Page 39

Chapter

4

Module Operation and System Considerations

This chapter describes: • Interface between the Module and Processor • System Considerations

Interface between the Module and the Processor

This section describes how to set up an analog module in a SLC 500 system.

Entering Module ID Codes When configuring an analog module for an SLC 500 system using your programming software, a list of the different I/O modules, including the analog modules, is most likely provided for you. If a list is not provided, you need to enter the module identification code when configuring the slot. Refer to the table below for the appropriate analog module ID code. Using the Hand-Held Terminal (HHT) firmware v1.1, enter the proper MODULE ID CODE under the “other” selection. Version 2.0 or later of the HHT firmware provides a list of I/O modules. Refer to the following publications for complete information: • your programming software’s user manual • the Hand-Held Terminal User Manual

1

Catalog No.

Module ID Code

1746-NI4

4401

1746-NIO4I

3201

1746-NIO4V

3202

1746-NO4I

5401

1746-NO4V

5402

Publication 1746-UM005B-EN-P - June 2004

Page 40

4-2

Module Operation and System Considerations

Addressing Analog Modules NI4 - Each input channel of the NI4 is addressed as a single word in the input image table. The NI4 uses a total of 4 words in the input image table. The converted values from channels 0 through 3 are addressed as input words 0 through 3 respectively for the slot where the module resides. EXAMPLE

If you want to address input channel 2 of the NI4 in slot 4, you would address it as input word 2 in slot 4 (I:4.2).

NIO4I and NIO4V - Each input channel of the NIO4I and NIO4V is addressed as a single word in the input image table and each output channel of the module is addressed as a single word in the output image table. Both the NIO4I and NIO4V use a total of 2 input words and 2 output words. The converted input values from input channels 0 and 1 are addressed as words 0 and 1 of the slot where the module resides. The output values for the output channels 0 and 1 are addressed as output words 0 and 1 of the slot where the module resides. EXAMPLE

If you want to address output channel 0 of the NIO4I in slot 3, you would address it as output word 0 in slot 3 (O:3.0).

NO4I and NO4V - Each output channel of the NO4I and NO4V is addressed as a single word in the output image table. Both modules use a total of 4 output words. The converted output values from output channels 0 through 3 are addressed as words 0 through 3 respectively for the slot where the module resides. EXAMPLE

Publication 1746-UM005B-EN-P - June 2004

If you want to address output channel 3 of the NO4I in slot 3, you would address it as output word 3 in slot 3 (O:3.3).

Page 41

Module Operation and System Considerations

4-3

The following illustration shows I/O addressing for the analog modules.

SLC 500 SLC 5/01 or 5/02 Data Files Output Image Input Image Slot e

Address

1746-NI4 Analog Input Module Input Scan

Input Image 4 words

Input Channel 0

Word 0

I:e.0

Input Channel 1

Word 1

I:e.1

Input Channel 2

Word 2

I:e.2

Input Channel 3

Word 3

I:e.3

Bit 15

1746-NIO4I & NIO4V Analog Combination Modules

SLC 500 SLC 5/01 or 5/02 Data Files Slot e

Address Output Scan

Output Image 2 words

Output Image Slot e

Output Channel 0

Word 0

O:e.0

Output Channel 1

Word 1

O:e.1

Input Channel 0

Word 0

I:e.0

Input Channel 1

Word 1

I:e.1

Bit 15 Input Scan

Input Image

Input Image 2 words

Bit 15

Output Image Input Image

Bit 0

Bit 0

1746-NO4I & NO4V Analog Output Modules

SLC 500 SLC 5/01 or 5/02 Data Files Slot e

Bit 0

Output Scan

Output Image 4 words

Address Output Channel 0

Word 0

O:e.0

Output Channel 1

Word 1

O:e.1

Output Channel 2

Word 2

O:e.2

Output Channel 3

Word 3

O:e.3

Bit 15

Bit 0 e = slot # of module

Publication 1746-UM005B-EN-P - June 2004

Page 42

4-4

Module Operation and System Considerations

Bit Level Addressing The following bit maps show bit level addressing for the analog inputs and outputs. The input channel converter resolution is 16 bits, or 1 word. The output channel converter resolution is 14 bits and is loaded from the most significant 14 bits of the associated output word. The two least significant bits (O:e.0/0 and O:e.0/1) of the output word have no effect on the actual output value.

1746-NI4 msb lsb

15

14

13

12

11

10

9

CH 0 INPUT 8 7

15

14

13

12

11

10

9

CH 1 INPUT 8 7

I:e.0 I:e.1

6

5

4

3

6

5

4

3

7

6

5

4

CH 3 INPUT 8 7

6

5

4

2

1

0

2

1

0

3

2

1

0

3

2

1

0

CH 2 INPUT

I:e.2 15

14

13

12

11

10

9

I:e.3 15

14

13

12

11

10

9

8

1746-NIO4I & NIO4V msb lsb

O:e.0 15

14

13

12

11

10

9

CH 0 OUTPUT 8 7

XX 6

5

4

3

2

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1 msb

14

13

12

11

10

9

CH 0 INPUT 8 7

6

5

4

3

2

1

0

6

5

4

3

2

1

0

CH 1 INPUT

I:e.1 15 1746-NO4I & NO4V

0 lsb

I:e.0 15

0

XX

CH 1 OUTPUT

O:e.1

1

14

13

12

11

10

9

8

7 msb lsb

15

14

13

12

11

10

9

6

5

4

3

6

5

4

3

15

14

13

12

11

10

9

CH 1 OUTPUT 8 7

15

14

13

12

11

10

9

CH 2 OUTPUT 8 7

O:e.1 O:e.2 O:e.3 15

14

13

12

11

10

9

CH 3 OUTPUT 8 7 e = slot # of module x = bit not used

Publication 1746-UM005B-EN-P - June 2004

XX

CH 0 OUTPUT 8 7

O:e.0

6

5

4

3

2

1

0

X

X

2

1

0

2

1

0

X

X

1

0

XX

6

5

4

3

2

Page 43

Module Operation and System Considerations

4-5

Processor Update of Analog Data The analog input and output data is updated by the processor once during each scan of the user program. The table below shows typical analog update scan times and the number of input and output bits for the specified modules. If an application requires processor updates of the analog data more frequently than once per scan, use an Immediate Input or an Immediate Output instruction. An Immediate Input or Output instruction typically updates 16 bits (or 1 analog channel) in 1 millisecond. Refer to your programming software’s user manual for more information.

Typical Time for Analog Data Updates to the Processor’s Input and Output Image Once per processor scan (Automatic)

10 milliseconds for typical 1K program

Using immediate Input or Output Instruction

1 millisecond per analog channel

Number of Input and Output Bits Representing Analog Data Description

Input Bits

Output Bits

NI4

64

-

NI4OI and NIO4V (2 input and 2 Output channels)

32

32

NO4I and NO4V

-

64

Monitoring the Input and Output Data The analog input and output data can be monitored in several different radices using your programming software. Viewing the radix as decimal allows the analog input and output data to be viewed as decimal representations of integer words. When monitoring in binary radix, data is viewed in two’s complement representation for negative values. A description of two’s complement data is available in Appendix B.

Publication 1746-UM005B-EN-P - June 2004

Page 44

4-6

Module Operation and System Considerations

If you are using the Hand-Held Terminal (HHT) or the Data Table Access Module™ (DTAM) to monitor input and output data, the binary radix is the only available option. To view the analog input and output data in decimal radix, the data must be moved to an integer data file.

Converting Analog Input Data Analog inputs convert current and voltage signals into 16 bit two’s complement binary values. The table below identifies the current and voltage input ranges for the input channels, the number of significant bits for the applications using input ranges less than full scale, and their resolution

Voltage/Current Range

Decimal Representation

Number of Significant Bits

Resolution per LSB

-10V dc to +10V dc - 1LSB

-32,768 to +32,767

16 bits

305.176 µV

0 to 10V dc - 1LSB

0 to 32,767

15 bits

0 to 5V dc

0 to 16,384

14 bits

1 to 5V dc

3,277 to 16,384

13.67 bits

-20 mA to +20 mA

-16,384 to +16,384

15 bits

0 to +20 mA

0 to 16,384

14 bits

4 to +20 mA

3,277 to 16,384

13.67 bits

1.22070 µA

To determine an approximate voltage that an input value represents, use one of the following equations:

10V 32,768

× input value = input voltage(V)

The Input Value is the decimal value of the word in the input image for the corresponding analog input. For example, if an input value of ±16,021 is in the input image, the calculated input voltage is: 10V × ±16,201 = ±4.889221(V) 32,768 It should be noted that this is the calculated value. The actual value may vary within the accuracy limitations of the module.

Publication 1746-UM005B-EN-P - June 2004

Page 45

Module Operation and System Considerations

4-7

To determine an approximate current that an input value represents, you can use the following equation:

20 mA 16,384

× input value = input current (mA)

The Input Value is the decimal value of the word in the input image for the corresponding analog input. For example, if an input value of 4096 is in the input image, the calculated input current is: 20 mA × 4096 = 5(mA) 16,384 It should be noted that this is the calculated value. The actual value may vary within the accuracy limitations of the module.

Converting Analog Output Data Analog outputs convert a 16-bit two’s complement binary value into an analog output signal. Because the analog output channels have a 14-bit converter, the 14 most significant bits of this 16-bit number are the bits that the output channel converts. The NIO4I and NO4I support two and four current outputs respectively, ranging from 0 mA to a maximum of 21 mA. The NIO4V and NO4V support two and four voltage outputs respectively, ranging from -10 to +10 Volts dc. The following tables identify the current and voltage output ranges for the output channels, the number of significant bits for the applications using output ranges less than full scale, and their resolution.

Current Range

Decimal Representation for Output Word

Number of Significant Bits

Resolution per LSB

0 to 21 mA - 1LSB

0 to +32,764

13 bits

2.56348 µA

0 to +20 mA

0 to +31,208

12.92 bits

4 to +20 mA

6,242 to +31,208

12.6 bits

Publication 1746-UM005B-EN-P - June 2004

Page 46

4-8

Module Operation and System Considerations

Voltage Range

Decimal Representation for Output Word

Number of Significant Bits

-10 to +10V dc - 1LSB

-32,768 to +32,764

14 bits

0 to +10V dc - 1LSB

0 to +32,764

13 bits

0 to 5V dc

0 to +16,384

12 bits

1 to 5V dc

+3,277 to +16,384

11.67 bits

Resolution per LSB

1.22070 mV

Use the following equation to determine the decimal value for the current output:

32,768 21 mA

× Desired Current Output (mA) = Output Decimal V alue

For example, if an output value of 4 mA is desired, the value to be put in the corresponding word in the output image can be calculated as follows: 32,768 21 mA

× 4 mA = 6242

Note: The actual resolution for analog current outputs is 2.56348 µA per LSB, where the LSB position in the output word is indicated as:

LSB 15

14

13

12

11

10

9

8

7

6

5

4

3

2

X

X

1

0

X = Bit Not Used

Use the following equation to determine the decimal value for the voltage output:

32,768 10V dc

× Desired Voltage Output (V dc) = Output Decimal V alue

For example, if an output value of 1V dc is desired, the value to be put in the corresponding word in the output image can be calculated as follows: 32,768 10V dc

× 1V dc = 3277

Note: The actual resolution for analog voltage outputs is 1.22070 mV per LSB, where the LSB position in the output word is indicated as:

LSB 15

14

13

12

11

X = Bit Not Used

Publication 1746-UM005B-EN-P - June 2004

10

9

8

7

6

5

4

3

2

X

X

1

0