SLC 500 Fixed Hardware Style (Cat. No. 1747-L20, 1747-L30, and 1747-L40 Processors) Installation and Operation Manual, pages 104 to 112

Pages 104 to 112 of 223: 9 - Replacement Parts; A - Setting Up the DH-485 Network

The original document is the PDF (1.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1747-L20A, Allen-Bradley 1747-L20B, Allen-Bradley 1747-L20C, Allen-Bradley 1747-L20L, Allen-Bradley 1747-L30D, Allen-Bradley 1747-AIC and Allen-Bradley 1747-L40C

Page 104

Chapter

9

Replacement Parts This chapter provides a list of replacement parts and a list of replacement terminal blocks for your SLC 500 controller.

Replacement Parts

This table provides a list of replacement parts and their catalog numbers. Description

Pre-wired Interface Cable Replacement Fuses

Available in 1.0m, 2.5m, and 5.0m lengths.

Catalog Number 1492-CABLE➀H

Five fuses per package. Orders must be for five fuses or multiples of five.

Replacement fuse for Fixed I/O AC units, MDL 1.25 Ampere

1746-F4

Replacement fuse for Fixed I/O DC units, MDL 1.6 Ampere

1746-F5

Modular Card Slot Fillers

1746-N2

Connector

Two fillers per package. Orders must be for two fillers or multiples of two.

Mating Connector for 32 Point user-made cable

Kit consisting of four replacement terminal covers and labels for 4, 8, 16 I/O modules Replacement Cover for Specialty I/O Two covers per package. Orders must be for two covers or multiples of two. Replacement Retainer Clips for Modules Four clips per package. Orders must be for four clips or multiples of four. Lithium Battery Assembly This is an optional part used for the SLC 500 Fixed and Modular Hardware Style processors and the Hand-Held Terminal. Refer to product documentation for proper storage and handling instructions. For disposal information, consult your nearest Allen-Bradley Sales Office.

1746-N3 1746-R9 1746-R13 1746-R15 1747-BA

Processor to Peripheral Programming/Communication Cable

1747-C10

Processor to Isolated Link Coupler Cable

1747-C11

Specialty Module to Isolated Link Coupler Cable

1747-C13

EEPROM with 1K User Instructions

1747-M1

UVPROM with 1K User Instructions

1747-M3

Adapter Sockets

1747-M5

Orders must be for five sockets or multiples of five.

Replacement Parts Kit for 20 I/O Fixed Hardware Style Processor Two Output Terminal Covers Two Input Terminal Covers Two Prom/Battery Covers One HHT/Comm Connector Cover Replacement Parts Kit for 30 and 40 I/O Fixed Hardware Style Processors Two Output Terminal Covers Two Input Terminal Covers Two Prom/Battery Covers One HHT/Comm Connector Cover Replacement Terminal Covers for 4, 8, & 16 I/O Modules This kit contains four blank covers and appropriate labels for replacement of any required I/O module cover. HHT Keypad Replacement Overlay for English Memory Pak Firmware Releases 1.02, 1.07 and 1.10

1747-R5

1747-R7

1747-R9 1747-R20

HHT Keypad Replacement Overlay for French Memory Pak Firmware Releases 1.10

1747-R20F

HHT Keypad Replacement Overlay for German Memory Pak Firmware Releases 1.10

1747-R20G

HHT Keypad Replacement Overlay for Italian Memory Pak Firmware Releases 1.10

1747-R20I

HHT Keypad Replacement Overlay for English Memory Pak Firmware Releases 2.00 and Later

1747-R21

HHT Keypad Replacement Overlay for French Memory Pak Firmware Releases 2.00 and Later

1747-R21F

➀ Insert the cable length code into the catalog number. Cable length codes are as follows: 10=1.0m, 25=2.5m, and 50=5.0m. For example, 1492-CABLE25H is a 2.5m cable.

9–1

Page 105

Chapter 9 Replacement Parts

Replacement Terminal Blocks

This table provides a list of replacement terminal blocks and their catalog numbers. Description

Replacement Terminal Block (Red)

Used with AC I/O modules, Catalog Numbers 1746-IA16, OA16, IM16

Replacement Terminal Block (Blue) Used with DC I/O modules, Catalog Numbers 1746-IB16, IV16, OB16, OV16, IN16, IG16, OG16 Replacement Terminal Block (Orange) Used with relay output modules, Catalog Numbers 1746-OW16, OX8 Replacement Terminal Block (Green)

Used with Specialty I/O modules, Catalog Numbers 1746-HSCE, IO12

Catalog Number 1746-RT25R 1746-RT25B 1746-RT25C 1746-RT25G

Replacement Terminal Block NO4V Replacement Terminal Block NO4V Replacement Terminal Block

2 position terminal block used with analog output modules, Catalog Numbers 1746-NO4I,

Used with analog input modules, Catalog Numbers 1746-NI4, NIO4I, NIO4V

1746-RT28

Replacement Terminal Block

Used with RIO Communication Modules, Catalog Numbers 1747-SN, DSN, DCM

1746-RT29

Replacement Terminal Block

Used with DH-485 Link Coupler, Catalog Number 1747-AIC

1746-RT30

9–2

8 position terminal block used with analog output modules, Catalog Numbers 1746-NO4I,

1746-RT26 1746-RT27

Page 106

A

Appendix

Setting Up the DH-485 Network The information in this appendix will help you plan, install, and operate the SLC 500 in a DH–485 network. This chapter also contains information that describes the DH–485 network functions, network architecture, and performance characteristics. It also covers: • DH–485 network description • DH–485 network protocol • DH–485 token rotation • DH–485 network initialization • devices that use the DH–485 network • 1747–AIC isolated link coupler for DH–485 • example system configuration • important planning considerations • DH–485 network installation

DH-485 Network Description

DH-485 Network Protocol

We have designed the DH–485 network to pass information between devices on the plant floor. The network monitors process parameters, device parameters, device status, process status and application programs to support data acquisition, data monitoring, program upload/download and supervisory control. The DH–485 network offers: • interconnection of 32 devices • multi–master capability • token passing access control • the ability to add or remove nodes without disrupting the network • maximum network length of 1219 m (4000 ft)

The following section describes the protocol used to control message transfers on the DH–485 network. The protocol supports two classes of devices: initiators and responders. All initiators on the network get a chance to initiate message transfers. To determine which initiator has the right to transmit, a token passing algorithm is used.

A–1

Page 107

Appendix A Setting Up the DH-485 Network

DH-485 Token Rotation

A node holding the token can send any valid packet onto the network. Each node is allowed only one transmission (plus two retries) each time it receives the token. After a node sends one message packet, it attempts to give the token to its successor by sending a “token pass” packet to its successor. If no network activity occurs, the initiator sends the token pass packet again. After two retries (a total of three tries) the initiator will attempt to find a new successor. Important: The maximum address that the initiator will search for before wrapping to zero is the value in the configurable parameter “maximum node address.” The default value for this parameter is 31 for all initiators and responders. The allowable range of the node address of an initiator is 0 to 31. The allowable address range for all responders is 1 to 31. There must be at least one initiator on the network.

DH-485 Network Initialization

Network initialization begins when a period of inactivity exceeding the time of a link dead timeout is detected by an initiator on the network. When the time for a link dead timeout is exceeded, usually the initiator with the lowest address claims the token. When an initiator has the token it will begin to build the network. The network requires at least one initiator to initialize it. Building a network begins when the initiator that claimed the token tries to pass the token to the successor node. If the attempt to pass the token fails, or if the initiator has no established successor (for example, when it powers up), it begins a linear search for a successor starting with the node above it in the addressing. When the initiator finds another active initiator, it passes the token to that node, which repeats the process until the token is passed all the way around the network to the first node. At this point, the network is in a state of normal operation.

A–2

Page 108

Appendix A Setting Up the DH-485 Network

Devices that Use the DH-485 Network

Presently, the following SLC 500 devices support the DH–485 network: • SLC 500 Fixed I/O Controller (responder) • SLC 5/01 Modular I/O Controller (responder) • SLC 5/02 Modular I/O Controller (initiator/responder) • SLC 5/03 Modular I/O Controller (initiator/responder) • Personal computer running SLC 500 Advanced Programming Software (initiator) • Hand–Held Terminal (initiator) • DTAM (initiator/responder) Other devices that use the DH–485 network include those in the table below.

Catalog Number

1746-BAS

1747-KE

1770-KF3

1784-KR

1785-KA5

2760-RB

Description

BASIC Module

DH-485/DF1 Interface Module

DH-485/DF1 Interface Module

PC DH-485 Interface Module

DH+t/DH485 Gateway

Flexible Interface Module

Installation Requirement

Function

Publication

SLC Chassis

Provides an interface for SLC 500 devices to foreign devices. Program in BASIC to interface the 3 channels (2 RS-232 and 1 DH485) to printers, modems, or the DH-485 network for data collection.

1746-ND005 1746-NM002 1746-NM001

SLC Chassis

Provides a non-isolated DH-485 interface for SLC 500 devices to host computers over RS-232 using full- or half-duplex DF1 protocol. Enables remote programming with APS to an SLC 500 processor or the DH-485 network through modems. Ideal for low cost RTU/SCADA applications.

1747-NU001

Standalone

Provides an isolated DH-485 interface for SLC 500 devices to host computers over RS-232 using full- or half-duplex DF1 protocol. Enables remote programming with APS to an SLC 500 processor or the DH-485 network through modems.

1770-6.5.18

IBM XT/AT Computer Bus

Provides an isolated DH-485 port on the back of the computer. When used with APS software, it improves communication speed and eliminates use of the Personal Interface Converter (1747-PIC). The Standard Driver allows you to write programs for data acquisition applications.

1784-2.23 6001-6.5.5

(1771) PLCr Chassis

Provides communication between stations on the PLC-5 (DH+) and SLC 500 (DH-485) networks. Enables communication and data transfer from PLC to SLC 500 on DH-485 network. Also enables APS programming or data acquisition across DH+ to DH-485.

1785-6.5.5 1785-1.21

(1771) PLC Chassis

Provides an interface for SLC 500 (using protocol cartridge 2760-SFC3) to other A-B PLCs and devices. Three configurable channels are available to interface with Bar Code, Vision, RF, Dataliners, and PLC systems.

2760-ND001

A–3

Page 109

Appendix A Setting Up the DH-485 Network

1747-AIC Isolated Link Coupler for DH-485

The isolated link coupler (1747–AIC) is used to connect SLC 500 family devices to the DH–485 network (as shown on page A–5). The coupler provides a 6–position removable terminal block for connection to the DH–485 communication cable. Network connections for the SLC 500 processor are provided by the Catalog Number 1747–C11, 304.8 mm (12 in.) cable supplied with the link coupler. Network connections for peripheral devices, such as the Personal Interface Converter (1747–PIC), Data Table Access Module (1747–DTAM–E), or Hand–Held Terminal (1747–PT1) are provided by the standard Catalog Number 1747–C10 1.8 m (6 ft) cable supplied with each of those devices. To protect connected devices, the coupler provides 1500 VDC isolation between the communications cable and the attached SLC 500 controller and peripheral devices (PIC, DTAM, or HHT). The isolated link coupler can also be used to provide connectivity between a peripheral device (APS and PIC, HHT, or DTAM) for distances greater than 1.8 m (6 ft) up to a maximum of 1219 m (4000 ft). Below is an example of a “remote” connection between a computer running APS and an SLC 500 processor.

1747-AIC

1747-AIC

APS PIC

>1.8 m (6 ft)

1747-C10 1747-C10

NP1

1747-C11 +24VDC

NP1➀ provides +24 VDC for the 1747-AIC.

➀ You can also use an NP2 desktop model.

A–4

Page 110

SLC 500 5/02 Modular I/O Controller

1747–AIC Isolated Link Coupler

1747–PIC Interface Converter

Allen–Bradley 1784–T45, T47 or compatible laptop

1747–AIC

SLC 500 20 point Fixed I/O Controller

1747–AIC

SLC 500 5/03 Modular I/O Controller

Data Table Access Module

SLC 500 5/01 Modular I/O Controller

1747–AIC

DH–485 Network max. length 1219 m (4,000 ft.)

SLC 500 Hand–Held Terminal

1747–AIC

SLC 500 Fixed I/O Controller

1747–AIC

IBM–PC, XT, or compatible with 1784–KR, DH–485 PC Interface

Appendix A Setting Up the DH-485 Network

Example System Configuration Below is an example of a DH–485 network.

A–5

Page 111

Appendix A Setting Up the DH-485 Network

Important Planning Considerations

Carefully plan your network configuration before installing any hardware. Listed below are some of the factors that can affect system performance: • amount of electrical noise, temperature, and humidity in the network environment • number of devices on the network • connection and grounding quality in installation • amount of communication traffic on the network • type of process being controlled • network configuration The major hardware and software issues you need to resolve before installing a network are discussed in the following sections.

Hardware Considerations You need to decide the length of the communication cable, where you route it, and how to protect it from the environment where it will be installed. When the communication cable is installed, you need to know how many devices are to be connected during installation and how many devices will be added in the future. The following sections will help you understand and plan the network. Number of Devices and Length of Communication Cable You must install a link coupler (1747–AIC) for each node on the network. If you plan to add nodes later, provide additional link couplers during the initial installation to avoid recabling after the network is in operation. The maximum length of the communication cable is 1219 m (4000 ft). This is the total cable distance from the first node to the last node on the network. Planning Cable Routes Follow these guidelines to help protect the communication cable from electrical interference: • Keep the communication cable at least five feet from any electric motors, transformers, rectifiers, generators, arc welders, induction furnaces, or sources of microwave radiation. • If you must run the cable across power feed lines, run the cable at right angles to the lines. • If you do not run the cable through a contiguous metallic wireway or conduit, keep the communication cable at least 0.15 m (6 in) from ac power lines of less than 20 A, 0.30 m (1 ft) from lines greater than 20 A, but only up to 100 kVA, and 0.60 m (2 ft) from lines of 100 kVA or more. • If you run the cable through a contiguous metallic wireway or conduit, keep the communication cable at least 0.08 m (3 in) from ac power lines of less than 20 A, 0.15 m (6 in) from lines greater than 20 A, but only up to 100 kVA, and 0.30 m (1 ft) from lines of 100 kVA or more. A–6

Page 112

Appendix A Setting Up the DH-485 Network

Running the communication cable through conduit provides extra protection from physical damage and electrical interference. If you route the cable through conduit, follow these additional recommendations: – Use ferromagnetic conduit near critical sources of electrical interference. You can use aluminum conduit in non–critical areas. – Use plastic connectors to couple between aluminum and ferromagnetic conduit. Make an electrical connection around the plastic connector (use pipe clamps and the heavy gauge wire or wire braid) to hold both sections at the same potential. – Ground the entire length of conduit by attaching it to the building earth ground. – Do not let the conduit touch the plug on the cable. – Arrange the cables loosely within the conduit. The conduit should contain only serial communication cables. – Install the conduit so that it meets all applicable codes and environmental specifications. For more information on planning cable routes, see Industrial Automation Wiring and Grounding Guidelines, publication number 1770–4.1.

Software Considerations Software considerations include the configuration of the network and the parameters that can be set to the specific requirements of the network. The following are major configuration factors that have a significant effect on network performance: • number of nodes on the network • addresses of those nodes • baud rate • maximum node address selection • 5/03 only: token hold factor The following sections explain network considerations and describe ways to select parameters for optimum network performance (speed). Number of Nodes The number of nodes on the network directly affects the data transfer time between nodes. Unnecessary nodes (such as a second programming terminal that is not being used) slow the data transfer rate. The maximum number of nodes on the network is 32.

A–7