Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 19 of 20

DH-485/RS-232C Interface Module, Catalog Number 1747-KE, User Manual: D - Interface Module Configuration Worksheets

Pages 131 to 134 of 139, from DH-485/RS-232C Interface Module, Catalog Number 1747-KE, User Manual

The original document is the PDF (1.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Allen-Bradley 1747-AIC DH-485

Page 131

Appendix

D

Interface Module Configuration Worksheets

This appendix contains worksheets to help you configure the interface module. You will find worksheets on: • DF1 Full-duplex. • DF1 Half-duplex.

1

Publication 1747-UM005B-EN-P - March 2006

Page 132

D-2

Interface Module Configuration Worksheets

DF1 Full-duplex

Name:_______________________________ Date:____________

Parameter

DH485 Port Options

Node Address

0...31 (decimal)

Max. Node Address

1...31 (decimal)

Message Timeout

100...12,750 ms

Pass Through

Disabled, Enabled

Communication Rate

300, 600, 1200, 2400, 4800, 9600, 19200

Parameter

DF1 Port Options

Communication Rate

300, 600, 1200, 2400, 4800, 9600, 19200

Bits Per Character

7, 8

Parity

Even, Odd, None

Stop Bits

1, 2

Parameter

DF1 Full-duplex Options

Duplicate Packet Detection

Enabled, Disabled

Checksum

BCC, CRC16

Constant Carrier Detect Disabled, Enabled Modem Init String Modem Init String Delay 0...25 s Message Timeout

100...12,750 ms

Hardware Handshaking Disabled, Enabled Embedded Response Detect

Embedded Response, Auto Detect Embedded Response

ACK Timeout

(0...65,535) x 5 ms

ENQuiry Retries

0...254

NAK Received Retries

0...254

Publication 1747-UM005B-EN-P - March 2006

Your Configuration

Your Configuration

Your Configuration

Page 133

Interface Module Configuration Worksheets

DF1 Half-duplex

D-3

Name:________________________________ Date:____________

Parameter

DH485 Port Options

Node Address

0...31 (decimal)

Max. Node Address

1...31 (decimal)

Message Timeout

100...5000 ms

Pass Through

Disabled, Enabled

Communication Rate

300, 600, 1200, 2400, 4800, 9600, 19200

Parameter

DF1 Port Options

Communication Rate

300, 600, 1200, 2400, 4800, 9600, 19200

Bits Per Character

7, 8

Parity

Even, Odd, None

Stop Bits

1, 2

Parameter

DF1 Half-duplex Options

Duplicate Packet Detection

Disabled, Enabled

Checksum

BCC, CRC16

Constant Carrier Detect

Disabled, Enabled

Your Configuration

Your Configuration

Your Configuration

Modem Init String Modem Init String Delay

0...25 s

Message Timeout

100...12,750 ms

Hardware Handshaking

Disabled, Enabled

Poll Timeout

(0...65,535) x 5 ms

Message Retries

0...254

RTS On Delay

(0...65,535) x 5 ms

RTS Off Delay

(0...65,499) x 5 ms

Local/Remote Mode

Local, Remote

Slave Address/ Group Number

Slave Address = 0...254 Group Number = 0...7

Master Station Address

0...254 (decimal)

Publication 1747-UM005B-EN-P - March 2006

Page 134

D-4

Interface Module Configuration Worksheets

Publication 1747-UM005B-EN-P - March 2006