Page 117

Appendix

A

Specifications

This appendix contains information regarding hardware specifications for the DH-485/RS-232C Interface Module.

Hardware Specifications

The module hardware specifications are listed in the following tables. Hardware Specifications Attribute

Value

Power Supply Loading at 5V dc

0.150 A (module only)

Power Supply Loading at 24V dc

0.070 A (module only)(2)(3)

Noise Immunity

NEMA Standard ICS 2-230

Vibration

Displacement: 0.015 in., peak-to-peak at 5...57 Hz

0.150 A (module with link coupler)

0.125 A (module with link coupler)

Acceleration: 2.5 g at 57...2000 Hz

1

Shock (operating)

30 g

Port Isolation(1) CONFIG Port DF1 Port CONFIG and DF1 Port

500V ac 500V ac 500V ac

Ambient Temperature Rating

Operating: 0...+60 °C (+32...+140 °F) Storage: -40...+85 °C (-40...+185 °F)

Humidity

5...95% without condensation

Clock/Calendar Accuracy

±1 minute/month at 25 °C (77 °F) +0, -6 minute/month at 60 °C (140 °F)

(1)

Port DH485 is not isolated.

(2)

If a 1747-AIC link coupler is connected to the 1747-KE module with a 1747-C11 cable, the link coupler draws its power (0.085 A @ 24V dc) through the module. Add this to the current listed for the link coupler requirements.

(3)

If a 1747-AIC link coupler is connected to the 1747-KE module with a 1747-C13 cable, then the power for the link coupler comes from either an SLC 500 controller or an external power supply.

Publication 1747-UM005B-EN-P - March 2006

Page 118

A-2

Specifications

IMPORTANT

The 1747-KE module requires both 5V dc and 24V dc power from the SLC backplane. The power consumption of the module must be taken into consideration when planning your SLC 500 system. Refer to the documentation supplied with your SLC 500 fixed or modular controller for additional information on power supplies and current requirements.

Certification Product Certifications Certification Certification

Value c-UL-us listed Class 1, Groups A, B, C, or D, Division 2 CE compliant for all applicable directives C-Tick marked for all applicable acts

Port Isolation

Publication 1747-UM005B-EN-P - March 2006

Port Isolation Port

Isolation

Isolation Voltage

CONFIG

Backplane to Port

500V dc

DF1

Backplane to Port

500V dc

CONFIG and DF1

CONFIG to DF1

500V dc

IMPORTANT

The DH-485 Port is not isolated.

Page 119

Specifications

A-3

Maximum Communication Distances Maximum Communication Distances Communication Max. Distance Allowed in m (ft) Rate (Kbps)

RS-232

RS-423

RS-422

RS-485

300

15 (50)

1230 (4000)

1230 (4000)

1230 (4000)

600

15 (50)

920 (3000)

1230 (4000)

1230 (4000)

1200

15 (50)

770 (2500)

1230 (4000)

1230 (4000)

2400

15 (50)

502 (1650)

1230 (4000)

1230 (4000)

4800

15 (50)

245 (800)

1230 (4000)

1230 (4000)

9600

15 (50)

120 (400)

1230 (4000)

1230 (4000)

19200

15 (50)

60 (200)

1230 (4000)

1230 (4000)

IMPORTANT

When communicating in RS-232 mode, use the RS-423 jumper settings. When communicating in RS-423 mode, use RS-423 or compatible receivers.

Publication 1747-UM005B-EN-P - March 2006

Page 120

A-4

Specifications

Publication 1747-UM005B-EN-P - March 2006