160 Analog Signal Follower Brake Module BR+

BR-

Figure 6.3

Capacitor Module DC+

DC-

L1/R

T1/U

L2/S

T2/V

L3/T

T3/W

Motor

GND/PE TB3 - 1

Frequency Reference

-10 to +10V or

TB3 - 2

Potentiometer

TB3 - 3 (Common)

GND/PE Control Power

Bus Voltage Circuitry

Fault Feedback or 4 - 20 mA Reverse Start Programable Input Common

Current Circuitry

Program Keypad Module

TB3 - 4 CPU TB3 - 5 TB3 - 6 TB3 - 8 TB3 - 7

Opto Isolator Relay Circuitry

TB3 - 9 User TB3 - 10 Programmable Output TB3 - 11