160 SSC Variable Speed Drive (Series C) User Manual: Chapter 2, pages 13 to 22

Pages 13 to 22 of 88, from 160 SSC Variable Speed Drive (Series C) User Manual

The original document is the PDF (2.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Allen-Bradley 160-BMB2 and Allen-Bradley 160-DM-PS1

Page 13

Chapter 2

Installation and Wiring Storage and Operation Conditions Follow these recommendations to prolong drive life and performance: • Store within an ambient temperature range of –40° to +85°C. • Store within a relative humidity range of 0% to 95%, non-condensing. • Protect the cooling fan by avoiding dust or metallic particles. • Avoid storing or operating the drive where it could be exposed to a corrosive atmosphere. • Protect from moisture and direct sunlight. • Operate at an ambient temperature range of 0° to +50°C.

CE Compliance Refer to Appendix C.

Installation Mount the drive on a flat, vertical and level surface. See Chapter 1, Figure 1.3 for mounting orientation. Choose an installation method: • Install with screws. Recommended screw size is listed in the table below. The appropriate drilling template for your drive is provided in Appendix B. • Install on 35 mm DIN Rail. This mounting method is not available on 4.0 kW (5 HP) three phase or 1.5 kW (2 HP) single phase models. Description Minimum Panel Thickness (14 GA) Mounting Base Screws Mounting Torque

Metric 1.9 mm m4 x 0.7 1.13 – 1.56 Nm

English 0.0747 in. # 8-32 10 – 14 lb.-in.

See Appendix B for details on drive dimensions and weights.

Clearances Maintain 12.5 mm (0.5 in.) clearance at the top, bottom, and front of all drives. Clearance requirements between units varies by model. • 2.2 kW (3 HP) 230V/460V Drives Provide a minimum of 8.5 mm (0.33 in.) clearance between units. • All Other Drive Ratings No clearance is required between units.

Debris Label The drive is shipped with a paper debris label attached to the top side of the plastic housing to cover the cooling vents. Leave the debris label attached during drive installation to protect against debris falling through the vents of the drive housing. To assure proper drive operation, you must remove label before applying power. ATTENTION: After system installation, remove the debris label from unit. Failure to remove this label may result in overheating or nuisance tripping.

Page 14

2-2

Installation and Wiring

Power Wiring Precautions ATTENTION: Remove and lock out power from the drive before you disconnect or reconnect wires or perform service. Verify bus voltage by measuring the voltage between DC- and DC+ on Terminal Block TB2. Do not attempt to service the drive until bus voltage has discharged to zero volts. ATTENTION: The drive is intended to be commanded by control input signals that will start and stop the motor. A device that routinely disconnects then reapplies input power to the drive for the purpose of starting and stopping the motor should not be used. If it is necessary to use this method for starting and stopping, or if frequent cycling of power is unavoidable, make sure that it does not occur more than once a minute. ATTENTION: Do not connect power factor correction capacitors to drive output terminals U, V and W (T1, T2 and T3) or component damage could occur.

Terminal Blocks Terminal R (L1) is not present on single phase drives. Three phase unit terminal block configuration is depicted in the figure below. Drive Terminal Blocks

Figure 2.1 TB1

R/L1 S/L2 T/L3 BR– BR+

Terminal Block TB1 Ground, Line Power & Dynamic Brake Module Wiring Hazardous Voltages Behind Panel

FAULT READY

1 2 3 4 5 6 7 8 9 10 11

TB3

Terminal Block TB3 Control Wiring

TB2

Terminal Block TB2 Ground, Motor & Capacitor Module Wiring

U/T1 V/T2 W/T3 DC– DC+

Page 15

Installation and Wiring

2-3

Terminal Block Wiring Terminal Block Wiring Detail

Figure 2.2 Required Branch Circuit Disconnect ➊

Branch Circuit Protective Device ➋ Terminal Block TB1

R/L1 S/L2 T/L3 BR– BR+ Ground Terminal/Protective Earth

U/T1 V/T2 W/T3 DC– DC+ Terminal Block TB2

Motor ➌

Specifications Terminal Block TB1 and TB2 Wiring Specifications Model

Screw Size

4.0 kW (5 HP) All Other Ratings

M4 M4

Max./Min. Wire Size ➍ mm2 (AWG) 5.26 – 3.31 (10 – 12) 3.31 – 0.82 (12 – 18)

Table 2.A Max./Min. Torque Nm (lb.-in.) 1.35 – 0.90 (12 – 8) 1.35 – 0.90 (12 – 8)

➊ For single phase input applications, connect the AC input power to input terminals S (L2) and T (L3). ➋ See Table 2.B for minimum recommended branch circuit protective devices. ➌ Bulletin 160 Drives are UL Listed (see Appendix A for details) as motor overload protective devices (IEC Class 10 overload). An external overload relay is not required for single motor applications as long as the Drive kW (HP) rating is less than three times larger than the motor kW (HP) rating. ➍ Each terminal supports up to 2 wires of approved gauge.

Page 16

2-4

Installation and Wiring

Motor Branch Circuit Analysis Short circuit and overload protection are requirements of any motor branch circuit. Input power conditioning, CE conformance, reflective wave, capacitive current coupling, and motor cable type are important considerations of drive applications. Branch Circuit Configuration

Figure 2.3

Branch Circuit Protective Devices – See Table 2.B Input Power Conditioning – See Table 2.C CE Conformance – See Appendix C 160 SSC™ Motor Cable Types – See Table 2.D Reflected Wave Protection – See Table 2.E Capacitive Current Coupling – See Table 2.F Overload Protection Motor • Branch Circuit Protective Devices A motor branch circuit requires protection against excessive current. This protection can be provided by a fuse, circuit breaker, or manual motor starter. See Table 2.B for a detailed list of these options. • Input Power Conditioning Certain conditions may exist that could damage a drive in the branch circuit. See Table 2.C for an explanation of problems and solutions. • CE Conformance See Appendix C for information on CE Conformance. • Motor Cable Types See Table 2.D for recommended cable types. • Reflected Wave Protection The use of a drive may result in increased peak-to-peak voltage at the motor. See Table 2.E for an explanation of motor insulation limitations versus cable lengths. • Capacitive Current Coupling High speed voltage switching causes AC coupling from motor cables to ground terminal/protective earth. See Table 2.F for cable length recommendations. • Overload Protection All motor branch circuits require overload protection. The Bulletin 160 Drive is UL listed to provide protection (IEC Class 10 overload) without an overload relay. Separate overload relays are required in multi-motor applications or if the drive kW (HP) rating is more than three times larger than the motor kW (HP) rating.

Page 17

Installation and Wiring

2-5

Branch Circuit Protective Devices Fusing The Bulletin 160 Smart Speed Controller has been UL tested and approved for use with input fuses. The ratings in the table below are the minimum recommended values for use with each drive rating. The devices listed in this table are provided to serve as a guide. Other devices which meet the requirements of UL508C and UL489 with similar trip characteristics may be used in order to meet local or national electrical codes. Bulletin 140 Manual Motor Starters/UL489 Circuit Breakers When using Bulletin 140 manual motor starters or UL489 rated circuit breakers, the guidelines listed below must be followed in order to meet the NEC requirements for branch circuit protection. • Bulletin 140 manual motor starters can be used in single and group motor applications. • In single motor applications, a fuse or UL489 rated circuit breaker is required ahead of the Bulletin 140 manual motor starter. • In group motor installations, the Bulletin 140 can be used for protection of an individual motor within the group and “one set” of fuses or a UL489 rated circuit breaker serves as the Branch Circuit Protective Device for the entire “Group Installation”. • Bulletin 140M manual motor starters can be used in single and group motor applications without additional short circuit protection. Refer to the technical support literature for the 140M for more details. Minimum Recommended Branch Circuit Protective Devices ➊ Voltage Rating

Drive Rating kW (HP)

Single Phase 230V

0.37 (0.5) 0.55 (0.75) 0.75 (1) 1.5 (2) 0.37 (0.5) 0.55 (0.75) 0.75 (1) 1.5 (2) 2.2 (3) 4.0 (5) 0.37 (0.5) 0.55 (0.75) 0.75 (1) 1.5 (2) 2.2 (3) 4.0 (5)

Three Phase 230V

Three Phase 460V

Table 2.B

Fuse Rating ➋ UL489 Rated Bulletin 140/140M Circuit Breaker Manual Motor Starter Amps Amps 6 16 16 10 16 16 15 16 16 30 20 20 6 16 16 6 16 16 10 16 16 15 16 16 20 20 20 30 30 30 4 6 6 4 6 6 5 6 6 8 16 16 15 16 16 20 20 20

➊ The maximum branch circuit protection rating is limited to four times the rated output current of the drive or 30A, whichever is less. ➋ Fuse class CC, J, BS88, VDE 06366/gG, IEC 269-1/gG, EN60269 part 1 and 2 type gG

Page 18

2-6

Installation and Wiring

Input Power Conditioning The drive is suitable for direct connection to input power within the rated voltage of the drive (see Appendix A). Listed in Table 2.C are certain input power conditions which may cause component damage or reduction in product life. If any of the conditions exist, as described in Table 2.C, install one of the devices listed under the heading Corrective Action on the line side of the drive. Important:

Only one device per branch circuit is required. It should be mounted closest to the branch and sized to handle the total current of the branch circuit.

Input Power Conditions Input Power Condition Low Line Impedance (less than 1% line reactance)

Available short circuit currents (fault currents) greater than 100,000 Amps Greater than 120 kVA supply transformer Line has power factor correction capacitors Line has frequent power interruptions Line has intermittent noise spikes in excess of 6000V (lightning)

Table 2.C Corrective Action • Check Line Impedance • Line Reactor (See Appendix B) • or Isolation Transformer • Check Supply Transformer • Line Reactor (See Appendix B) • or Isolation Transformer • Line Reactor (See Appendix B) • or Isolation Transformer • Line Reactor (See Appendix B) • or Isolation Transformer • Line Reactor (See Appendix B) • or Isolation Transformer • Line Reactor (See Appendix B) • or Isolation Transformer

Motor Cable Types A variety of cable types are acceptable for variable speed drive installations. For many installations, unshielded cable is adequate, provided it can be separated from sensitive circuits. As an approximate guide, allow a spacing of 1 meter (3.3 feet) for every 10 meters (33 feet) of unshielded length. If you cannot separate motor cables from sensitive circuits, or if you must run motor cables from multiple drives (more than three) in a common conduit or cable tray, shielded motor cable is recommended to reduce system noise. Motor cables should be four-conductor with the ground lead and shield (if using shielded cable) connected to the drive ground terminal and the motor frame ground terminal. Table 2.D provides the recommended wire type for both wet and dry installations as defined by NEC 1996 (70-31). These recommendations are based upon a variety of factors such as insulation thickness, susceptibility to moisture and susceptibility to nicks and cuts during installation. Recommended Cable Type Table 2.D Condition Dry Wet

Insulation Type PVC ➊ XLPE XLPE

Example THHN XHHW-2 XHHW-2

➊ For input power voltages in excess of 264VAC, or motor cable distances greater than 15 meters (50 feet), wire with XLPE insulation is recommended.

Page 19

Installation and Wiring

2-7

Long Motor Cable Effects Reflected Wave Protection The drive should be installed as close to the motor as possible. Installations with long motor cables may require the addition of external devices to limit voltage reflections at the motor (reflected wave phenomena). See Table 2.E for recommendations. Important:

Both Reflected Wave and Capacitive Current Considerations need to be taken into account when determining motor cable lengths (see Table 2.E and Table 2.F). The use of an external device to limit reflected wave phenomenon may effect the accuracy of Bulletin 160 current sensing.

The reflected wave data applies to all frequencies 2 to 8 kHz. For 230V ratings, the maximum cable length recommendations are the same as the capacitive current recommendations (see Table 2.F). Cable Length Recommendations – Reflected Wave Table 2.E Motor Cable Only RWR at Drive ➊ Reactor at Motor Shielded Unshielded Shielded Unshielded Shielded Unshielded feet meters feet meters feet meters feet meters feet meters feet meters 4.0 kW 1000 Vp-p 45 13.7 20 6.1 525 160 600 183 325 99.1 300 91.5 (5 HP) 1200 Vp-p 90 27.4 40 12.2 525 160 600 183 525 160 425 130 1600 Vp-p ➋ 525 160 475 145 525 160 600 183 525 160 600 183 2.2 kW 1000 Vp-p 40 12.2 40 12.2 525 160 600 183 225 68.6 250 76.2 (3 HP) 1200 Vp-p 90 27.4 60 18.3 525 160 600 183 325 99.1 425 130 1600 Vp-p ➋ 525 160 500 152 525 160 600 183 525 160 600 183 1.5 kW 1000 Vp-p 40 12.2 40 12.2 425 130 600 183 325 99.1 300 91.5 (2 HP) 1200 Vp-p 90 27.4 60 18.3 425 130 600 183 425 130 450 137 1600 Vp-p ➋ 500 152 500 152 425 130 600 183 540 165 600 183 0.75 kW 1000 Vp-p 55 16.8 40 12.2 325 99.1 600 183 325 99.1 350 107 (1 HP) 1200 Vp-p 125 38.1 60 18.3 325 99.1 600 183 500 152 450 137 1600 Vp-p ➋ 500 152 500 152 325 99.1 600 183 500 152 600 183 0.55 kW 1000 Vp-p 45 13.7 40 12.2 300 91.5 600 183 300 91.5 300 91.5 (0.75 HP) 1200 Vp-p 125 38.1 60 18.3 300 91.5 600 183 500 152 500 152 1600 Vp-p ➋ 500 152 500 152 300 91.5 600 183 500 152 600 183 0.37 kW 1000 Vp-p 45 13.7 90 27.4 300 91.5 425 130 300 91.5 425 130 (0.5 HP) 1200 Vp-p 125 38.1 180 54.9 300 91.5 425 130 500 152 500 152 1600 Vp-p ➋ 500 152 500 152 300 91.5 425 130 500 152 500 152 380Motor 460V Insulation Ratings Rating

➊ Cable lengths listed are for PWM frequencies of 2 kHz. Refer to publication 1204-5.1 for cable length recommendations at other PWM frequencies. ➋ The maximum peak-to-peak voltage of the drive is 1400V due to the minimum on/off time software. Reflective Wave Testing has been done on cable lengths up to 160 meters (600 feet). See Table 2.F for capacitive current recommendations.

Page 20

2-8

Installation and Wiring

Capacitive Current Coupling AC coupling exists from motor cables to ground terminal/protective earth. The current produced by this coupling is referred to as capacitive current. The drive current is the combination of capacitive current and motor current. Because motor current is monitored for overload protection, the table below lists the maximum cable length recommendations that will assure a capacitive current error of less than 15 percent. Cable Length Recommendations, Capacitive Current Table 2.F 380-460V kHz Ratings 4.0 kW (5 HP) 2.2 kW (3 HP) 1.5 kW (2 HP) 0.75 kW (1 HP) 0.55 kW (0.75 HP) 0.37 kW (0.5 HP)

2 4 8 2 4 8 2 4 8 2 4 8 2 4 8 2 4 8

200-240V Ratings 0.37 to 4.0 kW (0.5 to 5 HP) 2 through 8 kHz

Motor Cable Only RWR at Drive ➊ Reactor at Motor Shielded ➋ Unshielded Shielded ➋ Unshielded Shielded ➋ Unshielded feet meters feet meters feet meters feet meters feet meters feet meters 350 107 600 183 300 91.5 600 183 400 122 600 183 425 130 600 183 350 107 600 183 450 137 600 183 475 145 500 152 ➊ 450 137 500 152 360 110 600 183 280 85.4 600 183 400 122 600 183 375 114 600 183 275 83.8 600 183 400 122 600 183 400 122 500 152 ➊ 400 122 500 152 300 91.5 550 168 275 83.8 600 183 300 91.5 600 183 300 91.5 550 168 275 83.8 600 183 300 91.5 500 152 325 99.1 500 152 ➊ 350 107 500 152 200 61 375 114 200 61 425 130 225 68.6 400 122 225 68.6 375 114 200 61 425 130 225 68.6 375 114 250 76.2 375 114 ➊ 225 68.6 400 122 180 54.9 350 107 180 54.9 375 114 180 54.9 350 107 180 54.9 350 107 180 54.9 375 114 180 54.9 350 107 180 54.9 350 107 ➊ 180 54.9 350 107 100 30.5 325 99.1 100 30.5 350 107 100 30.5 300 91.5 100 30.5 325 99.1 100 30.5 350 107 100 30.5 350 107 100 30.5 325 99.1 ➊ 100 30.5 350 107 No Reactor RWR at Drive ➊ Reactor at Motor Shielded ➋ Unshielded Shielded ➋ Unshielded Shielded ➋ Unshielded feet meters feet meters feet meters feet meters feet meters feet meters 525 160 600 183 ➌ 525 160 600 183

➊ Not recommended for use above 4 kHz PWM Frequency. ➋ When using shielded cable at lightly loaded conditions, cable length recommendations for drives rated 0.75 kW (1 HP) and below are 61 meters (200 feet). ➌ Not recommended for 230V applications.

Page 21

Installation and Wiring

2-9

Control Wiring Requirements • Run all signal wiring in either a shielded cable or separate metal conduit. • Connect shield wire only at TB3 Common terminals (3 and 7). • Do not exceed control wiring length of 15 meters (50 feet). Control signal cable length is highly dependent on electrical environment and installation practices. To improve noise immunity, the control terminal block Common must be connected to ground terminal/protective earth. • Use Belden 8760 (or equivalent), 18 AWG (0.750 mm2), twisted pair, shielded or 3 conductor.

Specifications Control Terminal Block TB3 Wiring Specifications Terminal Block TB3

Max./Min. Wire Size mm2 (AWG) 2.5 – 0.5 (14 – 22)

Table 2.G

Max./Min. Torque Nm (lb.-in.) 0.8 – 0.4 (8 – 4)

Important Precautions ATTENTION: The drive is supplied with an internal 12V supply. Dry contact or open collector inputs are required for discrete control inputs. If an external voltage is applied, component damage could occur. TB3 5 6

NO! 7

External Power Supply

8 ATTENTION: The drive start/stop and enable control circuitry includes solid-state components. If hazards due to accidental contact with moving machinery or unintentional flow of liquid, gas or solids exist, an additional hardwired stop circuit is required to remove AC input power to the drive. When AC input power is removed, there will be a loss of inherent regenerative braking effect and the motor will coast to a stop. An auxiliary braking method may be required.

Page 22

2-10

Installation and Wiring

Control Wiring Considerations Wiring Diagram Key

Shielded Wire

N.O. Momentary Contact

N.C. Momentary Contact

N.O. Maintained Contact

N.C. Maintained Contact

General Control Wiring Advisories The figure below lists the control wiring requirements for all two wire control input modes (P46 - [Input Mode] settings 1 and 4 – 9). The requirements specific to each input mode are shown separately for that mode. TB3

5

➊➋➌

6

➊➋➌

7

➍

8

➋

➊ Run input must be maintained. After a stop command, either a Run Forward or Run Reverse input must be toggled to start the drive. ➋ Internal 12V supply. Contact closure or open collector input required. Refer to Appendix A for solid state control input specifications. ➌ If both Run Forward and Run Reverse inputs are closed at the same time, an undetermined state could occur. ➍ Control signal cable length is highly dependent on electrical environment and installation practices. To improve noise immunity, TB3 Common must be connected to ground terminal/protective earth. For control wiring installations greater than 15 meters (50 feet) in length, an optional 24V DC interface module is recommended. See Appendix A for ordering information.