Page 117
Appendix
A
Specifications
This appendix contains information regarding hardware specifications for the DH-485/RS-232C Interface Module.
Hardware Specifications
The module hardware specifications are listed in the following tables. Hardware Specifications Attribute
Value
Power Supply Loading at 5V dc
0.150 A (module only)
Power Supply Loading at 24V dc
0.070 A (module only)(2)(3)
Noise Immunity
NEMA Standard ICS 2-230
Vibration
Displacement: 0.015 in., peak-to-peak at 5...57 Hz
0.150 A (module with link coupler)
0.125 A (module with link coupler)
Acceleration: 2.5 g at 57...2000 Hz
1
Shock (operating)
30 g
Port Isolation(1) CONFIG Port DF1 Port CONFIG and DF1 Port
500V ac 500V ac 500V ac
Ambient Temperature Rating
Operating: 0...+60 °C (+32...+140 °F) Storage: -40...+85 °C (-40...+185 °F)
Humidity
5...95% without condensation
Clock/Calendar Accuracy
±1 minute/month at 25 °C (77 °F) +0, -6 minute/month at 60 °C (140 °F)
(1)
Port DH485 is not isolated.
(2)
If a 1747-AIC link coupler is connected to the 1747-KE module with a 1747-C11 cable, the link coupler draws its power (0.085 A @ 24V dc) through the module. Add this to the current listed for the link coupler requirements.
(3)
If a 1747-AIC link coupler is connected to the 1747-KE module with a 1747-C13 cable, then the power for the link coupler comes from either an SLC 500 controller or an external power supply.
Publication 1747-UM005B-EN-P - March 2006
Page 118
A-2
Specifications
IMPORTANT
The 1747-KE module requires both 5V dc and 24V dc power from the SLC backplane. The power consumption of the module must be taken into consideration when planning your SLC 500 system. Refer to the documentation supplied with your SLC 500 fixed or modular controller for additional information on power supplies and current requirements.
Certification Product Certifications Certification Certification
Value c-UL-us listed Class 1, Groups A, B, C, or D, Division 2 CE compliant for all applicable directives C-Tick marked for all applicable acts
Port Isolation
Publication 1747-UM005B-EN-P - March 2006
Port Isolation Port
Isolation
Isolation Voltage
CONFIG
Backplane to Port
500V dc
DF1
Backplane to Port
500V dc
CONFIG and DF1
CONFIG to DF1
500V dc
IMPORTANT
The DH-485 Port is not isolated.
Page 119
Specifications
A-3
Maximum Communication Distances Maximum Communication Distances Communication Max. Distance Allowed in m (ft) Rate (Kbps)
RS-232
RS-423
RS-422
RS-485
300
15 (50)
1230 (4000)
1230 (4000)
1230 (4000)
600
15 (50)
920 (3000)
1230 (4000)
1230 (4000)
1200
15 (50)
770 (2500)
1230 (4000)
1230 (4000)
2400
15 (50)
502 (1650)
1230 (4000)
1230 (4000)
4800
15 (50)
245 (800)
1230 (4000)
1230 (4000)
9600
15 (50)
120 (400)
1230 (4000)
1230 (4000)
19200
15 (50)
60 (200)
1230 (4000)
1230 (4000)
IMPORTANT
When communicating in RS-232 mode, use the RS-423 jumper settings. When communicating in RS-423 mode, use RS-423 or compatible receivers.
Publication 1747-UM005B-EN-P - March 2006
Page 120
A-4
Specifications
Publication 1747-UM005B-EN-P - March 2006