Page 13

Chapter

1

Overview

This chapter describes how analog is used and provides two application examples of analog. The types of available analog modules and their related specifications are also described.

How to Use Analog

Analog refers to the representation of numerical quantities by the measurement of continuous physical variables. Analog applications are present in many forms. The following application shows a typical use of analog. In this application the processor controls the amount of fluid placed in a holding tank by adjusting the percentage of the valve opening. The valve is initially open 100%. As the fluid level in the tank approaches the preset point, the processor modifies the output to degrade closing the valve 90%, 80%, adjusting the valve to maintain a set point.

Analog Output

Valve

CPU

Level Sensor

Analog I/O Module

Analog Input

Types of Analog Modules

1

The following sections provide an overview of the various analog modules.

Publication 1746-UM005B-EN-P - June 2004

Page 14

1-2

Overview

1746-NI4 Analog Input Module The 1746-NI4 Analog Input module contains 4 analog input channels that are user selectable per channel for voltage or current to support a variety of monitoring and controlling applications

1746-NIO4I and NIO4V Analog Combination Modules The NIO4I and NIO4V Analog Combination I/O modules provide two input and two output channels in a single slot module. The 1746-NIO4I module contains two current or voltage inputs (user selectable per channel), and two current outputs. The 176-NIO4V module contains two current or voltage inputs (user selectable per channel) and two voltage outputs.

1746-NO4I and NO4V Analog Output Modules The NO4I and NO4V Analog Output Modules provide 4 analog output channels. The NO4I module contains four current outputs. The NO4V module contains four voltage outputs. Both of these modules support a variety of monitoring and controlling applications. Catalog 1746-

Input Channels per Module

Output Channels per Module

Backplane Current Draw

External 24V dc Power Supply Tolerances

5V (max.)

24V (max.)

NI4

4 differential, voltage or current selectable per channel, not individually isolated

NA

35 mA

85 mA

NA

NIO4I

2 differential, voltage or current selectable per channel, not individually isolated

2 current outputs, not individually isolated

55 mA

145 mA

NA

NIO4V

2 differential, voltage or current selectable per channel, not individually isolated

2 voltage outputs, not individually isolated

55 mA

115 mA

NA

NO4I

NA

4 current outputs, not individually isolated

55 mA

195 mA

24 ±10% at 195 mA max. (21.6 to 26.4V dc)(1)

NO4V

NA

4 voltage outputs, not individually isolated

55 mA

145 mA

24 ±10% at 145 mA max. (21.6 to 26.4V dc)(1)

(1) Required for some applications if SLC 24V power is not readily available.

For more specification information, refer to Appendix A.

Publication 1746-UM005B-EN-P - June 2004

Page 15

Chapter

2

Quick Start for Experienced Users

This chapter can help you to get started using analog. The procedures are based on the assumption that you have an understanding of SLC 500 products. You should understand electronic process control and be able to interpret the ladder logic instructions required to generate the electronic signals that control your application. Because it is a start–up guide for experienced users, this chapter does not contain detailed explanations about the procedures listed. It does, however, reference other chapters in this book where you can get more information. If you have any questions or are unfamiliar with the terms used or concepts presented in the procedural steps, always read the referenced chapters and other recommended documentation before trying to apply the information. This chapter: • tells you what tools and equipment you need • lists preliminary considerations • describes when to configure the module • explains how to install and wire the module • discusses system power–up procedures

Required Tools and Equipment

1

Have the following tools and equipment ready: • small blade screwdriver • an adequate length of communication cable (Belden™ 8761) for your specific application. (See chapter 3, Installing and Wiring Your Analog Module for maximum cable distances.) • programming equipment

Publication 1746-UM005B-EN-P - June 2004

Page 16

2-2

Quick Start for Experienced Users

Procedures 1.

Check the contents of shipping box.

Reference

Unpack the shipping box making sure that the contents include: • Analog I/O module (Catalog Number 1746-Series) • installation instructions (publication 1746-IN008) If the contents are incomplete, call your local Allen–Bradley representative for assistance.

2.

Determine your power requirements for the modular controller.

Reference

Review the power requirements of your system to see that your chassis supports placement of the Chapter 3 analog module. (Installing and Wiring Your • For modular style systems, calculate the total load on the system power supply using the Analog Module) procedure described in the SLC 500 Modular Hardware Style User Manual (publication 1747-UM011) or the SLC 500 Family System Overview (publication 1747-SO001). Appendix A (Specifications) • For fixed SLC 500 controllers, refer to the SLC 500 Fixed Hardware Style Installation & Operation Manual (publication 1747-6.21).

Catalog Number

Backplane Current Draw 5V (max.)

24V (max.)

External 24V dc Power Supply Tolerance

1746-NI4

35 mA

85 mA

NA

1746-NIO4I

55 mA

145 mA

NA

1746-NIO4V

55 mA

115 mA

NA

1746-NO4I

55 mA

195 mA

24 ±10% at 195 mA max. (21.6 to 26.4V dc)(1)

1746-NO4V

55 mA

145 mA

24 ±10% at 145 mA max. (21.6 to 26.4V dc)(1)

(1)

Required for some applications if SLC 24V power is not readily available.

Publication 1746-UM005B-EN-P - June 2004

Page 17

Quick Start for Experienced Users

3.

Configure the module using the DIP switches (analog inputs only).

2-3

Reference

Each analog input channel can be configured for either voltage or current. Locate the DIP switches on your module and set them for your application.

Chapter 3 (Installing and Wiring Your Analog Module)

ON _ Configures channel for current input Off _ Configures channel for voltage input

Current

1746-NI4

O N

1 23 4

Switch 1 = Channel 0 Switch 2 = Channel 1 Switch 3 = Channel 2 Switch 4 = Channel 3

Voltage Current

1746-NIO4I, NIO4V

O N

1 2

Switch 1 = Channel 0 Switch 2 = Channel 1

Voltage External

1746-NO4I, NO4V

24V dc Power Selector

Sw 1

Backplane

4.

Install your module.

Reference

When selecting a slot for an analog module, position the module: • in a slot away from ac or high voltage dc modules • in the chassis closest to the bottom of the enclosure where the SLC 500 system is installed

Chapter 3 (Installing and Wiring Your Analog Module)

• away from the chassis power supply if installed in a modular system

ATTENTION

Never install, remove, or wire modules with power applied to the chassis or devices wired to the modules.

Publication 1746-UM005B-EN-P - June 2004

Page 18

2-4

Quick Start for Experienced Users

Make sure system power is off; then insert the analog module into your 1746 chassis. In this example procedure, local slot 1 is selected.

Top and Bottom Module Release(s)

Card Guide

5.

Wire the module. Important:

Follow these guidelines when wiring the module.

• Use shielded communication cable (Belden 8761) and keep length as short as possible. • Connect only one end of the cable shield to earth ground. • Channels are not isolated from each other. All analog commons are connected together internally. • The module does not provide power for analog inputs. • Use a power supply that matches the transmitter (sensor) specifications.

Publication 1746-UM005B-EN-P - June 2004

Reference Chapter 3 (Installing and Wiring Your Analog Module)

Page 19

Quick Start for Experienced Users

NI4

+ analog source _

0 1 2 3 4 5 6 7 8 9 10 11

IN 0 + IN 0 _ ANL COM IN 1 + IN 1 _ ANL COM IN 2 + IN 2 _ ANL COM IN 3 + IN 3 _ ANL COM

0 1 earth 2 ground 3 4 Jumper unused inputs. 5 6 7 8 earth 9 ground Do not jumper 10 unused outputs. 11

IN 0 +_ IN 0 ANL COM IN 1 + IN 1 _ ANL COM not used OUT 0 ANL COM not used OUT 1 ANL COM earth ground

+ analog source

_ earth ground Jumper unused inputs.

NIO4I & NIO4V

+ analog source _

Load

NO4I & NO4V

2-5

24V dc power supply if external power is selected. Cable length from external 24V dc power supply to analog module must be less than 10m.

Ext. pwr. sup.

Load earth ground

Load Analog commons are internally connected in the module. Channels are not isolated from each other.

earth ground

Do not jumper unused outputs.

0 1

+24V dc dc COM

0 1 2 3 4 5 6 7

OUT 0 ANL COM OUT 1 ANL COM OUT 2 ANL COM OUT 3 ANL COM

Publication 1746-UM005B-EN-P - June 2004

Page 20

2-6

Quick Start for Experienced Users

6.

Configure system I/O configuration.

Reference

Configure your system I/O configuration for the particular slot the analog module is in. When assigning an I/O module to a slot location, select the module from the displayed list. If not listed, select OTHER at the bottom of the list and enter the module’s ID code at the prompt.

Catalog No.

7.

Chapter 4 (Module Operation and System Considerations)

Module ID Code

1746-NI4

4401

1746-NIO4I

3201

1746-NIO4V

3202

1746-NO4I

5401

1746-NO4V

5402

Check that the module is operating correctly.

Reference Chapter 5 (Testing Your Module)

ATTENTION

Machine motion during system checkout can be hazardous to personnel. During all checkout procedures, you must disconnect all devices which, when energized, might cause machine motion.

Apply power to the fixed or modular system. The analog module LED (red) should be illuminated, indicating that the module is receiving 24V dc power.

Publication 1746-UM005B-EN-P - June 2004

Page 21

Quick Start for Experienced Users

8.

Understanding analog inputs.

2-7

Reference

Analog inputs convert current and voltage signals into 16–bit (max.) integer values and place them in the input image for the slot that the analog module resides in.

Address

1746-NI4

1746-NI04I, -NI04V

I:e.0

Input Channel 0

Input Channel 0

I:e.1

Input Channel 1

Input Channel 1

I:e.2

Input Channel 2

I:e.3

Input Channel 3

Chapter 4 (Module Operation and System Considerations)

Note: The e is the slot number.

Voltage/Current Range

Integer Representation

-10V dc to +10V dc

-32,768 to +32,767

0 to 10V dc

0 to 32,767±10V dc

0 to 5V dc

0 to 16, 384

1 to 5V dc

3,277 to 16,384

-20 mA to +20 mA

-16,384 to +16,384

0 to 20 mA

0 to 16,384±20 mA

4 to 20 mA

3,277 to 16,384

Publication 1746-UM005B-EN-P - June 2004

Page 22

2-8

Quick Start for Experienced Users

9.

Understanding analog outputs.

Reference

Analog outputs convert 16-bit integer values placed in the output image to voltage or current signals for the slot that the analog card is in.

Address

1746-NO4

O:e.0

Output Channel 0 Output Channel 0

O:e.1

Output Channel 1 Output Channel 1

O:e.2

Output Channel 2

O:e.3

Output Channel 3

1746-NI04I, -NI04V

1746-NO4I, -NIO4I

10.

Chapter 4 (Module Operation and System Considerations)

1746-NO4V, -NIO4V

Current Range

Decimal Representation for Output Word

Voltage Range

Decimal Representation for Output Word

0 to 21 mA

0 to 32,764

-10 to +10V dc

-32,768 to +32,764

0 to 20 mA

0 to 31, 208

0 to 10V dc

0 to 32,764

4 to 20 mA

6,242 to 31,208

0 to 5V dc

0 to 16,384

1 to 5V dc

3,277 to 16,384

Write ladder logic to process the module’s analog data. Several programming examples are provided in chapter 6 that demonstrate how to scale the raw data from the analog card into engineering units such as psi, percent, etc. Study these examples and apply them to your application as appropriate.

Reference Chapter 5 (Testing Your Module) Chapter 6 (Programming Examples)

Publication 1746-UM005B-EN-P - June 2004