Page 77
Appendix C
CE Conformity CE Compliance This drive is a component intended for implementation in machines or systems for the industrial environment. It is CE marked for conformity to the Low Voltage (LV) Directive 73/23/EEC when installed as described. It also has been tested to meet the Council Directive 89/336 Electromagnetic Compatibility (EMC). The standards used for this testing are, LV: EN50178, EN60204-1, EMC EN61800-3, EN50081-1, EN50082-2. These tests were conducted with a PWM frequency (Parameter 49) of 4.0 kHz. Important:
The conformity of the drive and filter to any standard does not guarantee that the entire installation will conform. Many other factors can influence the total installation and only direct measurements can verify total conformity. It is therefore the responsibility of the machine manufacturer, to ensure, that the conformity is met.
A copy of the Declaration of Conformity (DOC) is available from your local Rockwell Automation Sales Office.
Essential Requirements for a Conforming EMC Installation The following seven items are required for CE Conformance: 1. An input line filter module (see Appendix B, Accessories and Dimensions) must be installed to reduce conducted emissions. 160-LF Filters These units have been tested with a maximum motor cable length of 75 meters (250 feet) for drives rated 200 – 240VAC, and 40 meters (133 feet) for drives rated 380 – 460VAC. 160S-RF Filters These units have been tested with a maximum motor cable length of 25 meters (80 feet) for both 230V and 460V units. 2. The drive system must be mounted in a shielded enclosure to reduce radiated emissions. 3. Grounding of equipment and cable shields must be solid, with low impedance connections. 4. Motor and control cables entering the shielded enclosure must have EMCtested shielded cable clamps, or grounded metal conduit. 5. All motor cables must use shielded cable, or be in grounded metal conduit. 6. All control and signal wiring must use shielded cable or be in grounded metal conduit. 7. The Common terminals (TB3-3 and 7) must have a solid connection to ground terminal/protective earth.
Page 78
C-2
CE Conformity
General Instructions for an EMC Compliant Installation Shielded Enclosure • Typical NEMA or IEC metal enclosures are adequate. • The ground connection of the shielded enclosure must be solidly connected to the PE terminal of the drive. Good conductivity must be assured – grounding must provide a low impedance path for high frequency signals. • All wiring, except input power leads, must use shielded cable. • Input power, output power and control wiring inside the enclosure must be physically separated. • Input power, output power and control wiring outside the enclosure must use separate shielded cables, or separate conduit. • Wires do not touch the heatsink.
Recommended Grounding Configuration Enclosure Ground Connection
PE
AC Input Line
Figure C.1
T/L3
T (L3) Line S (L2)
S/L2
R (L1)
R/L1
Filter
Line Power TB1 Ground Terminal – PE
R/L1 S/L2 T/L3 BR– BR+
FAULT READY to TB3 1 2 3 4 5 6 7 8 9 10 11
Ground Terminal – PE
Control Cabinet ➊
Control Wiring TB3
U/T1 V/T2 W/T3 DC– DC+
Motor Wiring TB2 W/T3 V/T2 U/T1 Shielded Enclosure
= EMC Tested Shielded Cable Clamp (or Metal Conduit) ➊ When the control circuitry is located outside of the 160 enclosure.
Shielded Motor Cable to Motor
Page 79
CE Conformity
C-3
Cable Clamps • Use suitable EMC-tested cable clamps only. • The connection area must be 360 degrees around the shielded cable. • The cable clamps also provide strain-relief for the cable. • When using conduit, the contact point of metal entry connections must be free of paint or non-conductive surfaces and solidly connected with good conductivity to the enclosure.
Motor Cable • The cable between the drive and motor must be a 4-wire shielded cable (three phases and ground). • Do not exceed the maximum motor cable length for the specific line filter module used. • Inside the shielded enclosure, shielded motor cable must be used as close to the drive’s output terminals as possible. The shield must be solidly connected to the PE terminal of the drive. • Where the shielded motor cable exits the enclosure, an EMC-tested cable clamp, or metal conduit must be used to solidly connect the cable shield to the enclosure. • The shield on the motor side must be solidly connected to the motor housing with an EMC-tested cable clamp, or conduit, providing good conductivity from the cable shield to the motor housing. Motor Connections
Figure C.2
R/L1 S/L2 T/L3 BR– BR+
FAULT READY
1 2 3 4 5 6 7 8 9 10 11
Ground Terminal – PE
4 Wire Shielded Motor Cable
U/T1 V/T2 W/T3 DC– DC+
Motor Wiring TB2 W/T3 V/T2 U/T1 Shielded Enclosure
= EMC Tested Shielded Cable Clamp (or Metal Conduit)
Ground to Motor Housing
Page 80
C-4
CE Conformity
Control Cable • Control wiring must use shielded cable, or grounded metal conduit. Shielded Motor and Control Cable Example
Figure C.3
Stranded Copper Wire Plastic Insulation Inner Plastic Sheath Compact Screen of Galvanized (Tinned) Copper or Steel Outer Plastic Jacket
• The shield must be connected to signal common at both ends of the cable. • The Common terminals (TB3-3 & 7) must be solidly connected (and as short as possible) to the PE terminal of the drive. Control Connections
Ground Terminal – PE
Figure C.4
R/L1 S/L2 T/L3 BR– BR+
FAULT READY
1 2 3 4 5 6 7 8 9 10 11
Ground Terminal – PE
Control Wiring TB3
Control Cabinet ➊ to TB3
Signal Common
U/T1 V/T2 W/T3 DC– DC+
Shielded Control Cable Shielded Enclosure
= EMC Tested Shielded Cable Clamp (or Metal Conduit) ➊ When the control circuitry is located outside of the 160 enclosure.
Page 81
CE Conformity
C-5
Low Voltage Directive 73/23/EEC Compliance This product complies with Low Voltage Directive 72/23/EEC when conforming with the following installation requirements: • Review Chapter 1, Important Precautions and other ATTENTION statements throughout this manual prior to installation of the drive. • The drive is intended to be installed with a fixed connection to the earth. The use of residual-current-operated protective devices (RCDs) or ground fault indicators is not recommended. If unavoidable, the Bulletin 160 is compatible with type B RCDs only. • The drive should be installed in an appropriate or suitable enclosure. Important:
The conformity of this drive and filter to any standard does not guarantee that the entire installation will conform. Many factors can influence the total installation and only direct measurements can verify total conformity.
Page 82
C-6
CE Conformity
End of Chapter