Page 86
Chapter
7
Maintaining Your Control System This chapter covers the following: • handling, storing, and transporting battery, Catalog Number 1747–BA • installing or replacing your SLC 500 battery • replacing the power supply fuse • replacing retainer clips on a module Refer to chapter 2 for important information on testing the master control relay circuit and preventive maintenance.
Handling, Storing, and Transporting Battery, Catalog Number 1747-BA
Follow the procedure below to ensure proper battery operation and reduce personnel hazards.
Handling • Use only for the intended operation. • Do not ship or dispose of batteries except according to recommended procedures. • Do not ship on passenger aircraft.
!
ATTENTION: Do not charge the batteries. An explosion could result or they could overheat causing burns. Do not open, puncture, crush, or otherwise mutilate the batteries. A possibility of an explosion exists and/or toxic, corrosive, and flammable liquids would be exposed. Do not incinerate or expose the batteries to high temperatures. Do not attempt to solder batteries. An explosion could result. Do not short positive and negative terminals together. Excessive heat could build up and cause severe burns.
Storing Store the lithium batteries in a cool, dry environment, typically +20° C to +25° C (+68° F to +77° F) and 40% to 60% relative humidity. Store the batteries and a copy of the battery instruction sheet in the original container, away from flammable materials.
7–1
Page 87
Chapter 7 Maintaining Your Control System
Transporting One or Two Batteries – Each battery contains 0.23 grams of lithium. Therefore, up to two batteries can be shipped together within the United States without restriction. Regulations governing shipment to or within other countries may differ. Three or More Batteries – Procedures for the transportation of three or more batteries shipped together within the United States are specified by the Department of Transportation (DOT) in the Code of Federal Regulations, CFR49, “Transportation.” An exemption to these regulations, DOT – E7052, covers the transport of certain hazardous materials classified as flammable solids. This exemption authorizes transport of lithium batteries by motor vehicle, rail freight, cargo vessel, and cargo–only aircraft, providing certain conditions are met. Transport by passenger aircraft is not permitted. A special provision of DOT–E7052 (11th Rev., October 21, 1982, par. 8–a) provides that: “Persons that receive cell and batteries covered by this exemption may reship them pursuant to the provisions of 49 CFR 173.22a in any of these packages authorized in this exemption including those in which they were received.” The Code of Federal Regulations, 49 CRF 173.22a, relates to the use of packaging authorized under exemptions. In part, it requires that you must maintain a copy of the exemption at each facility where the packaging is being used in connection with shipment under the exemption. Shipment of depleted batteries for disposal may be subject to specific regulation of the countries involved or to regulations endorsed by those countries, such as the IATA Restricted Articles Regulations of the International Air Transport Association, Geneva, Switzerland. Important: Regulations for transportation of lithium batteries are periodically revised.
!
7–2
ATTENTION: Do not incinerate lithium batteries in general trash collection. Explosion or violent rupture is possible. Batteries should be collected for disposal in a manner to prevent against short circuiting, compacting, or destruction of case integrity and hermetic seal.
Page 88
Chapter 7 Maintaining Your Control System
For disposal, batteries must be packaged and shipped in accordance with transportation regulations, to a proper disposal site. The U.S. Department of Transportation authorizes shipment of “Lithium batteries for disposal” by motor vehicle only in regulation 173.1015 of CRF49 (effective January 5, 1983). For additional information contact: U.S. Department of Transportation Research and Special Programs Administration 400 Seventh Street, S.W. Washington, D.C. 20590 Although the Environmental Protection Agency at this time has no regulations specific to lithium batteries, the material contained may be considered toxic, reactive, or corrosive. The person disposing of the material is responsible for any hazard created in doing so. State and local regulations may exist regarding the disposal of these materials.
7–3
Page 89
Chapter 7 Maintaining Your Control System
Installing or Replacing Your SLC 500 Battery
Back–up power for RAM is provided by a capacitor that will retain the contents of the RAM for a period of 5 to 30 days. For applications requiring memory back–up for a longer period of time an optional replaceable battery, Catalog Number 1747–BA, is required. The lithium battery provides back–up for approximately five years. A red BATTERY LOW LED turns on when the battery voltage has fallen below a threshold level. For battery installation or replacement, do the following: 1. Back up your ladder program. 2. Disconnect power to the processor.
!
ATTENTION: When power is applied to the controller hazardous electrical potentials exist under the front cover. See page 2–8 for more information.
3. Remove the processor cover. 4. If you are: installing a battery in a new processor (battery never installed before), remove the jumper from the battery socket. Store jumper in safe place for possible future use without battery. replacing an old battery, unplug the battery connector from the socket. The figure below shows you where to install the battery in a fixed controller. 5. Insert a new or replacement battery in the holder making sure it is held in by the retaining clip. 6. Plug the battery connector into the socket. See the figure below. Battery Connector Red Lead
Battery
+ White Lead
Retaining Clips
7. Replace the cover.
7–4
Page 90
Chapter 7 Maintaining Your Control System
Replacing the Power Supply Fuse
Under normal power–up conditions, the POWER LED turns on. If a power supply fuse is blown, the POWER LED will not turn on. One of the following conditions could cause a blown power supply fuse:
• excessive line voltage • internal power supply malfunction • overloading 2–slot chassis
!
ATTENTION: Contact with AC line potential can cause injury to personnel. Remove system power before attempting fuse replacement. Use only replacement fuses of the type and rating recommended for the unit. Improper fuse selection can result in equipment damage.
After the conditions causing the malfunction have been corrected, you can replace the fuse: 1. Disconnect power to the processor.
!
ATTENTION: When power is applied to the controller hazardous electrical potentials exist under the front cover. See page 2–8 for more information.
2. Remove the cover on the processor. 3. Locate the fuse. Use a miniature fuse puller to grip the fuse and remove it from its holder. 4. Discard the fuse and replace it with the recommended replacement fuse. (See chapter 9 for more information.)
Fuse
5. Replace the cover on the processor. 6. Restore power to the processor. The POWER LED should now turn on.
7–5
Page 91
Chapter 7 Maintaining Your Control System
Replacing Retainer Clips on an I/O Module
If it becomes necessary to replace the retainer clip (also called self–locking tab), order Catalog Number 1746–R15 (4 clips per package). Retainer Clip
Holding Tabs
Removing Damaged Retainer Clips If necessary, pry off the broken retainer clip from the bottom with a screwdriver. Do not twist it off. You can damage the module. Retainer Clip
Installing New Retainer Clips Insert one of the pins of the retainer clip into the hole in the I/O module and then snap the other end in place.