The text of a manual · part 12 of 26
SLC 500 Fixed Hardware Style (Cat. No. 1747-L20, 1747-L30, and 1747-L40 Processors) Installation and Operation Manual: 8 - Troubleshooting
Pages 92 to 103 of 223, from SLC 500 Fixed Hardware Style (Cat. No. 1747-L20, 1747-L30, and 1747-L40 Processors) Installation and Operation Manual
The original document is the PDF (1.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1747-L20A, Allen-Bradley 1747-L20B, Allen-Bradley 1747-L20C, Allen-Bradley 1747-L20L, Allen-Bradley 1747-L30D, Allen-Bradley 1747-AIC and Allen-Bradley 1747-L40C
Page 92
Chapter
8
Troubleshooting In this chapter, you will learn about: • calling Allen–Bradley for assistance • tips for troubleshooting your control system • troubleshooting your fixed controller • troubleshooting your input modules • troubleshooting your output modules
Calling Allen-Bradley for Assistance
If you need to contact Allen–Bradley or your local distributor for assistance, it is helpful to obtain the following (prior to calling): • processor type, series letter, and firmware (FRN) number (see label on side of processor module) • processor LED status • processor error codes (found in S:6 of status file) • hardware types in system (I/O modules, chassis) • revision of programming device (on the main menu of the Hand–Held Terminal or Advanced Programming Software)
8–1
Page 93
Chapter 8 Troubleshooting
Tips for Troubleshooting Your Control System
When troubleshooting, pay careful attention to these general warnings:
!
ATTENTION: Have all personnel remain clear of the controller and equipment when power is applied. The problem may be intermittent and sudden unexpected machine motion could result in injury. Have someone ready to operate an emergency–stop switch in case it becomes necessary to shut off power to the controller equipment. Also, see NFPA 70E Part II for additional guidelines for safety related work practices. Never reach into a machine to actuate a switch since unexpected machine motion can occur and cause injury. Remove all electrical power at the main power disconnect switches before checking electrical connections or inputs/outputs causing machine motion.
If installation and start–up procedures detailed in chapters 3, 4, and 5 were followed closely, your SLC controller will give you reliable service. If a problem should occur, the first step in the troubleshooting procedure is to identify the problem and its source. The SLC 500 controller has been designed to simplify troubleshooting procedures. By observing the diagnostic indicators on the front of the processor unit and I/O modules, the majority of faults can be located and corrected. These indicators, along with error codes identified in the programming device user manual and programmer’s monitor, help trace the source of the fault to the user’s input/output devices, wiring, or the controller.
Removing Power Before working on a SLC 500 fixed system, always remove the power supply input power at the main power disconnect switch. The POWER LED on the power supply indicates that DC power is being supplied to the chassis. This LED could be off when incoming power is present when the:
• fuse is blown • voltage drops below the normal operating range. Refer to chapter 1 for more information. • power supply is defective
8–2
Page 94
Chapter 8 Troubleshooting
Replacing Fuses When replacing a fuse, be sure to remove all power from the system.
Program Alteration There are several causes of alteration to the user program, including extreme environmental conditions, Electromagnetic Interference (EMI), improper grounding, improper wiring connections, and unauthorized tampering. If you suspect the memory has been altered, check the program against a previously saved program on an EEPROM, UVPROM or Flash EPROM module.
Troubleshooting Your Fixed Controller
To receive the maximum benefit of this troubleshooting section, we recommend you follow these steps: 1. Match your processor LEDs with the status LEDs located in the first column in the tables on the following pages. 2. Once the status LEDs are matched to the appropriate table, simply move across the table identifying error description and probable causes. 3. Follow the recommended action steps for each probable cause until the cause is identified. 4. If recommended actions do not identify the cause, contact your local Allen–Bradley sales office or distributor.
8–3
Page 95
Chapter 8 Troubleshooting
Identifying Fixed Controller Errors Refer to the following key to determine the status of the LED indicators: Indicates the LED is OFF. Indicates the LED is ON. Indicates the LED is FLASHING. If the LEDs indicate: POWER
The Following Error Exists
PC RUN
Probable Cause No Line Power
CPU FAULT FORCED I/O BATTERY LOW
Inadequate System Power
Power Supply Fuse Blown
Power Supply Overloaded
Recommended Action Verify proper line voltage and connections on the power terminals. 1. Check the incoming power fuse, check for proper incoming power connections. Replace fuse. 2. If fuse blows again, replace the fixed controller. This problem can occur intermittently if power supply is lightly overloaded when output loading and temperature varies. If you are using a 2-slot chassis, verify the compatibility of the modules to prevent overloading the backplane power.
If the LEDs indicate: POWER
The Following Error Exists
Probable Cause
PC RUN
1. Verify selected processor mode.
CPU FAULT
2. If in program/test modes, attempt RUN mode entry.
FORCED I/O BATTERY LOW
Processor Not in Run Mode
Either Improper Mode Selected or User Program Logic Error
Line Power Out of Operating Range
8–4
Recommended Action
3. Check user program logic for suspend instructions if in suspend mode. Refer to either the Hand-Held Terminal User Manual, Catalog Number 1747-NP002, or the Advanced Programming Software User Manual, Catalog Number 1747-NM002. 1. Check incoming power connections. 2. Monitor for proper line voltage at the incoming power connections.
Page 96
Chapter 8 Troubleshooting
If the LEDs indicate: POWER
The Following Error Exists
Probable Cause
PC RUN
Monitor logic in Run mode and verify desired I/O status.
CPU FAULT FORCED I/O BATTERY LOW
Recommended Action
System Inoperable, No Major CPU Faults Detected
User Program Logic Error
Defective I/O Devices or I/O Wiring
Refer to either the Hand-Held Terminal User Manual , Catalog Number 1747-NP002, or the Advanced Programming Software User Manual, Catalog Number 1747-NM002. Test inputs and outputs according to I/O troubleshooting procedures starting on page 8-8.
If the LEDs indicate: POWER
The Following Error Exists
PC RUN
Probable Cause CPU Memory Error
CPU FAULT FORCED I/O
Recommended Action Cycle power. 1. Remove power and then remove the memory module from the controller.
BATTERY LOW
CPU Fault
Faulty Memory Module
2. Re-energize the controller. If steady CPU FAULT LED changes to flashing, replace the existing memory module with a replacement module. Refer to chapter 4 for removing and installing memory modules.
Processor Firmware Installed Incorrectly
If upgrading the processor to a different firmware level, verify that the firmware chip orientation matches the upgrade kit directions.
Refer to the following key to determine the status of the LED indicators: Indicates the LED is OFF. Indicates the LED is ON. Indicates the LED is FLASHING.
8–5
Page 97
Chapter 8 Troubleshooting
If the LEDs indicate: POWER
The Following Error Exists
PC RUN CPU FAULT FORCED I/O BATTERY LOW
Probable Cause
Recommended Action
Initial CPU Factory Power-up Condition
1. Refer to chapter 6 and follow the start-up procedures. 2. Clear processor memory to get rid of the flashing CPU FAULT LED. 1. Monitor Status File Word S:6 for major error code.
CPU Major Fault
Hardware/Software Major Fault Detected Erratic repetitive power cycling can cause a processor major hardware fault.
2. Refer to either the Hand-Held Terminal User Manual, Catalog Number 1747-NP002, or the Advanced Programming Software User Manual, Catalog Number 1747-NM002, for error codes and additional troubleshooting information. 3. Remove hardware/software condition causing fault. 4. Clear Status File S:1/13 major error bit, if set. 5. Clear Status File S:5 minor error bits, if set. 6. Clear Status File S:6 major error code (optional). 7. Attempt a processor Run mode entry. If unsuccessful, repeat recommended action steps above.
If the LEDs indicate: POWER
The Following Error Exists
Probable Cause
PC RUN
1. Monitor program file online and identify forced I/O.
CPU FAULT FORCED I/O BATTERY LOW
Refer to the following key to determine the status of the LED indicators: Indicates the LED is OFF. Indicates the LED is ON. Indicates the LED is FLASHING.
8–6
Recommended Action
System does not operate per ladder logic.
User Forced I/O Disabling Operation
2. Disable appropriate forces and test system conditions again. Refer to either the Hand-Held Terminal User Manual, Catalog Number 1747-NP002, or the Advanced Programming Software User Manual, Catalog Number 1747-NM002.
Page 98
Chapter 8 Troubleshooting
If the LEDs indicate: POWER
The Following Error Exists
Probable Cause
PC RUN
1. Monitor program file online and identify programmed forces.
CPU FAULT FORCED I/O BATTERY LOW
Recommended Action
System does not operate per programmed forces.
User Programmed Forces are Not Enabled
The Following Error Exists
Probable Cause
2. Enable appropriate forces and test system conditions again. Once forces are enabled, the FORCED I/O LED goes on steady. Refer to either the Hand-Held Terminal User Manual, Catalog Number 1747-NP002, or the Advanced Programming Software User Manual, Catalog Number 1747-NM002.
If the LEDs indicate: POWER PC RUN
1. Verify battery is connected. See page 7-4.
CPU FAULT FORCED I/O
BATTERY LOW➀
Recommended Action
2. Replace the battery. See page 7-4. CPU Major Error with Low or No Battery Back-up
Loss of RAM during Power Down Period
3. Refer to processor major fault recommended action steps. Refer to either the Hand-Held Terminal User Manual, Catalog Number 1747-NP002, or the Advanced Programming Software User Manual, Catalog Number 1747-NM002.
Refer to the following key to determine the status of the LED indicators: Indicates the LED is OFF. Indicates the LED is ON. Indicates the LED is FLASHING. ➀ Regardless of any other LED status indicator conditions, always replace the battery when the BATTERY LOW LED is on if you want RAM battery backup. If you want to back up RAM with a capacitor, add or replace the BATTERY LOW LED jumper.
8–7
Page 99
Chapter 8 Troubleshooting
Troubleshooting Your Input Modules
The following will assist you in troubleshooting your input modules.
Input Circuit Operation An input circuit responds to an input signal in the following manner: 1. An input filter removes false signals due to contact bounce or electrical interference. 2. Optical isolation protects the backplane circuits by isolating logic circuits from input signals. 3. Logic circuits process the signal. 4. An input LED turns on or off indicating the status of the corresponding input device. Input
Input Conditioning
Optical Isolation
Logic Circuits
Processor
LED
5. The processor receives the input status for use in processing the program logic.
8–8
Page 100
Chapter 8 Troubleshooting
Corrective Action If your Input Circuit LED is
And Your Input Device is
On/Closed/Activated
And
Probable Cause
Recommended Action
Your input device will not turn off.
Device is shorted or damaged.
Verify device operation. Replace device.
Input is forced off in program.
Check the FORCED I/O or FORCE LED on processor and remove forces.
Input circuit is damaged.
Try other input circuit. Replace module.
Input device Off-state leakage current exceeds input circuit specification.
Check device and input circuit specifications. Use load resistor to bleed-off current.
Input device is shorted or damaged.
Verify device operation. Replace device.
Input circuit is miswired or damaged.
Verify proper wiring. Try other input circuit. Replace module.
Input circuit is incompatible.
Check specification and sink/source compatibility (if DC input).
Low voltage across the input.
Check the voltage across input circuit and check source voltage.
Incorrect wiring or an open circuit.
Check wiring and COMmon connections.
Input signal turn on time too fast for input circuit.
Check timing specifications.
Input circuit is damaged.
Verify proper wiring. Try other input circuit. Replace module.
Input device is opened or damaged.
Verify operation. Replace device.
Input is forced on in program.
Check processor FORCED I/O or FORCE LED and remove forces. Verify proper wiring. Try other input circuit.
Input circuit is damaged.
Verify proper wiring. Try other input circuit. Replace module.
Your program operates as though it is off.
On
Off/Open/Deactivated
On/Closed/Activated
Your program operates as though it is on and/or the input circuit will not turn off.
Your program operates as though it is off and/or the input circuit will not turn on.
Off
Your input device will not turn on. Off/Open/Deactivated
Your program operates as though it is on.
8–9
Page 101
Chapter 8 Troubleshooting
Troubleshooting Your Output Modules
The following will assist you in troubleshooting your output modules.
Output Circuit Operation An output circuit controls the output signal in the following manner: 1. The processor determines the output status. 2. Logic circuits maintain the output status. 3. An output LED indicates the status of the output signal. 4. Optical isolation separates logic and backplane circuits from field signals. 5. The output driver turns the corresponding output on or off. Processor
Logic Circuits
Optical Isolation
LED
8–10
Output Drivers
Output
Page 102
Chapter 8 Troubleshooting
Corrective Action If your Output Circuit LED is
And Your Output Device is
And
Probable Cause
Recommended Action Check for duplicate outputs and addresses using the search function.
Programming problem.
On/Energized
Your program indicates that the output circuit is off or the output circuit will not turn off.
Use the force function to force output off. If this does not force the output off, output circuit is damaged. If the output does force off, then check again for logic/programming problem. Output is forced on in program.
Check processor FORCED I/O or FORCE LED and remove forces.
Output circuit is damaged.
Use the force function to force the output off. If this forces the output off, then there is a logic/programming problem. If this does not force the output off, the output circuit is damaged. Try other output circuit. Replace module.
Low or no voltage across the load.
Measure the source voltage and check specifications.
Incorrect wiring or open circuit.
Check wiring and COMmon connections.
Output device is incompatible.
Check specifications and sink/source compatibility (if DC output).
Output circuit is damaged.
Check wiring. Try other output circuit. Replace module.
Output device is incompatible.
Check specifications.
Output circuit Off-state leakage current may exceed output device specification.
Check specifications. Use load resistor to bleed off leakage current. See output specifications.
Incorrect wiring.
Check wiring. Disconnect from SLC and verify device operation.
Output device is shorted or damaged.
Verify device operation. Replace device.
Output circuit is damaged.
Check wiring. Try other output circuit. Replace module.
On
Off/De-energized
On/Energized
Your output device will not turn on and the program indicates that it is on.
Your output device will not turn off and the program indicates that it is off.
If using subroutines, outputs are left in their last state when not executing subroutines.
Check for duplicate outputs and addresses using search function. Off Programming problem.
Off/De-energized
Your program indicates that the output circuit is on or the output circuit will not turn on.
If using subroutines, outputs are left in their last state when not executing subroutines. Use the force function to force output on. If this does not force the output on, output circuit is damaged. If the output does force on, then check again for logic/programming problem.
Output is forced off in program.
Check processor FORCED I/O or FORCE LED and remove forces.
Output circuit is damaged.
Use the force function to force the output on. If this forces the output on, then there is a logic/programming problem. If this does not force the output on, the output circuit is damaged. Try other output circuit. Replace module. 8–11