Page 47
Installation and System Configuration
4-9
These illustrations show wiring diagrams for the RS-423/232, RS-422, and RS-485 communications. RS-423/232 DTE to DCE (Non-modem Hardware Handshake to DCE) Interface Module
Peripheral 9-pin 25-pin
NC
1
CD
1
8
RXD
2 3 4
RXD
2 3 4
3 2 20
5 6
7 6
7 8 9
4 5 22
TXD DTR COM DSR RTS CTS NC
TXD DTR
5 6
COM DSR
7 8 9
RTS CTS RI
DTE
DCE
RS-423/232 DTE to DCE (Modem Hardware Handshake to DCE)
Interface Module
Peripheral 9-pin 25-pin
NC
1
CD
1
8
RXD
2 3 4
RXD
2 3 4
3 2 20
5 6
7 6
7 8 9
4 5 22
TXD DTR COM DSR RTS CTS NC
DTE
5 6 7 8 9
TXD DTR COM DSR RTS CTS RI
DCE
Publication 1747-UM005B-EN-P - March 2006
Page 48
4-10
Installation and System Configuration
RS-423/232 DTE to DCE (No Handshake to DCE) Interface Module
Peripheral 9-pin 25-pin
NC
1
CD
1
8
RXD
RXD
COM
2 3 4 5
COM
2 3 4 5
3 2 20 7
DSR
6
DSR
6
6
RTS
7 8 9
RTS
7 8 9
4 5 22
TXD DTR
CTS NC
TXD DTR
CTS RI
DTE
(1)
(1)
DCE
(1) Connect DSR to DTR and CTS to RTS when using devices that cannot disable their hardware handshaking.
RS-423/232 DTE to DTE (Soft or No Handshake to DTE Interface Module
Peripheral 9-pin 25-pin
NC
1
CD
1
8
RXD
2
RXD
2
3
TXD
3 4
TXD
DTR
DTR
3 4
2 20
COM
5
COM
5
7
DSR
6
DSR
6
6
RTS
7 8 9
RTS
7 8 9
4 5 22
CTS NC
CTS RI
DTE
(1)
(1)
DTE
(1) Connect DSR to DTR and CD, and CTS to RTS when using devices that cannot disable their handshaking.
RS-422 Interface Module
Peripheral
TXD-
1
RXD-
RXD-
2
TXD-
3 4 COM
5
COM
RXD+
6
TXD+
TXD+
7 8 9
RXD+
DTE
Publication 1747-UM005B-EN-P - March 2006
Page 49
Installation and System Configuration
4-11
RS-485 Interface Module TRXD-
Peripheral
1
TRXD-
2 3 4 COM
5
COM
6
TRXD+
7 8 9
TRXD+
DTE
Connect Cable to the DH-485 Port
The DH485 port can communicate to user devices through the DH-485 Communication mode. Use a 1747-C11, 1747-C10, or 1747-C13 interface cable to connect the module to a link coupler interfaced with the DH-485 network. If you use the 1747-C11 or 1747-C10 cable, it connects between the DH-485 port on the module and the J1 (CPU) connector on the link coupler. Power for the link coupler will come from the interface module. Refer to page A-1 for more information. Connect to the DH-485 Port via the 1747-C11 Cable Link Coupler (1747-AIC)
Interface Module (1747-KE)
CONFIG Port
DF1 Port J1 (CPU) Cable (1747-C11)
DH-485 Port
If you use the 1747-C13 cable, it connects between the DH-485 port on the module and the J2 (Peripheral) connector on the link coupler. Power for the link coupler must be provided from some other source. See page A-1 for more information.
Publication 1747-UM005B-EN-P - March 2006
Page 50
4-12
Installation and System Configuration
Connect to the DH-485 Port via the 1747-C11 Cable Link Coupler (1747-AIC)
Interface Module (1747-KE)
CONFIG Port Cable (1747-C11)
J2 (Peripheral) DF1 Port J1 (CPU)
Power is supplied to link coupler through the DH-485 port on the SLC 500 processor.
Cable (1747-C11)
DH-485 Port
OR Power is supplied to link coupler by an eternal power source.
The 1747-C13 cable can also connect the module’s DH-485 port directly to a single SLC processor. It connects between the DH-485 port on the module and the DH-485 port on the SLC 500 processor. Connect to the DH-485 Port via the 1747-C13 Cable SLC 500 Processor
Module is connected directly to the DH-485 port on the SLC processor.
Publication 1747-UM005B-EN-P - March 2006
Interface Module (1747-KE)
Cable (1747-C13)
Page 51
Installation and System Configuration
4-13
Configure Your SLC Chassis The slot containing the interface module must be assigned within the SLC program. Using RSLogix 500 software, you can either manually insert the KE module into the chassis configuration in I/O Configuration or select Read I/O Config to read the current I/O configuration out of the processor and insert the module automatically. Enter the module ID code 4209. The ID code for interface modules with series A functionality is 4209, while the ID code for the interface modules with series B functionality is 3509. Entering the module ID code will automatically create the correct input and output words.
Publication 1747-UM005B-EN-P - March 2006
Page 52
4-14
Installation and System Configuration
Configure the DF1 Driver within RSLinx Software
To configure the DF1 driver within RSLinx software: 1. Open RSLinx Classic. 2. Select Configure Drivers. 3. Click Add New. 4. Click Auto-Configure. If RSLinx software successfully communicates with the 1747-KE module, the following dialog appears.
Publication 1747-UM005B-EN-P - March 2006
Page 53
Installation and System Configuration
Configure Your Module
4-15
Configuration instructions are in Chapter 5, Module Configuration Using an ASCII Terminal, and Chapter 6, Module Configuration Using the Backplane. Proceed to the chapter that corresponds to the configuration method you have chosen.
ATTENTION
Complete the Installation of Your Module
This module is a device used for communications. Improper configuration or module failure may cause communications to stop. Be careful to avoid system designs that would cause probable safety concerns within the system in the event of a communication failure.
Once your interface module has been configured, complete the module’s installation.
ATTENTION
Do not install or remove the 1747-KE module from the SLC 500 chassis until all power dissipates from the SLC 500 power supply (approximately 10 seconds).
1. If you configured your module using an ASCII terminal, place the module into Run mode. a. Remove the module from the chassis. The removal is reverse of the installation directions found on page 4-7. b. Place your module in Run mode using JW4 Series A Functionality (mod. config. ID=4209)
Horizontal Run Mode
Series B Functionality (mod. config. ID=3509)
Vertical Run Mode
Publication 1747-UM005B-EN-P - March 2006
Page 54
4-16
Installation and System Configuration c. Re-insert the module into the chassis. IMPORTANT
Make sure you have JW4 positioned for the Run mode that corresponds to the functionality you’ve chosen for your module.
2. Connect the DF1 cable to the DF1 port. 3. Connect the DH-485 cable to the DH-485 port. 4. Insert the cable tie in the slots and secure the cable. 5. Cover all unused slots with the Card Slot Filler (catalog number 1746-N2).
DF1 Port DH-485 Port
6. Apply power to the SLC 500 chassis. 7. Verify that the LED indicators on the module indicate normal operation per the LED indicator table on page 1-3.
Publication 1747-UM005B-EN-P - March 2006