Page 37

Chapter 4

Start-Up Start-Up Procedures This chapter guides you through a basic start-up of the drive using factory default parameter settings. The objective is to verify power and control wiring, set motor direction, control motor speed and prepare you for programming parameters (tuning) if necessary. Refer to Chapter 5 for a complete listing and description of parameters and programming information. ATTENTION: Power must be applied to the drive to perform the following start-up procedure. Some of the voltages present are at incoming line potential. To avoid electric shock hazard or damage to equipment, only qualified service personnel should perform the following procedure. Thoroughly read and understand the procedure before beginning. If an event does not occur while performing this procedure, Do Not Proceed. Remove Power by opening the branch circuit disconnect device and correct the malfunction before continuing.

Start-Up Checklist Verify that the drive is installed per the instructions in Chapter 2, including… • Drive is mounted on a flat, vertical and level surface. • Minimum clearance distance between drive and other equipment. • Proper grounding practices have been followed. • Proper power and control wiring has been used. • No external power applied to control inputs. Verify that AC line power at the disconnect device is within the rated value of the drive. Disconnect and lock out all incoming power to the drive including incoming AC power to terminals R, S and T (L1, L2 and L3) of TB1.

ATTENTION: A DC Bus voltage may be present at TB1 and TB2 for approximately three minutes after power is removed from the drive.

Verify that the motor leads are connected to the power terminal block TB2, terminals U, V, W (T1, T2, T3).

IMPORTANT: Verify that a closed contact input is present at TB3-8. See Chapter 2, Control Wiring for details onTB3-8 functionality when using P46 - [Input Mode] settings 4 through 9.

Confirm that all other control inputs are connected to the correct terminals and are secure.

Remove debris label and reconnect power to drive. continued on next page

Page 38

4-2

Start-Up continued from previous page

Program Keypad Module, Remote Keypad Module or CopyCat Keypad Module Procedure

Ready/Fault Indicating Panel Procedure

The green Ready indicator will illuminate. Use inputs to TB3 to operate the drive.

P01- [Output Frequency] will display. If drive has been previously powered up, a different parameter may display. Important: To enable the Start and Reverse keys on the Program Keypad Module, set P46 - [Input Mode] to 2 and cycle power (or set P56 - [Reset Function] to 2). Refer to P56 in Chapter 5.

Analog Signal Follower Model

Preset Speed Model

Set the frequency source to its minimum setting.

Select P61 - [Preset Frequency 0] by removing all inputs to SW1, SW2, and SW3 on TB3 (see Figure 2.21). The factory default setting for P61 - [Preset Frequency 0] is 3 Hz.

If you are using a Program Keypad Module, verify that the Clockwise LED is illuminated. If you are using a Ready/Fault Indicating Panel, verify that the Reverse input to TB3 is in the Open position. Issue a Start command from the Program Keypad Module or TB3. Drive fan will energize (some models).

If you are using a Program Keypad Module, verify that the Clockwise LED is illuminated. If you are using a Ready/Fault Indicating Panel, verify that the Reverse input to TB3 is in the Open position.

Issue a Start command from the Program Keypad Module or TB3. Check the direction of motor rotation. Drive fan will energize (some models).

Slowly increase the speed until the motor begins to turn. Check the direction of motor rotation.

Issue a Stop command from the Program Keypad Module or TB3.

❶ Start-up is complete!

Yes

Issue a Stop command from the Program Keypad Module or TB3.

Direction of Motor Rotation Correct? No

Disconnect and lock out all incoming power to TB1 terminals R, S and T (L1, L2, and L3).

ATTENTION: A DC Bus voltage may be present at the power terminal blocks TB1 and TB2 for approximately three minutes after power is removed from the drive.

Switch any two of the three motor leads connected to TB2, terminals U, V and W (T1, T2 and T3). Reconnect power. Check rotation.

❶

After successfully completing start-up, proceed to Chapter 5. If you need to change any factory defaults, you will need a Program Keypad Module or other type of Communication Module.

Page 39

Chapter 5

Parameters and Programming Overview of Parameters This chapter describes both Display and Program parameters. Display parameters are read only (they cannot be programmed), while Program parameters can be changed to fit your motor control requirements. A Program Keypad Module, Remote Keypad Module or CopyCat Keypad Module allow you to view or change parameters. Communication Modules (RS1, DN1 or DN2) allow you to view or change parameters with an additional device. A Ready/Fault Indicating Panel cannot be used to view or change parameters. The table below describes which parameters apply to the Preset Speed and Analog Signal Follower models. Parameter Type

Analog Signal Follower Model Parameter Numbers

Preset Speed Model Parameter Numbers

Display

1 – 19

1 – 15, 17 – 19

Program

30 – 62, 65, 66, 69 – 76, 78 – 84

30 – 59, 61 – 73, 78 – 80

Some parameters pertain only to either the Analog Signal Follower or Preset Speed model, not both. ⇐ Indicates that parameter applies only to the Analog Signal Follower Model ⇐ Indicates that parameter applies only to the Preset Speed Model

Review the factory default settings. These parameters can be changed to meet your specific application requirements with any of the following: Program Keypad Module, Remote Keypad Module or CopyCat Keypad Module. The table below provides a list of parameters that are frequently changed. Commonly Changed Parameters Table 5.A Parameter

Setting

Default Setting

P30 - [Accel Time 1]

Desired accel time.

10.0 sec

P31 - [Decel Time 1]

Desired decel time.

10.0 sec

P33 - [Maximum Frequency]

Maximum frequency required.

60 Hz

P34 - [Stop Mode Select]

Desired stopping mode.

0

P35 - [Base Frequency]

Motor rated nameplate frequency.

60 Hz

P36 - [Base Voltage]

Motor rated nameplate voltage.

460V or 230V

P38 - [Boost Select]

Desired V/F boost setting.

2

P42 - [Motor Overload Current]

Motor nameplate Full Load Amps (FLA).

115%

P43 - [Current Limit]

Desired maximum output current.

150%

P46 - [Input Mode]

Desired control method.

0

P47 - [Output Configure]

Desired output relay function.

0

P56 - [Reset Functions]

Desired drive reset description.

0

P58 - [Internal Frequency]

Desired internal frequency.

60.0 Hz

P59 - [Frequency Select]

Desired frequency source.

0

P61 – P68 - [Preset Frequency 0-7] Desired preset frequencies.

0-7

P74 – P76 - [Analog Input]

0, 0.0, 100.0%

Desired analog input functionality.

Refer to the Programming Example on the next page for instructions.

Page 40

5-2

Parameters and Programming

Important Reset Actions You must set P56 - [Reset Functions] to 2 or cycle power after changing the setting of P46 - [Input Mode] for the change to take effect. If you reset to factory defaults, you cannot use the Program Keypad Module for start or reverse control until it is selected using P46 setting 2. Note: P56 - [Reset Functions] must be set to 2 or power must be cycled for the change to take effect. Important:

If you cycle power, you must wait a minimum of one minute for the bus to discharge to zero to ensure the change has taken effect.

An F48 - Reprogram Fault can be cleared using the Program Keypad Module, Remote Keypad Module or CopyCat Keypad Module stop button or by cycling input to TB3-8.

Programming Example The following is an example of the programming steps required to change a Program Group parameter setting. In this example, P31 - [Decel Time] is changed from its factory default setting of 10.0 seconds to 2.2 seconds. Refer to Chapter 3 for an explanation of the Program Keypad Module display and programming keys. Important: Action

To reset ALL values to original factory default settings, refer to P56 - [Reset Defaults].

Description 1. To program the value of a Program Group parameter, enter the Program Group by pressing the ESCape key. The Program Mode Indicator will illuminate. 2. Press the Up/Down keys until the desired parameter displays. In this case, press the Up key until P31 - [Decel Time] displays. 3. Press SELect. The Program Mode Indicator flashes, indicating that you can use the Up/Down keys to change the parameter value. 4. Change the decel time value from the factory default of 10.0 seconds to 2.2 seconds by pressing the Down key until 2.2 displays. Important: Continuously holding the Up or Down key will cause the value to increase or decrease as long as the key is pressed. 5. When the desired value displays, press the Enter key. This writes the new value to memory. The Program Mode Indicator will stop flashing and the display will flash once indicating that the new value has been accepted. Important: If at any time (while in the program mode) you wish to abort the editing process, press the ESCape key. The original value of the parameter will remain unchanged and you will be exited from the Program mode.

Keypad Display

Page 41

Parameters and Programming

5-3

Display Group Parameters (Read Only) This group of parameters consists of commonly viewed drive operating conditions such as output frequency, output voltage, output current and frequency command. All parameters in this group are read only. Important:

The last user-selected Display Group parameter is saved when power is removed and is displayed by default when power is reapplied.

Display Group (Read Only) No. Parameter Name/Description

01

Min./Max. Range 0.0/240.0

Units 0.1 Hz

0/Max Voltage

1 Volt

0/2 x Drive Rated Output Current

0.01A

0/2 x Rated Drive Output Power

0.01 kW 1 Volt

Displays the DC Bus Voltage level.

0/400 - 230V 0/800 - 460V

[Frequency Command]

0.0/240.0

0.1 Hz

0/48

Numeric Value

69/150

1 Degree C

0000/1011

Binary Number

Numeric Value

Numeric Value

Fixed Value

Numeric Value

[Output Frequency] Displays the output frequency at TB2 terminals U, V & W (T1, T2 & T3).

02

[Output Voltage] Displays the output voltage present at TB2 terminals U, V & W (T1, T2 & T3).

03

[Output Current] Displays the output current present at TB2 terminals U, V & W (T1, T2 & T3).

04

[Output Power] Displays the output power present at TB2 terminals U, V & W (T1, T2 & T3).

05 06

[Bus Voltage]

Displays the frequency that the drive is commanded to output. This command may come from any of the frequency sources selected by P59 - [Frequency Select] or from a currently selected preset frequency.

07

[Active Fault] Displays the coded active fault number. If a fault is currently active (has not been cleared) the display will flash. After fault condition is cleared, display will read zero. Refer to P17, P18, and P19 for fault history. See Chapter 6 for fault code descriptions.

08

[Heatsink Temperature] Displays the temperature of the drive heatsink. Note: A display value of 69 indicates a temperature of less than 70°C.

09

[Drive Status] Displays the status of the drive in a binary coded format. Important: 0 = Inactive, 1 = Active.

10

Bit 3 Bit 2

Bit 1

Bit 0 Running Forward Accel Decel

[Drive Type] Used by Rockwell Automation field service personnel.

11

[Firmware Version] Displays version of drive firmware. Used by Rockwell Automation field service personnel.

Page 42

5-4

Parameters and Programming

Display Group (Read Only) No. Parameter Name/Description

12

[Input Status]

Min./Max. Range 0000/1111

Units Binary Number

0.0/180.0

0.1 degrees

Numeric Value

Numeric Value

Preset – 0000/0111

Binary Number

Displays the open (0) and closed (1) state of the inputs to TB3 in binary coded format as follows: Input Mode 0 (3-Wire) Input Mode 1 (2-Wire) Input Mode 2 (Keypad) Input Mode 3 (Mom. Run Fwd./Rev.) Input Mode 4 (Accel/Decel) Input Mode 5 (Coast to Rest) Input Mode 6 (TB3 Control/ Keypad or Comm.) Input Mode 7 (Frequency Select) Input Mode 8 ➊ (SF1 Preset Speed) Input Mode 9 (2-Wire PI control)

Bit 3 Polarity 0= Positive Analog Input 1= Negative Analog Input

Bit 2 TB3-6 Start

Bit 1 TB3-8 Stop

Bit 0 TB3-5 Reverse

Run Forward N/A

Stop

Run Reverse N/A

Run Forward Run Forward Run Forward Run Forward

Stop

0 = TB3 Control 1 = Keypad or Comm.

Run Reverse Run Reverse Run Reverse Run Reverse

Run Forward Run Forward Run Forward

0 = Analog Frequency Select 1 = Internal Frequency Select 0 = Open 1 = Closed 0 = PI 1 = Internal Frequency Select

Run Reverse Run Reverse Run Reverse

Stop

0 = Accel 2/Decel 2 1 = Accel 1/Decel 1 Coast to Rest Stop

➊ Status of Bit 3 for Input Mode 8 is TB3-2 is: 0 = Open, 1 = Closed.

13

[Power Factor Angle] Displays the angle in electrical degrees between motor voltage and motor current.

14

[Memory Probe Display] Used by Rockwell Automation field service personnel.

15

[Preset Status] Displays the open (0) and closed (1) state of TB3 inputs SW1, SW2 and SW3 in binary coded format.

Bit 3 Bit 2

Bit 1

Bit 0 SW1 SW2 SW3 Not Used

16

[Analog Input] Displays the analog input as a percent of full scale. Used in setting P60 - [Zero Offset], P75 - [Analog Input Minimum], and P76 - [Analog Input Maximum]. Important: On initial set up of the drive, apply a 0V or 4 mA analog command to the drive. Once applied, if the value of this parameter displays something other than zero, program that value into P60 - [Zero Offset]. Please note that the value of [Zero Offset] will be subtracted from the value of this parameter. This parameter applies only to the Analog Signal Follower model. This TB3 input applies only to the Preset Speed model.

Analog – 0000/0011

–150.0/+150.0

0.1%

Page 43

Parameters and Programming

Display Group (Read Only) No. Parameter Name/Description

17

5-5

Min./Max. Range Units 0/48 Numeric Value

[Fault Buffer 0] This parameter stores the last fault that occurred. If the same fault occurs multiple times in a row, it will be stored once. After a “reset defaults” (P56) this will set this parameter to F48 - Reprogram Fault. As faults occur, the previous value of this parameter is moved to P18 - [Fault Buffer 1].

18

[Fault Buffer 1]

0/48

Numeric Value

0/48

Numeric Value

This parameter stores the second most recent fault that occurred. After a “reset defaults” (P56) this will set this parameter to 0 (No active fault). As faults occur, the value of this parameter will be overwritten by P17 - [Fault Buffer 0]. The previous value of this parameter is moved to P19 - [Fault Buffer 2].

19

[Fault Buffer 2] This parameter stores the third most recent fault that occurred. After a “reset defaults” (P56) this will set this parameter to 0 (No active fault). As faults occur, the value of this parameter will be overwritten by P18 - [Fault Buffer 1].

Program Group Parameters This group contains parameters whose values can be programmed. Refer to Programming Example earlier in this chapter. Unless otherwise stated, parameters that are programmed while the drive is running take immediate effect. Program Group No.

Parameter Name/Description

30

[Accel Time 1]

Min./Max. Range 0.0/600.0

Time for the drive to ramp from 0.0 Hz. to P33 - [Maximum Frequency]. The rate is linear for any increase in command frequency unless P53 - [S-Curve] is set to a value other than “0”. Setting this to 0.0 sec. gives 0.1 sec acceleration with the initial current limit turned off. This allows quicker acceleration times for low inertia systems. For medium to high inertia systems, the minimum value should be 0.1 sec. Maximum Frequency

0 Accel Time

0 n atio

Acc eler eler atio n

Dec

Speed

Time

Decel Time

Units 0.1 Seconds

Factory Default 10.0 Seconds

Page 44

5-6

Parameters and Programming

Program Group No.

Parameter Name/Description

31

[Decel Time 1]

Min./Max. Range ➊/600.0

Units 0.1 Seconds

Factory Default 10.0 Seconds

0/240

1 Hz

0 Hz

0/240

1 Hz

60 Hz

0/3

Numeric Value

0

10/240

1 Hz

60 Hz

Time for the drive to ramp from P33 - [Maximum Frequency] to 0.0 Hz. The rate is linear for any decrease in command frequency unless P53 - [S-Curve] is set to a value other than 0. ➊ Minimum deceleration time must be set based on the applied motor size. To guard against premature drive failure, do not set P31 - [Decel Time 1] or P70 - [Decel Time 2] below the minimum value listed in the table below. 230 and 460V Motor Sizes 4.0 kW (5 HP) 2.2 kW (3 HP) 1.5 kW (2 HP) 0.75 kW (1 HP) 0.55 kW (0.75 HP) 0.37 kW (0.5 HP)

32 ➋

Minimum Deceleration Settings 0.7 seconds 0.6 seconds 0.2 seconds 0.1 seconds 0.1 seconds 0.1 seconds

[Minimum Frequency] Lowest frequency that drive will output continuously.

33 ➋

[Maximum Frequency] Highest frequency the drive will output. This parameter cannot be changed while running. The value of this parameter setting must be greater than the value set in P32 - [Minimum Frequency].

34

[Stop Mode Select] Determines stopping mode used by the drive when a stop is initiated. Refer to the P44 - [DC Hold Time] and P45 - [DC Hold Voltage] diagrams. Settings: 0 Ramp to Stop 1 Coast to Stop 2 DC Injection Braking 3 DC Injection Braking (w/Auto Shutoff) – works the same as standard DC injection braking except that it may shut off before the P44 - [DC Hold Time]. This occurs if the drive is out of current limit before the P44 - [DC Hold Time] expires.

35

[Base Frequency] Set value to rated nameplate frequency of motor. A Program Keypad Module, Remote Keypad Module or CopyCat Keypad Module is required if P35 must be changed to 50 Hz.

20/460 for 460 for 1 Volt 460V units & 460V units & Set value to rated nameplate voltage of motor. 230 for 20/230 for 230V units 230V units 20/510 for 460 for 1 Volt 37 [Maximum Voltage] 460V units & 460V units & Sets the highest voltage that the drive will output. P37 - [Maximum Voltage] must 20/255 for 230 for be greater than or equal to P36 - [Base Voltage]. 230V units 230V units ➋The analog inputs to the drive (i.e. 4-20mA, 0 to +10 V, or remote potentiometer) can be scaled to P32 - [Minimum Frequency] and P33 - [Maximum Frequency] by programming P75 - [Analog Input Minimum] and P76 - [Analog Input Maximum].

36

[Base Voltage]