The text of a manual · part 5 of 16
SLC 500 4-Channel Analog I/O Modules User Manual: 3 - Installing and Wiring Your Analog Module, pages 23 to 30
Pages 23 to 30 of 113, from SLC 500 4-Channel Analog I/O Modules User Manual
The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1746-NI4
Page 23
Chapter
3
Installing and Wiring Your Analog Module
To obtain the maximum performance from an analog module, proper module installation is imperative. This chapter describes the procedures that you must follow to install the analog module in an SLC 500 system. The following items are described: • European Union Directive Compliance • determining your power requirements • configuring your module • selecting a slot in the chassis • installing your module • wiring considerations – system wiring guidelines – grounding your cable – determining the cable length • wiring the analog module • minimizing electrical noise on the analog module
European Union Directive Compliance
If this product is installed within the European Union or EEA regions and has the CE mark, the following regulations apply.
EMC Directives This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file: • EN 50081–2 EMC - Generic Emission Standard, Part 2 - Industrial Environment • EN 50082–2 EMC - Generic Immunity Standard, Part 2 - Industrial Environment This product is intended for use in an industrial environment.
1
Publication 1746-UM005B-EN-P - June 2004
Page 24
3-2
Installing and Wiring Your Analog Module
Determining Your Power Requirements for a Modular Controller
Analog modules require both 5V dc and 24V dc power from the backplane of the SLC 500 system. However, the NO4I and NO4V analog modules can use an external 24V dc power supply. This eliminates the 24V dc backplane power requirement, providing configuration flexibility if SLC power supply loading is critical. These two modules provide user-supplied external 24V dc power supply connections. The 24V dc user power connection on a fixed SLC 500 can power an NO4I or NO4V analog module. However, the regulation of the 24V dc user connection on a modular SLC 500 power supply, Catalog Number 1746-P1, -P2, -P4 is outside of the requirements of the NO4I and NO4V analog modules and cannot be used. The following table shows the power requirements for each analog module using backplane power. Use this table to calculate the total load on the modular system power supply. For more information refer to the SLC 500 user manual for modular controllers. IMPORTANT
Catalog Number
5 Volt Current
24 Volt Current
1746-NI4
35 mA
85 mA
1746-NIO4I
55 mA
145 mA
1746-NIO4V
55 mA
115 mA
1746-NO4I
55 mA
195 mA(1)
1746-NO4V
55 mA
145 mA(1)
(1)
Determining Your Power Requirements for a Fixed Controller
The analog modules do not supply loop power for the input device. You must supply the appropriate loop power for loop-powered input devices.
Omit these values from your SLC power supply loading calculations if you decide to use an external power supply.
The chart starting on the next page provides available analog module combinations in the expansion chassis of a fixed controller. • valid combination invalid combination
∇ valid combination when used with external power supply
BASIC net = Basic Module is supplying power to an AIC. No other device requiring power is connected to the AIC.
Publication 1746-UM005B-EN-P - June 2004
Page 25
Installing and Wiring Your Analog Module
NI4
NIO4I
NIO4V
NO4I
NO4V
•
•
•
_
•
IA4
•
•
•
∇
•
IA8
•
•
•
∇
•
IA16
•
•
•
∇
•
IM4
•
•
•
∇
•
IM8
•
•
•
∇
•
IM16
•
•
•
∇
•
OA8
∇
∇
OA16
∇
∇
OAP12
•
•
•
∇
•
IB8
•
•
•
∇
•
IB16
•
•
•
∇
•
IV8
•
•
•
∇
•
IV16
•
•
•
∇
•
IG16
•
•
•
∇
•
OV8
•
∇
∇
OV16
• •
•
•
∇
•
OB8
•
•
•
∇
•
OG16
•
∇
∇
OW4
∇
∇
OW8
∇
∇
OW16
•
∇
•
IO4
•
∇
∇
IO8
•
∇
∇
IO12
•
∇
∇
NI4
∇
∇
NIO4I
∇
∇
NIO4V
∇
∇
DCM
•
∇
∇
HS
•
∇
∇
OB16
∇
•
IN16
∇
∇
BASIC net
∇
∇
BASIC
• •
•
•
•
•
•
•
•
•
3-3
OB32 OV32
Publication 1746-UM005B-EN-P - June 2004
Page 26
3-4
Installing and Wiring Your Analog Module
NI4
NIO4I
NIO4V
NO4I
NO4V
•
•
•
∇
•
IV32
•
•
•
∇
•
IB32
∇
∇
OX8
•
∇
∇
∇
∇
∇
NO4I
∇
∇
∇
∇
∇
NO4V
•
•
•
∇
•
ITB16
•
•
•
∇
•
ITV16
•
•
•
∇
•
IC16
•
•
∇
∇
OBP16
•
•
∇
∇
OVP16
•
•
•
∇
•
NT4
•
•
•
∇
•
NR4
IMPORTANT
The NO4I and NO4V modules provide user supplied external 24V dc power supply connections. When the NO4I module is used in a fixed controller, you must provide an external power supply.
When the NO4I or NO4V is used with an external 24V dc power supply and is placed in a fixed controller expansion chassis, it is compatible with those modules noted in the compatibility chart starting on the previous page. When set for external power, the module will only draw the 5V current off the backplane. Refer to the next section for details on how to configure your module for external power. The 24V dc user power connection on a fixed SLC 500 can power an NO4I or NO4V analog module. However, the regulation of the 24V dc user connection on a modular SLC 500 power supply, Catalog Number 1746-P1, -P2, and -P4 is outside of the requirements of the NO4I and NO4V analog modules and cannot be used.
Publication 1746-UM005B-EN-P - June 2004
Page 27
Installing and Wiring Your Analog Module
Configuring Your Module
3-5
The NI4, NIO4I and NIO4V analog modules have user selectable DIP switch settings which allow you to configure the input channels as either current or voltage inputs. The switches are located on the analog module board. The following illustration shows the ON and OFF switch settings. Switch orientation is also provided on the nameplate of the module. ON – Configures channel for current input OFF – Configures channel for voltage input
ATTENTION
Care should be taken to avoid connecting a voltage source to a channel configured for current input. Improper module operation or damage to the module can occur.
Switch Settings for the 1746–NI4 The NI4 has 4 individual DIP switches that control the input mode of input channels 0 through 3. A switch in the ON position configures the channel for current input. A switch in the OFF position configures the channel for voltage input. Current O N
1 2 3 4
Switch 1 = Channel 0 Switch 2 = Channel 1 Switch 3 = Channel 2 Switch 4 = Channel 3
Voltage
Switch Settings for the 1746-NIO4I and -NIO4V The NIO4I and NIO4V have 2 individual switches labeled 1 and 2. These switches control the input mode of input channel 0 and 1. A switch in the ON position configures the channel for current input. A switch in the OFF position configures the channel for voltage input. Current O N
12
Switch 1 = Channel 0 Switch 2 = Channel 1
Voltage
Publication 1746-UM005B-EN-P - June 2004
Page 28
3-6
Installing and Wiring Your Analog Module
External Power Switch for the 1746-NO4I and -NO4V The NO4I and NO4V analog output modules have an external 24V dc power switch, SW1, which gives you the option of using an external power supply. In the UP position, power is drawn from an external power source. In the DOWN position, power is drawn from the backplane of the module. The switch is located on the analog module board. Switch orientation is also provided on the nameplate of the module. The 24V dc user power connection on a fixed SLC 500 can power an NO4I or NO4V analog module. However, the regulation of the 24V dc user connection on a modular SLC 500 power supply, Catalog Number 1746-P1, -P2, is outside of the requirements of the NO4I and NO4V analog modules and cannot be used.
External 24V dc Power Selector
Sw 1
Backplane
Choosing a Slot in the Chassis
Two factors determine where the analog module should be located in the chassis: ambient temperature and electrical noise. Consider the following conditions when selecting a slot for an analog module. Position the module: • in a slot away from ac or high voltage dc module • in the chassis closest to the bottom of the enclosure where the SLC 500 system is installed • away from the chassis power supply if installed in a modular system
Installing Your Module
All modules are mounted in a single slot. Remember that in a modular system the processor always occupies the first slot of the first chassis. When installing the analog module in a chassis, it is not necessary to remove the terminal block from the module. However, if the terminal block is removed, use the write-on label located on the side of the terminal block to identify the module location and type.
Publication 1746-UM005B-EN-P - June 2004
Page 29
Installing and Wiring Your Analog Module
ATTENTION
3-7
Never install, remove, or wire modules with power applied to the chassis. Also, do not expose analog modules to surfaces or other areas that may typically hold an electrostatic charge. Electrostatic charges can destroy the analog circuitry.
SLOT ____ RACK ____ MODULE _____
Removing the Analog Module Terminal Block To remove the terminal block, grasp it on the top and bottom and pull outward and down. IMPORTANT
The potentiometer sets the voltage during factory calibration to 2.5 volts. It is set and sealed at the factory and does not require any adjustments.
1. Verify that all switches are set correctly for the application.
ATTENTION
Care should be taken to avoid connecting a voltage source to a channel configured for a current input.
Publication 1746-UM005B-EN-P - June 2004
Page 30
3-8
Installing and Wiring Your Analog Module
2. Align the circuit board of the analog module with the card guide of the chassis. 3. Slide the module in until both top and bottom retaining clips are secured.
Top and Bottom Module Release(s)
Card Guide
4. To remove the module, depress the retaining clips at the top and bottom of the module and slide the module out.
Wiring Considerations
The following section provides system wiring guidelines, how to ground your Belden cable, and how to determine the cable length.
ATTENTION
Publication 1746-UM005B-EN-P - June 2004
Before wiring any analog module, disconnect power from the SLC 500 system and from any other source to the analog module.