Page 23

Installation and Wiring

2-11

Control Methods and Selection Guide You can use P46 - [Input Mode] to select the control method for start, stop, and direction control. Control can be performed from the Control Terminal Block (TB3) or the optional Program Keypad Module or the Remote Programming Adapter via cable to either a Remote Keypad or a CopyCat Keypad depending on the P46 [Input Mode] setting being used. The default setting is 0 which means that only the Control Terminal Block will be active for control. If any other input mode is needed (1-9) you must have a device for changing the input mode such as a Program Keypad Module (160-P1). Table 2.H is a guide to wiring diagrams associated with each P46 - [Input Mode] setting. Important:

After a Stop input, a Run command (either Run Forward, Run Reverse or Start) must be toggled to run again. This is true for all P46 - [Input Mode] settings except setting 3. See the Attention statement below.

ATTENTION: Hazard of injury exists due to unintended operation. When P46 - [Input Mode] is set to 3, and the Run input is maintained, the Run inputs do not need to be toggled after a Stop input for the drive to run again. A Stop function is provided only when the Stop input is active (open). Control Selection by Input Mode P46 Setting

Description

Table 2.H Reference

0

Three-Wire control (factory default)

Figure 2.4

1

Two-Wire Run Forward/Run Reverse control

Figure 2.5

2➊

Program, Remote, CopyCat Keypad or Communication Module control

Figure 2.6

3

Momentary Run Forward/Run Reverse control

Figure 2.7

4

Two-Wire Accel/Decel control

Figure 2.8

5

Two-Wire Enable control

Figure 2.9

6➊

Two-Wire TB3 control/Keypad or Communication control

Figure 2.10

7

Two-Wire Frequency Select control

Figure 2.11

8

Two-Wire Preset control (Analog Signal Follower Models Only)

Figure 2.12

9

Two-Wire PI control (Analog Signal Follower Models Only)

Figure 2.13

➊ When using Firmware Versions FRN 7.05, 7.04 & 7.03, input modes 2 and 6 are the only modes which allow a serial option, such as 160-DN2 or 160 RS1, to command the drive to run or stop.

PI Control Firmware Version FRN 7.06 allows activation of PI control in P46 - [Input Mode] settings 0 through 7 and 9 listed in Table 2.H. Refer to page 5-17 for PI Control Setup and Activation instructions. Users of Firmware Version FRN 7.05 and earlier can only use P46 - [Input Mode] setting 9 to activate PI control. Refer to page 5-17 for PI Control Setup and Activation instructions.

Page 24

2-12

Installation and Wiring

P46 Setting 0 - Three-Wire Control (Factory Default) This input mode provides a typical three wire control function where a momentary start input will command the drive to start. Three-Wire control – Factory Default

Figure 2.4

TB3 5

Reverse

6

Start ➊

7

Common

8

Stop

Note: A contact closure on terminals 7 and 8 is required for the controller to respond to a Start/Run command.

➊ Start input can be a momentary input.

P46 Setting 1 - Two-Wire Run Forward/Run Reverse Control This input mode provides a typical two wire control function where a maintained Run Forward or Run Reverse input will provide both a directional and start command to the drive. Opening the Run Forward or Run Reverse input will command the drive to stop in accordance with the P34 - [Stop Mode] setting. The stop switch (TB3-7 and 8) is not required but can be wired as an Auxiliary Stop if desired. Two-Wire Run Forward/Run Reverse control

Figure 2.5

TB3

5

Run Reverse

6

Run Forward

7

Common

8

Stop

Note: A contact closure on terminals 7 and 8 is required for the controller to respond to a Start/Run command.

Page 25

Installation and Wiring

2-13

P46 Setting 2 - Program Keypad or Communication Module Control This input mode activates the Start and Reverse functions from either the Program Keypad Module (PKM), Remote Keypad Module, CopyCat Keypad Module or plug in communication modules and deactivates the Start and Reverse inputs on the control terminal block (TB3). Note: the frequency reference can be controlled from the keypad modules or communication modules by setting P59 - [Frequency Select] to a setting of “1”. The frequency will then be controlled by the value programmed into P58 - [Internal Frequency]. Program Keypad Module control

Figure 2.6

TB3 5

Reverse ➊

6

Start ➊

7

Common

8

Stop

Note: A contact closure on terminals 7 and 8 is required for the controller to respond to a Start/Run command.

➊ When performing start and reverse operations from the Program Keypad Module, Remote Keypad Module, CopyCat Keypad Module or plug-in communication modules, the Start and Reverse inputs from the Control Terminal Block (TB3) are disabled.

P46 Setting 3 - Momentary Run Forward/Run Reverse Control This input mode allows the drive to respond to either a momentary or maintained Run Forward or Run Reverse input, but requires a stop input to TB3 terminals 7 and 8 to command the drive to stop. In addition, this is the only input mode that uses “level triggered” control logic, therefore once the stop command is removed or if power is lost and restored, the drive will immediately restart if a maintained Run command is present. Momentary Run Fwd/Run Rev control

Figure 2.7

TB3

5

Run Reverse ➊

6

Run Forward ➊

7

Common

8

Stop ➋

Note: A contact closure on terminals 7 and 8 is required for the controller to respond to a Start/Run command.

ATTENTION: Hazard of injury exists due to unintended operation. When P46 - [Input Mode] is set to 3, and the Run input is maintained, the Run inputs do not need to be toggled after a Stop input for the drive to run again. A Stop function is provided only when the Stop input is active (open). ➊ A momentary or maintained input can be used. If using maintained inputs, please read the Attention statement above. ➋ A normally closed maintained input is recommended. See Attention statement above.

Page 26

2-14

Installation and Wiring

Important:

Settings 4 through 9 provide additional flexibility of TB3 control input terminal 8.

P46 Setting 4 - Two-Wire Accel/Decel Control This input mode is similar to Setting 1 except TB3 terminal 8 provides the function of switching from P30 - [Accel Time 1] and P31 - [Decel Time 1] to P69 - [Accel Time 2] and P70 - [Decel Time 2] for any commanded frequency reference. Two-Wire Accel/Decel control

Figure 2.8

TB3

5

Run Reverse

6

Run Forward

7

Common

8

Accel/Decel Select ➊

TB3-8 Open Accel 2, Decel 2 TB3-8 Closed Accel 1, Decel 1

➊ TB3 terminal 8 can be used to clear faults. See Figure 2.14 for details.

P46 Setting 5 - Two-Wire Enable Control This input mode is similar to Setting 1 except TB3 terminal 8 provides the function of “enable” command. The “enable” input is required for the drive to operate and if opened during operation the programmed P34 - [Stop Mode] will be overridden and the motor will coast to rest. Two-Wire Enable control

Figure 2.9

TB3

5

Run Reverse

6

Run Forward

7

Common

8

Enable ➊

TB3-8 Open Controller Disabled ➋ TB3-8 Closed Controller Enabled

➊ TB3 terminal 8 can be used to clear faults. See Figure 2.14 for details. ➋ When this input is in an open state, the motor will coast to rest.

Page 27

Installation and Wiring

2-15

P46 Setting 6 - Two-Wire TB3 Control/Keypad or Communication Control This input mode is similar to Setting 1 except TB3 terminal 8 provides the function of switching the start, reverse and speed reference from the Program Keypad Module, Remote Keypad Module, CopyCat Keypad Module, or Communication Module to the control terminal block (TB3). Two-Wire TB3 control/Keypad or Communication control

Figure 2.10

TB3

5

Run Reverse

6

Run Forward

7

Common

8

TB3/Keypad or Communication ➊

TB3-8 Open TB3 Control ➋ TB3-8 Closed Keypad or Communication Control

➊ TB3 terminal 8 can be used to clear faults. See Figure 2.14 for details. ➋ When this input is in an open state the Frequency source is always from the terminal block regardless of the setting of P59 - [Frequency Select].

P46 Setting 7 - Two-Wire Frequency Select Control This input mode is similar to Setting 1 except TB3 terminal 8 provides the function of switching the frequency reference from the control terminal block (TB3) to the frequency commanded by P58 - [Internal Frequency]. For Analog Signal Follower models this provides the ability to switch from analog control to one preset speed. For Preset Speed models this provides a ninth preset speed via P58 - [Internal Frequency]. Two-Wire Frequency Select control TB3

5

Run Reverse

6

Run Forward

7

Common

8

Frequency Select ➊

Figure 2.11 TB3-8 Open External (TB3) Frequency Command TB3-8 Closed Internal (P58) Frequency Command

➊ TB3 terminal 8 can be used to clear faults. See Figure 2.14 for details.

Page 28

2-16

Installation and Wiring

P46 Setting 8 - Two Wire Preset Speed Control (Analog Models Only) This input mode is similar to Setting 1 except TB3 terminals 1, 2 and 8 provide the function of preset speeds. Note: All analog functionality is disabled when using this input mode setting. Two-Wire Preset control Figure 2.12 TB3

1

+10V

2

SW1

3

Common

4

4 – 20 mA input ➊

5

Run Reverse

6

Run Forward

7

Common

8

SW2 ➋

TB3-2 and TB3-8 See Table 2.I below

TB3 Terminal 2 and 8 Switch Definitions SW2 Position TB3-8 Open (0)

SW1 Position TB3-2 Open (0)

Open (0)

Closed (1)

Closed (1)

Open (0)

Closed (1)

Closed (1)

Speed Reference Parameter 61 (Preset 0) Parameter 62 (Preset 1) Parameter 65 (Preset 4) Parameter 66 (Preset 5)

Table 2.I Accel Rate Parameter 30

Decel Rate Parameter 31

Parameter 30

Parameter 31

Parameter 69

Parameter 70

Parameter 69

Parameter 70

➊ Do not connect to TB3-4 in this mode. ➋ TB3 terminal 8 can be used to clear faults. See Figure 2.14 for details.

Page 29

Installation and Wiring

2-17

P46 Setting 9 - Two-Wire PI Control (Analog Models Only) This input mode is similar to Setting 1 except TB3 terminal 8 provides the function of PI Control. Two-Wire PI control Figure 2.13 TB3

TB3

3

Common

4

2

0 – 10V DC

4 – 20 mA

3

Common

5

➊

6

Run Forward

7

Common

8

OR

PI/Internal Frequency ➋

TB3-8 Open PI TB3-8 Closed Internal Frequency

Refer to Chapter 5, 160 PI Control Setup for a detailed PI Control Setup description. ➊ Do not connect to TB3-5 in this mode. ➋ TB3 terminal 8 can be used to clear faults. See Figure 2.14 for details

Important:

For P46 - [Input Mode] settings 4 through 9, Terminal TB3-8 is also used to clear faults. See figure below for details.

TB3-8 – Clear Faults

Figure 2.14

TB3-8 Closed TB3-8 Open Fault Occurs Important:

Fault Clears

Fault Occurs

Fault Clears

The system programmer is responsible for returning terminal TB3-8 to its original state if necessary.

Page 30

2-18

Installation and Wiring

When connecting a single input such as Run, Stop, Reverse or Preset Speeds to multiple drives, it is important to connect the commons (TB3-7) together for all drives. If they are to be tied into another common (such as earth ground or separate apparatus ground) only one point of the daisy chain of TB3-7 should be connected. Predicting actual performance given the variety of installation possibilities is difficult, however, up to five drives with two meters of cable between have been tested without problems. Typical Multiple Drive Input Connections TB3

5

6

7

5

Customer Inputs

6

7

Figure 2.15 5

6

7

5

6

7

Optional Ground Connection

Configurable Relay Output Contacts (P47 Settings) You can configure the drive’s dry contact Form C output relay to change state based on P47 - [Output Configure] setting and P48 - [Output Threshold] limits. See Chapter 5 for details. Configurable Relay Output Contacts

Figure 2.16

TB3 9

Normally Closed

10

Relay Common

11

Normally Open

User Configurable Relay Outputs (Form C Relay) Resistive Load = 0.4A at 125V AC, 2A at 30V DC Inductive Load = 0.2A at 125V AC, 1A at 30V DC To set up, use P47 - [Output Configure]

Frequency Source Wiring Analog Signal Follower Model You can control the output frequency of the drive via the Control Terminal Block (TB3) using the following methods. Analog Frequency Sources Important:

Only one frequency source may be connected at a time. If more than one reference is connected at the same time, an undetermined frequency reference will result.

Page 31

Installation and Wiring

±10V or 0 – 10V DC Frequency Control/Speed Control

2-19

Figure 2.17

TB3

2

±10V or 0 – 10V DC

If calibration is required, use parameters 16, 59, 60, 74, 75, 76

3

Common

Controller Input Impedance = 100k Ohms

4 – 20 mA Frequency Control/Speed Control

Figure 2.18

TB3

3

Common

If calibration is required, use parameters 16, 59, 60, 74, 75, 76

4

4 – 20 mA

Controller Input Impedance = 250 Ohms

Potentiometer Frequency Control/Speed Control

Figure 2.19

TB3

1

10V DC Supply

2

Wiper

3

Common

If calibration is required, use parameters 16, 59, 60, 74, 75, 76 10k Ohms, 2 Watt Linear Taper

When connecting a single potentiometer to multiple drives it is important to connect commons (TB3-3) together for all drives. TB3-3 (common) and TB3-2 (potentiometer wiper) should be daisy-chained to each drive. All drives must be powered up for the analog signal to be read correctly. Predicting actual performance given the variety of installation possibilities is difficult, however, up to five drives with two meters of cable between have been tested without problems. Typical Multiple Drive Analog Connection TB3

1

2

3

1

2

3

Figure 2.20

1

2

3

1

2

3

Optional Ground Connection Preset Frequency Sources The Analog Signal Follower model has a special input mode, P46 setting 8 that allows the drive to be operated via preset speed inputs. See Figure 2.12 and Table 2.I for details.

Page 32

2-20

Installation and Wiring

Preset Speed Model You can control the output frequency of the drive via the Control Terminal Block (TB3) using dry contacts or open collector inputs to SW1, SW2, and SW3 (see Figure 2.21). Important:

Refer to parameters 61 – 68 in Chapter 5 for the eight preset frequency factory default settings and switch configurations. A program keypad module is required to change the factory default settings.

TB3 Control Wiring for Preset Speed Model

Figure 2.21

TB3 1

SW1 ➊

2

SW2 ➊

3

Common ➋

4

SW3 ➊

To select/program preset speeds, use parameters 61 – 68

➊ Internal 12V supply. Contact closure or open collector input required. Refer to Appendix A for solid state control input specifications. ➋ Control signal cable length is highly dependent on electrical environment and installation practices. To improve noise immunity, TB3 Common must be connected to ground terminal/protective earth. For control wiring installations greater than 15 meters (50 feet) in length, an optional 24V DC interface module is recommended. See Appendix A for ordering information.

Analog and Preset Models Internal Frequency Source Both the Analog Signal Follower and Preset Speed models have the provision for frequency control via P58 - [Internal Frequency]. This is accomplished by setting P59 - [Frequency Select] to a value of 1. See Chapter 5 for a description of these parameters.

What To Do Next You should become familiar with the Program Keypad Module operation in Chapter 3 if you need to change any factory default parameter settings for your application. Then proceed to Chapter 4, Start-Up and follow the flow diagram. After applying power, you can program parameters if necessary. Refer to Table 5.A for a list of commonly changed parameters.