Page 33
Chapter 3
Program Keypad Module The Program Keypad Module is located on the front panel of the drive. This module is only operational when it is installed directly on the drive.
Features The Program Keypad Module provides the following features: • 6-digit, 7-segment LED display • Program Mode Indicator • Five keys for programming and displaying drive parameters • Three keys for control inputs to the drive • Two directional LED indicators Program Keypad Module
Figure 3.1 Parameter Number Display Indicates which Display or Program Group parameter is active. Parameter Value/Fault Number Displays the parameter value or fault code number. Program Mode Indicator Flashes when in program mode. Control Inputs and Indicators Direction, Start, Stop (Stop is always active).
Important:
To activate Direction and Start inputs, P46 - [Input Mode] must be set to 2. Power must be cycled or P56 - [Reset Functions] must be set to 2 for the change to take effect.
Display Mode The drive always powers up in the Display mode. While in this mode you may view all read only drive parameters, but not modify them.
Program Mode You enter the Program mode by pressing the ESCape key. While in this mode, you can edit Program Group parameters by pressing the SELect key. The Program Mode Indicator will flash (see Figure 3.1) indicating the parameter value can be changed. The Enter key (↵) must be pressed to write the new value to memory. Refer to Chapter 5 for programming steps.
Page 34
3-2
Program Keypad Module
Key Functions Escape The ESCape key allows you to toggle between the Display and Program modes. When the Program mode is active, this key will disable the editing of a parameter value. Select The SELect key enables editing of a parameter value when the Program mode is active. When you press this key, the Program Mode Indicator flashes. Up/Down Arrow Keys Use the Up/Down Arrow keys to scroll through a list of parameters, or increase and decrease parameter values. Press and hold either key to increase scrolling speed. Real time frequency adjustment can be achieved when using P58 - [Internal Frequency] and P59 - [Frequency Select]. Refer to Chapter 5 for further information. Enter Pressing this key causes the current value displayed to be entered into memory (only while in the Program mode). When you press this key, the Program Mode Indicator remains on, but stops flashing. Direction LEDs (Indicators) The appropriate LED will illuminate continuously to indicate the commanded direction of rotation. If the second LED is flashing, the drive has been commanded to change direction, but is still decelerating. Important:
Actual motor rotation could be different if motor leads are not connected properly. Refer to Chapter 4 for details on how to verify correct motor rotation.
Reverse (Change Direction) This function is only active when P46 - [Input Mode] is set to 2. When active, pressing this key causes the motor to ramp down to 0 Hz and then ramp up to its set speed in the opposite direction. When the motor is running, pressing this key causes the (currently illuminated) LED to flash, indicating motor rotation while decelerating to zero. The other LED will illuminate indicating the commanded direction. Start This function is only active when P46 - [Input Mode] is set to 2. When active, pressing this key initiates a start command. Stop Pressing the Stop key will cause the motor to stop, using the selected stop mode. Refer to the P34 - [Stop Mode] parameter. If the drive has stopped due to a fault, pressing this key will clear the fault. Important:
The Stop key is always active in all control modes.
Page 35
Program Keypad Module
3-3
Module Removal and Installation ATTENTION: Ensure that you disconnect line power and wait three minutes before installing or removing the Program Keypad Module. Failure to do so could result in personal injury or death.
ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing or repairing this assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, reference Publication 8000-4.5.2, “Guarding Against Electrostatic Damage” or any other applicable ESD protection handbook.
Removal Insert a small screw driver into the slot at top of keypad. Carefully pry back and pivot the module out. Avoid bending or twisting the contact pins located underneath the center portion of the module. Figure 3.2
ES
C
SE
L
Removing Program Keypad Module
Page 36
3-4
Program Keypad Module
Installation 1. Insert the module, bottom end first, into the drive. 2. Press on the symbol at the top of the module until it is firmly seated.
It is critical that the Program Keypad Module is firmly seated to ensure circuit integrity. Installing Program Keypad Module
Figure 3.3