Installing and Wiring Your Analog Module
3-9
System Wiring Guidelines Use the following guidelines in planning the system wiring for the analog modules: • all analog common terminals (ANL COM) are electrically connected inside the module. ANL COM is not connected to earth ground inside the module. • voltages on IN+ and IN- terminals must remain within ± 20 Volts with respect to ANL COM to ensure proper input channel operation. This is true for current and voltage input channel operation. • voltage outputs (OUT 0 and OUT 1) of the NIO4V and NO4V are referenced to ANL COM. Load resistance (R1) for a voltage output channel must be equal to or greater than 1K ohms. • current output channels (OUT 0 and OUT 1) of the NIO4I and NO4I source current that returns to ANL COM. Load resistance (R1) for a current output channel must remain between 0 and 500 ohms.
Grounding Your Cable Belden cable #8761 has two signal wires (black and clear), one drain wire and a foil shield. Refer to the illustration on p. 3-10. The drain wire and foil shield must be grounded at one end of the cable. Do not earth ground the drain wire and foil shield at both ends of the cable. Input Channel - Use a chassis mounting tab as a ground for the drain wire and foil shield. Output Channel - Ground the drain wire and foil shield at the analog load. IMPORTANT
If you cannot ground the output channel at the load, ground the drain wire and foil shield at the chassis mounting tab. Do not connect the foil shield or drain wire to the analog terminal block. They must be connected to an earth ground, which is not provided at the analog module.
Publication 1746-UM005B-EN-P - June 2004
Page 32
3-10
Installing and Wiring Your Analog Module
F oil Shield Insulation
Black Wire
Clear Wire
Drain Wire
Determining the Cable Length Determine the length of cable you will need to connect a channel to its input or output device. Remember to leave additional length to route the drain wire and foil shield for earth grounding.
Wiring the Analog Module
After the analog module is properly installed in the chassis, use the following wiring procedure. Belden cable #8761 is recommended when wiring analog modules. This section assumes that you have properly installed the analog module.
ATTENTION
Before wiring any analog module, disconnect power from the SLC 500 system and from any other source to the analog module.
To wire your analog module follow these steps and refer to the illustrations on the next page. 1. Designate the end of the cable where the drain wire and foil shield is earth grounded as END 1. Designate the other end as END 2. 2. At each end of the cable strip some casing to expose the individual wires. 3. Trim the signal wires to 2 inch lengths. Strip about 3/16 inch (4.76mm) of insulation away to expose the end of the wire. 4. At End 1, twist the drain wire and foil shield together, bend them away from the cable, and apply shrink wrap.
Publication 1746-UM005B-EN-P - June 2004
Page 33
Installing and Wiring Your Analog Module
3-11
5. At End 2, cut the drain wire and foil shield back to the cable and apply shrink wrap. 6. Connect the signal wires (black and clear) to the terminal block and the input and output devices. The recommended maximum torque is 5 lb.-in (0.565 NM) for all terminals. • If the foil shield and drain wire of the channel are grounded at the sourcing device, make sure End 2 of the cable is connected to the terminal block. • If the foil shield and drain wire are grounded at the chassis mounting tab, make sure End 1 is connected to the terminal block. 7. Repeat steps 1 through 6 for each channel on the analog module. Jumper the unused plus (+), minus (-) and common terminals of each input channel individually. Unused output and common terminals should be left unconnected. The following illustrations depict the proper cable preparation for END 1 and END 2. Shrink wrap is applied to each cable end. Make sure the foil shield and drain wires on END 1 are long enough to reach their designated earth ground points.
F oil Shield and Drain Wire Insulation
Black Wire
Clear Wire
Insulation
Black Wire
Clear Wire
Publication 1746-UM005B-EN-P - June 2004
Page 34
3-12
Installing and Wiring Your Analog Module
Labeling and Installing the Terminal Block
The terminal block has a write-on label. Labeling the terminal block will help ensure that it is installed on the correct module.
SLOT ____ RACK ____ MODULE _____
Note: The black dot on the terminal block label indicates the position of terminal 0. Once you have wired your analog module and properly labeled the terminal block, install the terminal block on the analog module. To install the terminal block: 1. Align the terminal block with the receptacle. 2. Insert the terminal block and press firmly at the top and bottom until it is properly secured.
Grounding the Foil Shields and Drain Wires
Publication 1746-UM005B-EN-P - June 2004
You are now ready to earth ground your foil shield and drain wire from each cable. Do not connect the foil shield or drain wire to the analog module terminal block. The foil shield and drain wire must be connected to earth ground, which is not available on the terminal block. Refer to the illustration on the next page for wiring diagrams of the analog modules.
Page 35
Installing and Wiring Your Analog Module
NI4
+ analog source
– +
0 1 2 3 4 5
IN 0 + IN 0 – ANL COM
6 7 8 9 10 11
IN 2 + IN 2 – ANL COM IN 3 + IN 3 – ANL COM
0 1 2 3 4 5
IN 0 + IN 0 – ANL COM
6 7 8 9 Do not jumper 10 unused outputs. 11 not used OUT 0 ANL COM earth ground analog source
– earth ground Jumper unused inputs.
NIO4I & NIO4V
IN 1 + IN 1 – ANL COM
+ analog source
– earth ground Jumper unused inputs.
Load earth ground
NO4I & NO4V
3-13
24V dc power supply if external power is selected. Cable length from external 24V dc power supply to analog module must be less than 10m.
Ext. pwr. sup.
Load earth ground
Load earth ground
Do not jumper unused outputs.
IN 1 + IN 1 – ANL COM not used OUT 1 ANL COM
0 1
+24V dc dc COM
0 1
OUT 0 ANL COM
2 3
OUT 1 ANL COM
4 5
OUT 2 ANL COM
6 7
OUT 3 ANL COM
Analog commons are internally connected in the module. Channels are not isolated from each other.
Publication 1746-UM005B-EN-P - June 2004
Page 36
3-14
Installing and Wiring Your Analog Module
Wiring Schematics for 2, 3, and 4-Wire Analog Input Devices
Important: The module does not provide loop power for analog inputs. Use a power supply that matches the transmitter specifications. 2-Wire Transmitter Transmitter Power + Supply –
3-Wire Transmitter
+
–
Transmitter Supply Signal GND
Power + Supply –
Module IN + IN – ANL COM
Module IN + IN – ANL COM
4-Wire Transmitter Transmitter Supply Signal Power + Supply
–
Publication 1746-UM005B-EN-P - June 2004
+ –
+ –
Module IN + IN – ANL COM
Page 37
Installing and Wiring Your Analog Module
3-15
Wiring Schematic for Single-ended Analog Input Connections
When wiring single-ended analog input devices to the analog input card, the number of total wires necessary can be limited by using the ANALOG COMMON terminal. Note that dif ferential inputs are more immune to noise than single-ended inputs.
Power + Supply –
Transmitter
+
Signal
NI4 IN 0 + IN 0 –
Transmitter
+
Signal
ANL COM IN 1 + IN 1 –
Transmitter
+
Signal
ANL COM IN 2 + IN 2 –
Transmitter Supply Signal Ground +
ANL COM IN 3 + IN 3 – ANL COM
Minimizing Electrical Noise on Analog Modules
Inputs on analog modules employ digital high frequency filters that significantly reduce the effects of electrical noise on input signals. However, because of the variety of applications and environments where analog modules are installed and operating, it is impossible to ensure that all environmental noise will be removed by the input filters. Although it is not the purpose of this manual to address SLC 500 system procedures, several specific steps can be taken to help reduce the effects of environmental noise on analog signals: • install the SLC 500 system in a properly rated (i.e., NEMA) enclosure. Make sure that the SLC 500 system is properly grounded. • use Belden cable #8761 for wiring the analog modules making sure that the drain wire and foil shield are properly earth grounded. • route the Belden cable separate from any other wiring. Additional noise immunity can be obtained by routing the cables in grounded conduit. Publication 1746-UM005B-EN-P - June 2004
Page 38
3-16
Installing and Wiring Your Analog Module
• group analog and low voltage dc modules away from ac I/O or high voltage dc modules. A system may malfunction due to a change in the operating environment after a period of time. We recommend periodically checking system operation, particularly when new machinery or other noise sources are installed near the SLC 500 system. For further details on system installation and startup refer to: • SLC 500 Modular Hardware Style User Manual (publication 1747-UM011) • SLC 500 Fixed Hardware Style Installation & Operation Manual (publication 1747-6.21) • Safety Guidelines for the Application, Installation Maintenance of Solid State Control (A–B Publication SGI–1.1).