Page 45

Parameters and Programming

5-7

Program Group No.

Parameter Name/Description

38

[Boost Select]

Min./Max. Range 0/12

Sets the boost voltage and redefines the Volts per Hz curve. Settings 0 – 8 can provide increased torque at low frequency. Settings 9 – 12 are used to reduce energy consumption. Setting

1/2 Base Volts

50

9 10 11 12

1/2 Base Freq.

% [Base Voltage]

100

8 See Settings 1-8 1 0

50

% [Base Frequency]

0 1 2 3 4 5 6 7 8 Setting 9 10 100 11 12

Units Numeric Value

Factory Default 2

Boost Voltage (% of [Base Voltage]) 0 2.5 5.0 7.5 10.0 12.5 15.0 17.5 20.0 Fan/Pump Curves ➊ 45.0 40.0 35.0 30.0

➊ Break Point Voltages in percent of [Base Voltage]

39

[Skip Frequency]

0/240

1 Hz

240 Hz

0/30

1 Hz

0 Hz

Works in conjunction with P40 - [Skip Frequency Band] creating a range of frequencies at which the drive will not operate continuously. Frequency Controller tpu Ou t

Command Frequency

Frequency

Skip Frequency Setting

2 x P40 [Skip Freq Band] Setting

Time

40

[Skip Frequency Band] Determines the band around the P39 - [Skip Frequency] parameter. The actual band width will be 2 times P40 - [Skip Frequency Band] - 1/2 the band above and 1/2 the band below. A value of zero will disable the skip frequency.

Page 46

5-8

Parameters and Programming

Program Group No.

Parameter Name/Description

41

[Motor Overload Select]

Min./Max. Range 0/2

Bulletin 160 provides Class 10 overload protection. Settings 0 – 2 select the derating factor for the I2t overload function. Setting 0 1 2

Derate Level No Derate Min. Derate Max. Derate

Min Derate

60 40 20 0

25 50 75 100 125 150 175 200 % of Base Speed

% of [Overload Curent] Setting

% of [Overload Curent] Setting % of [Overload Curent] Setting

100

80

0

Factory Default 0

10:1 speed range 4:1 speed range, derate below 25% of base speed 2:1 speed range, derate below 50% of base speed

No Derate 100

Units Numeric Value

100 80 60 40 20 0 0

25 50 75 100 125 150 175 200 % of Base Speed

Max Derate Settings 0 = No Derating 1 = Minimum Derating 2 = Maximum Derating

80 60 40 20 0

0

25 50 75 100 125 150 175 200 % of Base Speed

42

[Motor Overload Current] Set to motor nameplate Full Load Amps (FLA).

43

[Current Limit] Maximum output current allowed before current limiting occurs. Value set in percent of drive rated output current.

44

[DC Hold Time] The time that P45 - [DC Hold Voltage] will be applied to the motor when P34 [Stop Mode Select] is set to either “DC Injection Braking” or “Ramp to Stop.”

0.1/200% of Drive Rating

0.01A

1/180% of Drive Rating

1%

115% of Drive Rating 150%

0.0/25.0

0.1 Seconds

0.0 Seconds

Page 47

Parameters and Programming

5-9

Program Group No.

Parameter Name/Description

45

[DC Hold Voltage]

Min./Max. Range 0/115

Units 1 Volt

Factory Default 0 Volts

DC Voltage level applied to the motor during braking when P34 - [Stop Mode Select] is set to either DC Injection Braking or Ramp to Stop mode. If the current exceeds P43 - [Current Limit] the voltage applied to the motor will be less than this setting. Ramp-to-Stop Mode

DC Injection Braking Mode Voltage

Vo lta ge

Volts/Speed

Volts/Speed [DC Hold Time]

Spe ed

Speed

[DC Hold Time]

[DC Hold Voltage]

[DC Hold Voltage]

Stop Command

46

Time

[Input Mode] Configures the TB3 control inputs for various 3-wire or 2-wire control schemes. Also enables/disables the Program Keypad Module, Remote Keypad Module or CopyCat Keypad Module input control. See Chapter 2 for wiring diagrams and descriptions of settings. Important: The method used to activate PI control is dependent upon Firmware Version. Refer to 5-17 for PI Control Setup and Activation instructions. Important: This parameter cannot be programmed while the drive is running. In addition, power must be cycled or P56 - [Reset Function] must be set to 2 for the change to take effect. Settings: 0 = 3-wire control ➊ 1 = 2-wire control ➊ 2 = Program Keypad Module, Remote Keypad Module, CopyCat Keypad Module, or Communication control ➊ 3 = Momentary Run Forward/ Run Reverse control ➊ 4 = 2-wire Accel/Decel control 5 = 2-wire Coast to Rest control ➊ 6 = 2-wire TB3 Control/Keypad or Communication control 7 = 2-wire Frequency Select control 8 = 2-wire Preset control ➋ 9 = 2-wire PI control ➋ ➊ A contact closure on TB3 Terminal 7 and 8 is required for the drive to respond to a Run command. ➋ Only available in Analog Signal Follower model.

Stop Command

0/9

Time

Numeric Value

0

Page 48

5-10

Parameters and Programming

Program Group No.

Parameter Name/Description

47

[Output Configure]

Min./Max. Range 0/10

Configures the TB3 relay output functionality. Setting 0 Drive Ready/Faulted

48

1 2 3 4 5

At Frequency Motor Running Reverse Motor Overload Ramp Regulated

6

Above Frequency

7

Above Current

8

Above DC Bus Voltage

9 10

Retries Exhausted Above Power Factor Angle

0

0/815

Numeric Value

0

2.0/8.0

0.1 kHz

4.0 kHz

0/9

Numeric Value

0

Determines the on/off point for the TB3 output relay when P47 - [Output Configure] is set to 6, 7, 8, and 10.

49

Factory Default

Output Changes State When . . . Energized and returns to shelf state when power is removed or a fault occurs. Drive reaches commanded frequency. The motor is receiving power from drive. Drive is commanded to run in the reverse direction. A motor overload condition exists. The ramp regulator is modifying the programmed accel/ decel times to avoid an overcurrent or overvoltage fault from occurring. The drive exceeds the frequency value set in P48 - [Output Threshold]. Drive exceeds the value set in P48 - [Output Threshold]. Important: Value for P48 - [Output Threshold] must be entered in percent of drive rated output current. Drive exceeds the DC bus voltage value set in P48 - [Output Threshold]. Number of retries for P50 - [Restart Tries] is exceeded. Power Factor angle exceeds the value set in P48 - [Output Threshold].

[Output Threshold]

Setting 6 7 8 10

Units Numeric Value

Ranges 0 to 240 Hz 0 to 180% 0 to 815 Volts 0 to 180˚

[PWM Frequency]

% Output Current (A)

Carrier frequency for the PWM output waveform. The chart below provides derating guidelines based on the PWM frequency setting. 100 98 96 94 92 90 88 86 84

1

2

3

4

5

6

7

8

Carrier Frequency (kHz)

Important: Ignoring derating guidelines can cause reduced drive performance.

50

[Restart Tries] Maximum number of times the drive will attempt to reset a fault. Faults 03 – 20 will automatically reset according to this parameter setting.

Page 49

Parameters and Programming

5-11

Program Group No.

Parameter Name/Description

51

[Restart Time]

Min./Max. Range 0.0/300.0

Time between restart attempts. If this parameter and P50 - [Restart Tries] are both set to zero, and P46 - [Input Mode] is not set to 3, the auto fault clear feature is enabled. This feature automatically clears overvoltage, undervoltage, and overtemperature faults 1 second after the fault condition is removed. If this parameter is set to zero and P50 - [Restart Tries] is not zero, then the time between restart attempts is 1 second.

52

[DB Enable]

Units 0.1 Seconds

Factory Default 10.0 Seconds

0/100

Numeric Value

0

0/10

Numeric Value

0

Enables/disables external dynamic braking. Setting “0” = Disable. Settings 1 through 100 = % duty cycle braking. ATTENTION: The 160 Dynamic Brake Module is rated for 5% duty cycle. Use of this package above 5% should not be used and voids the UL rating of this device. When setting this parameter to a value above 5% duty cycle, the resistor must be sized to avoid overheating of the resistor package. This parameter cannot be programmed while the drive is running.

53

[S-Curve] Enables a fixed shape S-Curve. See formula below: Formula:

S-Curve Time = Accel or Decel Time x S-Curve Setting (in percent) ➊ ➊ See values below.

Example:

Accel Time = 10 Seconds S-Curve Setting = 3 S-Curve Time = 10 x 0.3 = 3 Seconds

Important: Maximum S-Curve time is 60 seconds. 1/2 S-Curve

1/2 S-Curve

Time

Time

1/2 S-Curve

1/2 S-Curve

Time

Time

Enabled

Disabled

Accel Time

Decel Time

S-Curve Setting 0 = 0% 1 = 10% 2 = 20% 3 = 30% 4 = 40% 5 = 50% 6 = 60% 7 = 70% 8 = 80% 9 = 90% 10 = 100%

Page 50

5-12

Parameters and Programming

Program Group No.

Parameter Name/Description

54

[Clear Fault]

Min./Max. Range 0/1

Setting this parameter to a 1 performs a fault reset. When the fault reset function is complete, the value is automatically set back to 0. This parameter cannot be programmed while the drive is running.

55 56

Units Numeric Value

Factory Default 0

Used by Rockwell Automation field service personnel.

Numeric Value

Numeric Value

Numeric Value

[Reset Functions]

0/2

Numeric Value

0

0/1

Numeric Value

0

0.0/240.0

0.1 Hz

60.0 Hz

0/1

Numeric Value

0

–50.0/+ 50.0

Numeric Value

0%

[Memory Probe Address]

Drive parameters and their associated defaults are reset according to the following descriptions: Settings: 0 Idle State 1 Reset defaults (restores all parameter settings to factory defaults). 2 Update Input Mode (restores the drive to most recent programmed P46 - [Input Mode] setting).

After the reset/update function is complete, this parameter will set itself back to a “0.” This parameter cannot be programmed while the drive is running. Important: For setting 1 only, an F48 - Reprogram Fault will occur and must be cleared by cycling the Stop input to the drive. P46 - [Input Mode] factory defaults to 3-wire control. If using keypad control, change parameter setting back to a 2 to regain program keypad control, cycle power or use P56 Setting 2 again.

57

[Program Lock] When set to 1, all parameters will be protected against change by unauthorized personnel.

58

[Internal Frequency] When P59 - [Frequency Select] is set to a 1, this parameter will provide the drive frequency command. This parameter will change the frequency command in “Real time” using the up/down arrow keys. Maximum value is set in P33 - [Maximum Frequency]. Important: Follow normal programming procedures. Once the desired command frequency is reached, the Enter key must be pressed to store this value to EEPROM memory. If the ESC key is used before the Enter key, the frequency will return to the original value following the normal accel/decel curve.

59

[Frequency Select] Selects the source of the frequency command for the drive. Settings: 0 = External frequency command from the Control Terminal Block (TB3) 1 = Internal frequency command from P58 - [Internal Frequency].

60

[Zero Offset] Used to add or subtract any system offset to the analog input. See P16 - [Analog Input] for additional information. Important: This parameter cannot be programmed while the drive is running. This parameter applies only to the Analog Signal Follower model.

Page 51

Parameters and Programming

5-13

Program Group No.

Min./Max. Range 0.0/240.0

Parameter Name/Description

[Preset Frequency 0-7]

Units 0.1 Hz

Factory Default See Table

The programmed value sets the frequency that the drive outputs when selected. Refer to Chapter 2, Figure 2.21 for the Preset Speed model control wiring diagram.

Preset Speed Model Only

Signal Follower Model Only (Input Mode 8)

Preset Freq.

Default

TB3-4 (SW3)

TB3-2 (SW2)

TB3-1 (SW1)

TB3-8 (SW2)

TB3-2 (SW1)

61

Preset 0

3.0 Hz

0

0

0

0

0

62

Preset 1

20.0 Hz

0

0

1

0

1

63

Preset 2

30.0 Hz

0

1

0

N/A

N/A

64

Preset 3

40.0 Hz

0

1

1

N/A

N/A

65

Preset 4

45.0 Hz

1

0

0

1

0

66

Preset 5

50.0 Hz

1

0

1

1

1

67

Preset 6

55.0 Hz

1

1

0

N/A

N/A

68

Preset 7

60.0 Hz

1

1

1

N/A

N/A

Accel ➊

Decel ➊

P30 [Accel Time 1]

P31 [Decel Time 1]

P69 [Accel Time 2]

P70 [Decel Time 2]

➊ When using P46 - [Input Mode] setting 4, the Accel and Decel times are selected by providing an input to TB3-8.

See Chapter 2, Figure 2.12 for additional information.

69

[Accel Time 2]

0.0/600.0

0.1 Sec.

20.0 Seconds

➋/600.0

0.1 Sec.

20.0 Seconds

Time for the drive to ramp from 0.0 Hz to P33 - [Maximum Frequency]. The rate is linear for any increase in command frequency unless P53 - [S-Curve] is set to a value other than 0. Setting this to 0.0 gives 0.1 seconds acceleration with the initial current limit turned off. This allows quicker acceleration times for low inertia systems. For medium to high inertia systems, the minimum value should be 0.1.

70

[Decel Time 2] Time for the drive to ramp from P33 - [Maximum Frequency] to 0.0 Hz. The rate is linear for any decrease in command frequency unless P53 - [S-Curve] is set to a value other than 0. ➋ Minimum deceleration time must be set based on the applied motor size. To guard against premature drive failure, do not set P31 - [Decel Time 1] or P70 - [Decel Time 2] below the minimum value listed in the table below. 230 and 460V Motor Sizes 4.0 kW (5 HP) 2.2 kW (3 HP) 1.5 kW (2 HP) 0.75 kW (1 HP) 0.55 kW (0.75 HP) 0.37 kW (0.5 HP)

Minimum Deceleration Settings 0.7 seconds 0.6 seconds 0.2 seconds 0.1 seconds 0.1 seconds 0.1 seconds

This parameter applies only to the Preset Speed model.

Page 52

5-14

Parameters and Programming

Program Group No.

Parameter Name/Description

71

[IR Compensation]

Min./Max. Range 0/150

Units

Factory Default

1%

50%

0.0/5.0

0.1 Hz

2.0 Hz

0/1

Numeric value

0

0/1

Numeric value

0

The programmed value adds a voltage to the output based on the torque current. An additional 31 volts (150%) is added to 460 volt units to compensate for stator resistance. 15.5 volts (150%) is added for 230 volt units. If the drive trips on an F07 - Motor Overload fault, or has trouble accelerating to commanded speed, this value should be reduced. A setting of 0% disables this function.

72

[Slip Compensation] This parameter compensates for the inherent slip in an induction motor. A frequency is added to the commanded output frequency based on torque current. If motor shaft speed decreases significantly under heavy loads then this value should be increased. A setting of 0.0 Hz disables the function. This parameter along with P83 - [PI Process Reference] also activates PI control in drives using Firmware Version FRN 7.06. See page 5-17 for PI Control Setup and Activation instructions. ATTENTION: Hazard of personal injury or equipment damage exists due to unpredictable changes in motor speed. Do not use P72 - [Slip Compensation] and P83 - [Process Reference] to disable PI control while the drive is running. Disable PI control only when the drive is stopped.

73

[Reverse Disable] When this parameter is set to a 1, reverse is disabled. The reverse command may come from the analog input, TB3-5, the keypad or a serial command. With a negative analog input and reverse disabled, the frequency command will be zero in bipolar mode and minimum frequency in unipolar mode. All digital reverse inputs including two-wire Run Reverse will be ignored with reverse disabled. Important: This parameter cannot be programmed while the drive is running.

74

[Analog Select] Settings: 0 = unipolar analog input 0 to +10V 1 = bipolar analog input -10 to +10V

Important: With this parameter set to bipolar (setting 1), the parameter settings for P75 - [Analog Input Minimum] and P32 - [Minimum Frequency] are ignored. In addition, all other reverse inputs (Program Keypad Module, Remote Keypad Module, CopyCat Keypad Module, TB3-5 control terminal block, or serial communication module) are ignored with the exception of when P46 - [Input Mode] is programmed to setting 7. (This applies to drives with firmware version FRN 7.03 and later.) When P46 - [Input Mode] setting 7 is active, and TB3-8 is closed, the frequency source is P58 - [Internal Frequency] and the direction will be commanded from the control terminal block (either terminal TB3-5 or TB3-6). Important: This parameter cannot be programmed while the drive is running. This parameter applies only to the Analog Signal Follower model.