Page 53

Parameters and Programming

5-15

Program Group No.

Parameter Name/Description

75

[Analog Input Minimum]

Min./Max. Range 0.0/150.0

Units 0.1%

Factory Default 0.0%

0.0/150.0

0.1%

100.0%

0 to 2

Numeric value

0

0/50%

1%

0%

0/5

Numeric Value

0

Important: Do not adjust this parameter until setting P60 - [Zero Offset]. Sets the percent of analog input used to represent P32 - [Minimum Frequency]. If the minimum analog input equals minimum frequency, no action is needed. If it is desired to adjust the analog input to equal P32 - [Minimum Frequency], use P16 - [Analog Input] to adjust the analog input to the desired level using P60 and then enter this value into P75. Analog inversion can be accomplished by setting this value larger than P76. Important: This parameter cannot be programmed while the drive is running.

76

[Analog Input Maximum] Important: Do not adjust this parameter until setting P60 - [Zero Offset]. Sets the percent of analog input used to represent P33 - [Maximum Frequency]. If the maximum analog input equals maximum frequency, no action is needed. If it is desired to adjust the analog input to equal P33 - [Maximum Frequency], use P16 - [Analog Input] to adjust the analog input to the desired level using P60 and then enter this value into P76. Analog inversion can be accomplished by setting this value smaller than P75. Important: This parameter cannot be programmed while the drive is running.

78

[Compensation] Settings:

0 No compensation. 1 Some drive/motor combinations have inherent instabilities which are exhibited as non-sinusodial motor currents. This setting attempts to correct this condition. 2 Some motor/load combinations have mechanical resonances which can be excited by the drive current regulator. This setting slows down the current regulator response and attempts to correct this condition.

79

[Software Current Trip] This provides a software instantaneous current trip similar to the 300% hardware current trip. This value is the percent above the P43 - [Current Limit] at which the drive trips immediately. A setting of zero disables the Software Current Trip.

80

[Stall Fault Time] This selects the amount of time the drive must be in a stall condition before it causes a stall fault. 0 = Normal stall time, approximately 60 seconds 1 = 2 times normal stall time 2 = 4 times normal stall time 3 = 6 times normal stall time 4 = 8 times normal stall time 5 = Stall fault disabled ATTENTION: Continuous operation at high currents caused by a stall can cause motor damage. This parameter applies only to the Analog Signal Follower model.

Page 54

5-16

Parameters and Programming

Program Group No.

Parameter Name/Description

Min./Max. Range

81

[PI Proportional Gain]

0/10.00

Numeric Value

0.01

0/10.00

Numeric Value

0.01

0/100.0%

0.1%

0.0%

0/10.0%

0.1%

0.0%

Proportional gain used by the PI regulator. This parameter is scaled so that when it is set to 1.0, the process response is 1 Hz when the process error is 1%. The correct value for this parameter depends on the dynamics of the process being controlled, as well as the desired response. This parameter is active when P46 - [Input Mode] setting 9 is used.

82

[PI Integral Gain] Integral Gain used by the PI regulator. This parameter is scaled so that when it is set to 1.0, the process response is 10 Hz/sec when the process error is 1%. The correct value for this parameter depends on the dynamics of the process being controlled, as well as the desired response. This parameter is active when P46 - [Input Mode] setting 9 is used.

83

[PI Process Reference]

Factory Default

Units

The PI control will regulate to this set point value. It represents a percentage of the analog input. This parameter is active when P46 - [Input Mode] setting 9 is used. This parameter along with P72 - [Slip Compensation] also activates PI control in drives using Firmware Version FRN 7.06. See page 5-17 for PI Control Setup and Activation instructions. ATTENTION: Hazard of personal injury or equipment damage exists due to unpredictable changes in motor speed. Do not use P72 - [Slip Compensation] and P83 - [Process Reference] to disable PI control while the drive is running. Disable PI control only when the drive is stopped.

84

[PI Dead Band] The PI control will ignore errors less than this value. This parameter is active when P46 - [Input Mode] setting 9 is used. This parameter applies only to the Analog Signal Follower model.

PI Control Block Diagram

Figure 5.1

P83 [PI Process Reference]

+ -

P81 [PI Proportional Gain]

Analog Feedback P82 [PI Integral Gain] P58 [Internal Frequency]

P84 [PI Dead Band]

+ +

TB3-8 Open TB3-8 Closed

P01 [Output Frequency]

Page 55

Parameters and Programming

5-17

PI Control Setup and Activation The Analog Signal Follower model provides for closed loop process control (PI control) where PI regulator output is used to drive the process to a desired set point.

Wire For PI Control 1. Connect input and output power to the drive. Follow the instructions provided in Section 2, Installation and Wiring. 2. Connect control wiring (see Chapter 2, Figure 2.17). A contact closure on terminals 6 and 7 is required for the drive to respond to a Start/Run command. 3. Select an external frequency command source. See Table 5.B. 4. Connect feedback device to TB3-2 and TB3-3 for 0 – 10V feedback or to TB3-3 and TB3-4 for 4 – 20 mA feedback. 5. Verify polarity of feedback. That is, increasing feedback signal requires increasing output frequency.

Program for PI Control 1. Set P56 - [Reset Functions] to 1 to reset the drive to defaults. An F48 - Reprogram Fault will occur which must be cleared by cycling the Stop input to the drive. 2. Users of Firmware Version 7.06: Set P46 - [Input Mode] to the desired setting. Users of Firmware Version 7.05 and earlier: Set P46 - [Input Mode] to 9. Table 5.B describes how to reference the external frequency command source for each P46 - [Input Mode] setting. Parameter 46 Settings and Frequency Source Selection Table 5.B P46 Setting

Reference External Frequency Command Source

Firmware Version

0

Set P59 - [Frequency Select] to 0 (Factory Default)

FRN 7.06 only

1

Set P59 - [Frequency Select] to 0 (Factory Default)

FRN 7.06 only

2

Set P59 - [Frequency Select] to 0 (Factory Default)

FRN 7.06 only

3

Set P59 - [Frequency Select] to 0 (Factory Default)

FRN 7.06 only

4

Set P59 - [Frequency Select] to 0 (Factory Default)

FRN 7.06 only

5

Set P59 - [Frequency Select] to 0 (Factory Default)

FRN 7.06 only

6

Set P59 - [Frequency Select] to 0 (Factory Default)

FRN 7.06 only

7

Open the contact at TB3-8

FRN 7.06 only

8 9

This setting is not used with PI control. Open the contact at TB3-8

FRN 7.06 or earlier

3. Cycle power or set P56 - [Reset Functions] to 2 for the change made at Step 2 to take effect. 4. Set P72 - [Slip Compensation] to 0.

Page 56

5-18

Parameters and Programming

5. Use P75 - [Analog Input Minimum] and P76 - [Analog Input Maximum] to scale feedback to the process operating range. This may also be used to invert the feedback so that increasing feedback signal produces decreasing output frequency. 6. Set P83 - [PI Process Reference] to 20 as an initial setting. This establishes the set point as 20% of the maximum analog input. (This setting must be greater than zero to activate PI control in Firmware Version FRN 7.06 except when using input mode 9.) 7. Connect TB3-8 with TB3-7. This will disable PI control and force the output frequency to the P58 - [Internal Frequency] setting. 8. Connect TB3-6 with TB3-7 to start the drive. Verify motor operation and direction. 9. Remove the connection between TB3-8 from TB3-7. This will place the drive into PI control mode when using input modes 7 and 9. ATTENTION: Hazard of personal injury or equipment damage exists due to unpredictable changes in motor speed. Do not use P72 - [Slip Compensation] and P83 - [Process Reference] to disable PI control while the drive is running. Disable PI control only when the drive is stopped.

Tune the PI Loop Parameters P81 - [PI Proportional Gain] and P82 - [PI Integral Gain] are used to set how the drive will respond to errors (fluctuations) in feedback. • P81 - [PI Proportional Gain] corrects output frequency based on the magnitude of the error. • P82 - [PI Integral Gain] corrects output frequency based on the length of time an error has been present. 1. Set P82 - [PI Integral Gain] to zero and P81 - [PI Proportional Gain] to some low value. 2. Apply a step function command via P83 - [PI Process Reference] and monitor the output response. 3. Increase P81 - [PI Proportional Gain] until the response of the output is acceptably fast or the output becomes too noisy. 4. Reduce P81 - [PI Proportional Gain] back to the highest value at which the response is still clean. 5. Set P82 - [PI Integral Gain] to a low value. 6. Apply a step function command and monitor the output response. 7. Increase P82 - [PI Integral Gain] until the response is acceptably fast without overshoot. Important:

If either the value of P81 or P82 is set too high, drive output will oscillate around the set point entered in P83 - [PI Process Reference] due to continually changing loads in the application. Use P84 [Dead Band] to limit the effects of this oscillation by blocking a frequency count to either side of the set point frequency.

Page 57

Parameters and Programming

5-19

Common Problems with PI Control 1. Drive direction is incorrectly set for PI control. Ensure that the drive is operating with the clockwise direction indicator illuminated. 2. Drive oscillates between 0 and 3 Hz. • Check direction and polarity of analog input signal. • Ensure that the drive is operating with the clockwise direction indicator illuminated. • Ensure the +10V DC wire is connected to TB3-2 and that the common is connected to TB3-3. • Check that parameters P81 - [PI Proportional Gain] and P82 - [PI Integral Gain] are set to a value other than 0.00. 3. Drive accelerates too quickly resulting in an F05 - OverVoltage Fault. • Lower P81 - [PI Proportional Gain] below its current value. • Lower P82 - [PI Integral Gain] below its current value. • Raise P31 - [Decel Time 1] above its current value. • Raise P30 - [Accel Time 1] above its current value. • Evaluate the need for a dynamic brake for the application. 4. Drive will only run off the internal frequency or does not control with the PI process loop. • Check that P46 - [Input Mode] is set to 9. • Ensure that power was cycled for one minute after changing the P46 setting. • Ensure that there is not a connection between TB3-7 and 8. 5. Nothing works properly. • Set P56 - [Reset Functions] to 1 and press the Enter key. • Press the Stop button to clear the F48 - Reprogram Fault. • Cycle power to the drive. • Confirm that wiring is correct. • Reapply power and program according to this procedure. 6. PI does not function with DeviceNet. • Firmware Version 7.05 and earlier only allows one P46 - [Input Mode] setting to be active at one time (settings 2 or 6 for DeviceNet or setting 9 for PI). • It is possible for users of Firmware Version 7.05 and earlier to set up PI control via an external processor, such as a SLC500. Consult your processor manual for specific instructions.

Page 58

5-20

Parameters and Programming

End of Chapter