Application Examples
IMPORTANT
8-21
Before continuing, the PC modem must be connected to a working outside phone line and the network modem must be connected to the incoming phone line specified in the phone book. Also, the network modem must be connected to a working Allen-Bradley network.
Once the proper connections are verified, the AB_DF1-1 driver can be tested.
Publication 1747-UM005B-EN-P - March 2006
Page 110
8-22
Application Examples
10. To complete the driver configuration and attempt a connection, click OK. The Dialer window appears and relays the information about the attempted connection. The dialer will repeatedly attempt to establish a connection until the time duration expires or retries as shown in the Dialer dialog.
When the connection is properly established, the status will be connected to the 1747-KE module. 11. Click OK to exit the dialer and maintain a connection to the network device. 12. If the connection was successful, click OK at the Modem Initialization dialog which will return you to the Configure Drivers dialog.
A successful connection is indicated by the status shown as Running in the AB_DF1 driver. You are now ready to view the network connection.
Publication 1747-UM005B-EN-P - March 2006
Page 111
Application Examples
8-23
13. Click Close to exit the Configure Drivers dialog. 14. Click on Communications>RSWho
If everything was completed properly, you should be remotely monitoring the DH-485 network and all existing devices on the network.
Publication 1747-UM005B-EN-P - March 2006
Page 112
8-24
Application Examples
The following is an example network configuration.
Publication 1747-UM005B-EN-P - March 2006
Page 113
Application Examples
8-25
Go Online using RSLogix 500 Software and RSLinx Version 2.x and Later The DF1 driver makes the communication connection between the PC (sending modem) and the 1747-KE module (receiving modem). Once configured, this driver can be called by the programming software used to program the SLC processor. The steps below describe how to go online using RSLogix500 software and RSLinx version 2.x. To begin: 1. Start RSLogix500 software. If the RSLogix500 software is properly installed, the main dialog appears.
2. Select Comms>System Comms from the main menu.
The System Communication dialog appears.
Publication 1747-UM005B-EN-P - March 2006
Page 114
8-26
Application Examples
3. Select the driver of the PLC controller. Make sure the driver currently selected is AB_DF1-1. If another driver is in the driver window, click on the combo box down arrow and select the AB_DF1-1 driver. 4. Select the node address of the PLC controller. If the node address is known then enter the value directly into the Processor Node dialog. If the processor node is unknown, the value can be selected from RSLinx software’s NetworkWho.
5. To obtain the current processor node, double-click on the highlighted node.
Publication 1747-UM005B-EN-P - March 2006
Page 115
Application Examples
8-27
The program returns to the System Options dialog and the Processor Node dialog is populated with the node address selected in the NetworkWho.
6. Click the Online button. If everything occurred correctly, you will have a remote connection with the processor. This is indicated by the Remote Run or Program indicator.
Publication 1747-UM005B-EN-P - March 2006
Page 116
8-28
Application Examples