Page 39

Chapter

4

Installation and System Configuration

This chapter provides the following installation and system configuration information. • European Union directives compliance • Module functionality • Mode selection • Port configuration verification • Module installation • Cable connection • SLC chassis, DF1 driver, and module configuration

ATTENTION

European Union Directives Compliance

Do not install or remove the 1747-KE module from the SLC chassis until all power dissipates from the SLC 500 power supply (approximately 10 seconds).

If this product has the CE mark, it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.

EMC Directive This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file: • EN 50081-2 EMC - Generic Emission Standard, Part 2 - Industrial Environment • EN 50082-2 EMC - Generic Immunity Standard, Part 2 - Industrial Environment This product is intended for use in an industrial environment.

1

Publication 1747-UM005B-EN-P - March 2006

Page 40

4-2

Installation and System Configuration

Choose the Module’s Functionality

Your series B interface module has the ability to function as a series A interface module. This feature may be important to you if you are replacing a series A module with a series B module. Refer to page 4-2 for more information. The module’s functionality depends on the placement of the JW4 jumper. Horizontal placement of the jumper gives the module functionality equivalent to a series A interface module, while vertical placement of the jumper accesses the added functionality of a series B interface module. Module Functionality Settings Series A Functionality (mod. config. ID=4209)

Horizontal Configuration Mode

Horizontal Run Mode

Series B Functionality (mod. config. ID=3509)

Vertical Configuration Mode

Vertical Run Mode

Add an Interface Module to Your System If you are not replacing a series A module, you will want to access the full functionality of the series B module. Therefore, as you work through the remainder of this manual, follow the instructions for series B functionality (vertical placement of the JW4 jumper). Skip the next section and move on to Set the Module’s Mode.

Replace a Series A Interface Module in Your System IMPORTANT

Choosing series B functionality requires you to change the module configuration ID assigned in your processor.

Series A Functionality If you do not want to alter the existing configuration in your user program in any way, choose the series A functionality for your new module. The horizontal placement of JW4 gives the series B module a

Publication 1747-UM005B-EN-P - March 2006

Page 41

Installation and System Configuration

4-3 module configuration ID equivalent to the module configuration ID of the series A module you are replacing (4209). As you work through the remainder of this manual, follow the instructions for series A functionality (horizontal placement of the JW4 jumper). IMPORTANT

The increased functionality of the series B interface module (for example, the Real Time Clock, backplane configuration, and SLC processor reset of the interface module) is not available with the series A functionality.

Series B Functionality The series B module functions identical to the series A module, but has these additional features. • Real Time Clock (RTC) • Backplane configuration • SLC processor reset of the interface module If you want to use the added features of the series B interface module, follow the directions given for series B functionality (vertical placement of the JW4 jumper) as you work through the remainder of this manual.

IMPORTANT

You will be required to change the module configuration ID assigned in your processor. The vertical placement of the JW4 jumper gives your module a configuration ID that differs from the configuration ID of your series A interface module. The procedure for changing the module configuration ID is explained later in this chapter. See page 4-13 for more information.

Publication 1747-UM005B-EN-P - March 2006

Page 42

4-4

Installation and System Configuration

Set the Module’s Mode

Setting the module’s mode depends on which method you want to use to configure the module. You can configure the module using: • an ASCII terminal. • backplane communications. IMPORTANT

You can only use backplane communications if you selected series B functionality for the module.

Decide which method you want to use and then place the JW4 jumper according to the directions given below.

Configure with an ASCII Terminal Configuration of the interface module with an ASCII terminal is allowed only when the JW4 jumper is in Configuration mode. Place the module in the Configuration mode that corresponds to the functionality you chose for the interface module. JW4 in Configuration Mode Series A Functionality

Series B Functionality

Vertical Configuration Mode

Horizontal Configuration Mode

Configure Through the Backplane Reading and writing configuration data through the backplane is allowed only for series B interface modules, and then only when the JW4 jumper is in the vertical Run mode position. Place the module in vertical Run mode. JW4 in Vertical Run Mode JW4

Vertical Run Mode

Publication 1747-UM005B-EN-P - March 2006

Page 43

Installation and System Configuration

Verify CONFIG Port Configuration

4-5

Jumper JW1, located at the top of the module, selects the following electrical interface for the CONFIG port. • RS-423/232 (default) • RS-422 • RS-485 CONFIG Port Configuration

2 4 6 8 10

RS-423/232

1 3 5 7 9 RS-422 JW1 CONFIG Port RS-485

ATTENTION

All other jumper settings are illegal and may cause damage to the module.

Publication 1747-UM005B-EN-P - March 2006

Page 44

4-6

Installation and System Configuration

Verify DF1 Port Configuration

Jumper JW2 selects the following electrical interface for the DF1 port. • RS-423/232 (default) • RS-422 • RS-485 DF1 Port Configuration RS-423/232

9 7 5 3 1 10 8 6 4 2

RS-485

JW2 DF1 Port

RS-422

ATTENTION

Publication 1747-UM005B-EN-P - March 2006

All other jumper settings are illegal and may cause damage to the module.

Page 45

Installation and System Configuration

Install Your Module in an Open Slot

4-7

Installation procedures for this module are the same as any other digital I/O or specialty module. IMPORTANT

ATTENTION

Make sure you have JW1, JW2, and JW4 configured.

Do not install or remove the 1747-KE module from the SLC 500 chassis until all power dissipates from the SLC 500 power supply (approximately 10 seconds).

To install the module: 1. Align the full-size module circuit board with the chassis card guide. The first slot (slot 0) of the first chassis is reserved for the CPU. 2. Slide the module into the chassis until the top and bottom latches are latched. To remove the module, press the releases at the top and bottom of the module and slide it out.

Module Release

Card Guide

Publication 1747-UM005B-EN-P - March 2006

Page 46

4-8

Installation and System Configuration

Connect Cable to CONFIG or DF1 Ports

The CONFIG and DF1 ports communicate to user devices through RS-423/232, RS-422, and RS-485 Communication modes. The Communication mode is selected by setting jumpers JW1 and JW2 as described on pages 4-5 and 4-6. IMPORTANT

The following table and cable drawings assume the peripheral devices have conventional pin assignments. Check the documentation for your device to verify signals conform to those shown.

Use these pin assignments to construct communication cables for the CONFIG and DF1 ports. These connectors must be wired to correspond to the selected communication mode. Pin Assignments for CONFIG and DF1 Ports RS-423/232 RS-422 RS-485 Pin for Signal Signal Interface Signal Module

Signal

25-pin Pin

9-pin Pin

1

(1)

TXD-

TRXD-

DCD or CD

8

1

2

RXD

RXD-

(3)

RXD

3

2

3

TXD

(2)

(2)

TXD

2

3

4

DTR

(2)

(2)

DTR

20

4

5

COM

COM

COM

COM

7

5

6

DSR

RXD+

(3)

DSR

6

6

7

RTS

(2)

(2)

RTS

4

7

8

CTS

(2)

(2)

CTS

5

8

9

(1)

TXD+

TRXD+

RI

22

9

(1)

In RS-423 mode, these pins are still connected to their RS-422 loads. Do not use these pins in RS-423 mode.

(2)

In RS-422 and RS-485 modes these pins are connected to their RS-423 drivers and receivers. Do not use these pins in either RS-422 or RS-485 modes.

(3)

In RS-485 mode, these pins are still connected to their RS-422 receivers. Do not use these pins in RS-485 mode.

IMPORTANT

Publication 1747-UM005B-EN-P - March 2006

IBM AT Standard RS-423/232

The signal names on a DCE device are viewed from a DTE perspective. For example, TXD is a DTE output and also a DCE input.