Page 56

Chapter

4

Installing Your Hardware Components This chapter shows you how to install and remove the following hardware components: • 2–slot expansion chassis • I/O and speciality modules • memory module • high–speed counter

Mounting the 2-Slot Expansion Chassis

The expansion chassis mounts on the right side of the fixed controller. The chassis has mounting tabs that are inserted into slots in the fixed controller and slid forward. No tools are required. 1. Insert the mounting tabs of the expansion chassis into the mounting slots of the controller.

Mounting Slots

Right Side of the Fixed Controller

4–1

Page 57

Chapter 4 Installing Your Hardware Components

2. Slide the expansion chassis forward until the back of the expansion chassis is flush with the fixed controller and the connector on the expansion circuit board is mated with the connector in the controller.

19528

Installing I/O and Speciality Modules

With the 2–slot expansion chassis on the fixed style unit, additional I/O and specialty modules can be supported.

!

ATTENTION: Never install, remove, or wire modules with power applied to the chassis.

1. Align circuit board of the module with card guide in chassis. Retainer Clip

Side View

Retainer Clip

4–2

Page 58

Chapter 4 Installing Your Hardware Components

2. Gently slide the module in until both top and bottom retainer clips are secured.

19530

3. To remove the module, press the retaining clips at the top and bottom of the module and slide the module out.

4–3

Page 59

Chapter 4 Installing Your Hardware Components

Installing Your Memory Module Always turn off power to the controller before inserting or removing the memory module. This guards against possible damage to the module and also undesired processor faults. Memory modules are mounted in carriers and have connectors that are “keyed” to guard against improper installation.

!

ATTENTION: To avoid potential damage to the memory modules, handle them by the ends of the carrier or edges of the plastic housing. Skin oil and dirt can corrode metallic surfaces, inhibiting electrical contact. Also, do not expose memory modules to surfaces or areas that may hold an electrostatic charge. Electrostatic charges can alter or destroy memory.

1. Always turn off power to the controller before inserting or removing the memory module. This guards against possible damage to the module and also undesired processor faults.

!

ATTENTION: When power is applied to the controller hazardous electrical potentials exist under the front cover. See page 2–8 for more information.

2. Remove the processor compartment cover. 3. Locate the socket on the PC board. Socket

4. Position the module correctly over the socket and press it firmly in place. (The memory module is keyed.)

1747-M1, -M2, -M3

5. Replace the cover on the SLC controller and restore power. 4–4

Page 60

Chapter 4 Installing Your Hardware Components

Removing Your Memory Module To remove a memory module use the following procedure: 1. Remove the power from the fixed I/O unit. 2. Remove the processor compartment cover. 3. Grasp the carrier tabs with the thumb and index fingers, then gently but firmly lift upwards on either end of the memory module carrier. 4. When the end is partially raised, begin lifting the other end in the same manner. Repeat this until the memory module has been completely removed from the socket. 5. Replace processor cover.

Using the High-Speed Counter The fixed I/O units that have 24 VDC input circuits are also equipped with a high–speed counter. The counter is capable of counting at a rate of up to 8 kHz. You have the option of using input 0 as a normal input or as a high–speed counter. To accommodate this dual function the input is equipped with a jumper selectable filter. You must cut the jumper for high–speed counter use. A shielded cable is recommended to reduce noise to the input.

High-Speed Counter Operation For high–speed counter operation do the following: 1. Turn off power to the fixed controller.

!

ATTENTION: When power is applied to the controller hazardous electrical potentials exist under the front cover. See page 2–8 for more information.

2. Remove the SLC 500 cover. 3. Locate and cut jumper wire J2. The jumper is either beneath or to the right of the battery connector, as shown below. Do not remove completely but make certain that the ends of the cut jumper wire are not touching each other.

4–5

Page 61

Chapter 4 Installing Your Hardware Components

The High-Speed Counter jumper is located either beneath the battery connector OR to the right of the battery connector.

J2

J2

4. Replace the cover.

High-Speed Counter Input Compatibility The high–speed counter input circuit has the following characteristics: • nominal input impedance of ≈ 1200 Ω • on–state voltage of 10–30 VDC • nominal input current draw of 20mA • minimum pulse width of 62.5 µsec. Your input device or encoder must be single–ended and be compatible with the specifications of the high–speed counter input. See the table below for more information.

4–6

For an Input Device or Encoder that Is

Use an HSC Input Circuit that Is

Sourcing

Sinking

Open Collector/ Sinking

Sourcing

Open Collector with Pull-up Resistor

Sinking

Page 62

Chapter 4 Installing Your Hardware Components

Wiring Diagram of a High-Speed Counter Sinking Input Circuit DC COM CHASSIS GND

DC COM

IN 1

IN 0 HSC

IN 3 IN 2

IN 5 IN 4 Shielded Twisted Pair Belden or Equivalent

Sourcing Input Device

10-30 VDC

-

+

Wiring Diagram of a High-Speed Counter Sourcing Input Circuit VDC CHASSIS GND

VDC

IN 1

IN 0 HSC

IN 3 IN 2

IN 5 IN 4 Shielded Twisted Pair Belden or Equivalent

Sinking Input Device

10-30 VDC

+

-

4–7