The text of a manual · part 9 of 26

SLC 500 Fixed Hardware Style (Cat. No. 1747-L20, 1747-L30, and 1747-L40 Processors) Installation and Operation Manual: 5 - Wiring Your Control System

Pages 64 to 73 of 223, from SLC 500 Fixed Hardware Style (Cat. No. 1747-L20, 1747-L30, and 1747-L40 Processors) Installation and Operation Manual

The original document is the PDF (1.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1747-L20A, Allen-Bradley 1747-L20B, Allen-Bradley 1747-L20C, Allen-Bradley 1747-L20L, Allen-Bradley 1747-L30D, Allen-Bradley 1747-AIC and Allen-Bradley 1747-L40C

Page 64

Chapter

5

Wiring Your Control System This chapter describes how to wire your I/O modules. It covers the following: • defining sinking and sourcing • determining approximate transient duration • preparing your wiring layout • features of an I/O module • recommendations for wiring I/O devices • wiring your I/O modules • using Removable Terminal Blocks (RTBs)

Defining Sinking and Sourcing

Sinking and sourcing are terms used to describe a current signal flow relationship between field input and output devices in a control system and their power supply. • Field devices connected to the positive side (+V) of the field power supply are sourcing field devices. • Field devices connected to the negative side (DC Common) of the field power supply are called sinking field devices. To maintain electrical compatibility between field devices and the programmable controller system, this definition is extended to the input/output circuits on the discrete I/O modules. • Sourcing I/O circuits supply (source) current to sinking field devices. • Sinking I/O circuits receive (sink) current from sourcing field devices.

5–1

Page 65

Chapter 5 Wiring Your Control System

Contact Output Circuits

AC or DC

Relays can be used for either AC or DC output circuits and accommodate either sinking or sourcing field devices. These capabilities are a result of the output switch being a mechanical contact closure, not sensitive to current flow direction and capable of accommodating a broad range of voltages. This high degree of application flexibility makes contact output modules very popular and useful in control environments with a broad mix of electrical I/O circuit requirements.

Solid-State DC I/O Circuits The design of DC field devices typically requires that they be used in a specific sinking or sourcing circuit depending on the internal circuitry of the device.

Sourcing Device with Sinking Input Module Circuit The field device is on the positive side of the power supply between the supply and the input terminal. When the field device is activated, it sources current to the input circuit. FIELD DEVICE

I Input

+

DC INPUT CIRCUIT

DC POWER SUPPLY _ DC Com

5–2

Page 66

Chapter 5 Wiring Your Control System

Sinking Device with Sourcing Input Module Circuit The field device is on the negative side of the power supply between the supply and the input terminal. When the field device is activated, it sinks current from the input circuit. I Input

FIELD DEVICE _

DC INPUT CIRCUIT

DC POWER SUPPLY + VDC

Sinking Device with Sourcing Output Module Circuit The field device is on the negative side of the power supply between the supply and the output terminal. When the output is activated, it sources current to the field device.

+ DC POWER SUPPLY _

VDC I FIELD DEVICE

Out

DC OUTPUT CIRCUIT

DC Com

Sourcing Device with Sinking Output Module Circuit The field device is on the positive side of the power supply between the supply and the output terminal. When the output is activated, it sinks current from the field device. VDC + DC POWER SUPPLY _

I FIELD DEVICE

Out

DC Com

DC OUTPUT CIRCUIT

5–3

Page 67

Chapter 5 Wiring Your Control System

Preparing Your Wiring Layout

Careful wire routing within the enclosure helps to cut down electrical noise between I/O lines. Follow these rules for routing your wires:

• Route incoming power to the controller by a separate path from wiring to I/O devices. Where paths must cross, their intersection should be perpendicular. Important: Do not run signal or communications wiring and power wiring in the same conduit.

• If wiring ducts are used, allow for at least two inches between I/O wiring ducts and the controller. If the terminal strips are used for I/O wiring, allow for at least two inches between the terminal strips and the controller. • Segregate I/O wiring by signal type. Bundle wiring with similar electrical characteristics together. Wires with different signal characteristics should be routed into the enclosure by separate paths.

!

5–4

ATTENTION: If the controller is being installed within a potentially hazardous environment (that is, Class I, Division 2), all wiring must comply with the requirements stated in the National Electrical Code 501–4 (b).

Page 68

Chapter 5 Wiring Your Control System

Features of an I/O Module

Below is an example of a combination I/O module. OUTPUT

Color Band

INPUT

0

4

0

4

1

5

1

5

2

2

3

3

I/O Status Indicators

Terminal Block Release Screw

HSCE

Input and Output Terminals Connected to Terminal Block

VAC–VDC OUT 0 OUT 1 OUT 2

Hinged Wiring Terminal Door with Label

OUT 3

Terminal Block (May Be Colorcoded and Removable on Some Modules)

OUT 4 OUT 5 NOT USED NOT USED IN 0 IN 1 IN 2 IN 3 IN 4 IN 5 NOT USED

Terminal Block Release Screw

NOT USED AC COM

Tie Wire

Wires Leading to Output and Input Devices

5–5

Page 69

Chapter 5 Wiring Your Control System

Recommendations for Wiring I/O Devices

The following are general recommendations for wiring I/O devices.

!

ATTENTION: Before you install and wire I/O devices, disconnect power from the controller and any other source to the I/O devices.

Use acceptable wire gauge, The I/O wiring terminals are designed to accept #14 or smaller AWG stranded wires, and two wires per terminal (maximum). Maximum torque 0.9 N–m (8 in–lb). Label wires, Label wiring to I/O devices, power sources, and ground. Use tape, shrink–tubing, or other dependable means for labeling purposes. In addition to labeling, use colored insulation to identify wiring based on signal characteristics. For example, you may use blue for DC I/O wiring and red for AC I/O wiring. Bundle wires, Bundle wiring for each similar I/O device together. If you use ducts, allow at least 5 cm (2 in.) between the ducts and the controller so there is sufficient room to wire the devices. Identify terminals, Terminal cover plates have a write–on area for each terminal. Use this area to identify your I/O devices. Label the Removable Terminal Block (RTB) with appropriate slot, rack (chassis) and module identification if you have not already. Refer to page 5–8 for more information.

!

ATTENTION: Calculate the maximum possible current in each power and common wire. Observe all local electrical codes dictating the maximum current allowable for each wire size. Current above the maximum ratings may cause wiring to overheat, which can cause damage. Capacitors on input modules have a stored charge that can cause a non–lethal shock. Avoid mounting the controller in a position where installation or service personnel would be in danger from startle reaction.

5–6

Page 70

Chapter 5 Wiring Your Control System

Wiring Your I/O Modules

Terminals on the modules have self–lifting pressure plates that accept two #14 AWG wires. Series B 12–point and 16–point and analog modules are equipped with removeable terminal blocks (RTBs) for ease of wiring. For more information on using RTBs, see the next section. LED indicators on the front of each module display the status of each I/O point. The LED indicators turn on when the proper signal to an input terminal is applied or when the processor commands an output to be energized. To locate the I/O module wiring diagrams, contact your Allen–Bradley sales office for the latest product data entitled Discrete Input and Output Modules, Publication Number 1746–2.35. Or, locate the installation instruction sheet that was sent with your I/O module; it also includes I/O wiring diagrams. 1. Install a wire tie to secure your wiring and keep it neat. (If you feed the tie into one hole, it will be routed back out through the other.) OUTPUT INPUT 0 4 1 5 2 3

0 4 1 5 2 3

Tie Wire

Wires Leading to Output and Input Devices

2. Cover any unused slots with card slot fillers, Catalog Number 1746–N2, to keep the chassis free from debris and dust.

5–7

Page 71

Chapter 5 Wiring Your Control System

Using Removable Terminal Blocks (RTBs)

Removable Terminal Blocks (RTBs) are provided on all 12–point and 16–point discrete I/O modules and analog modules. RTBs can only be used with these modules in the 2–slot expansion chassis. RTBs allow for faster and more convenient wiring of the I/O modules. The modules and RTBs are color–coded as follows: Color

Type of I/O Removable Terminal Block

Red

AC inputs/outputs

Blue

DC inputs/outputs

Orange relay outputs

Green specialty modules

Replacement terminal blocks are available if they are lost or damaged. See the replacement part list in chapter 9.

Removing RTBs Below are guidelines for removing the I/O RTBs.

!

ATTENTION: Never install or remove I/O modules or terminal blocks while the SLC is powered.

1. If the I/O module is already installed in the chassis, remove power to the SLC. 2. Unscrew the upper right and lower left terminal block release screws. 3. Grasp the RTB with your thumb and forefinger and pull straight out. 4. Label the RTB with appropriate slot, rack (chassis) and module identification. Terminal Block Release Screw Terminal Block Release Screw Dot indicates terminal number 0 (or top of I/O wiring).

5–8

SLOT______RACK______

• MODULE______

Page 72

Chapter 5 Wiring Your Control System

Installing RTBs Below are guidelines for installing the I/O RTBs. 1. Label the RTB properly. 2. Match the label identification to the correct chassis, slot, and module type.

!

ATTENTION: Inserting a wired RTB on an incorrect module can damage the I/O module circuitry when power is applied.

3. Be sure the color band on the I/O module matches the color of the RTB.

!

ATTENTION: Never install or remove I/O modules or RTBs while the SLC 500 chassis is powered.

4. Remove power from the SLC 500 chassis. 5. Line up terminal block release screws. 6. Press the RTB firmly onto connector contacts. 7. Tighten the RTB release screws.

5–9

Page 73

This page is a scan with no text; see it in the PDF.