Page 25

Chapter

1

Features, Installation, Powerup This chapter introduces you to the Hand–Held Terminal (HHT) hardware. It covers: • HHT features • installing the memory pak, battery, and communication cable • powerup • display format • the keyboard

HHT Features

The Hand–Held Terminal is used to:

• • • • configure the SLC 500 fixed, SLC 5/01, and SLC 5/02 controllers enter/modify a user program download/upload programs monitor, test, and troubleshoot controller operation

You can use the HHT as a standalone device (for remote programming development with 1747–NP1 or NP2 power supply), point–to–point communication (one HHT to one controller), or on a DH–485 network (communicate with up to 31 nodes over a maximum of 4,000 feet or 1219 meters). When equipped with a battery (1747–BA), the HHT retains a user program in memory for storage and later use. Specifications: Environmental conditions Operating temperature Storage temperature Humidity rating Display

0 to +40° C (+32° to +104° F) –20° to +65° C (–4° to +149° F) 5 to 95% (non–condensing) 8 line x 40 character super–twist nematic LCD

Keyboard

30 keys

Operating Power

0.105 Amps (max.) at 24 VDC

Communications

DH–485

Certification

UL listed, CSA approved

Memory Retention with Battery

2 years

Compatibility Dimensions

Fixed, SLC 5/01, SLC 5/02 Not SLC 5/03 201.0 mm H x 193.0 mm W x 50.8 D (7.9 in H x 7.6 in W x 2.0 in D)

1–1

Page 26

Chapter 1 Features, Installation, Powerup

The HHT is menu–driven. The display area accommodates 8 lines by 40 characters. You can display up to five rungs of a user program. When monitoring a program ONLINE, in the Run mode, instructions in a ladder diagram are intensified to indicate “true” status. A zoom feature is included to give immediate access to instruction parameters. Display Area

SLC 500 PROGRAMMING SOFTWARE Rel. 2.03 1747 – PTA1E Allen–Bradley Company Copyright 1990 All Rights Reserved PRESS A FUNCTION KEY OFL SELFTEST TERM PROGMAINT UTILITY F1 F2 F3 F4 F5

F1

Calculator–style, Color–coded Keyboard

Keys operate with motion and tactile response.

1–2

N

F3

F4

U

SPACE

ESC

ZOOM

F2 S

I

PRE/LEN ACC/POS

O

A 7

B 8

C 9

D 4

E 5

F 6

T 1

R 2

M 3

RUNG

# 0

–

.

SHIFT

:

/

F5

ENTER

Page 27

Chapter 1 Features, Installation, Powerup

Installing the Memory Pak, Battery, and Communication Cable

The HHT (with communication cable), memory pak, and battery are supplied separately. Install each as follows: 1. Install the memory pak first. The English version is catalog number 1747–PTA1E.

!

ATTENTION: The memory pak contains CMOS devices. Wear a grounding strap and use proper grounding procedures to guard against damage to the memory pak from electrostatic discharge.

a. To install the memory pak, remove the cover from the back of the HHT.

Slide cover to the left. Lift off cover. Backside of HHT

1–3

Page 28

Chapter 1 Features, Installation, Powerup b. Insert the memory pak in its compartment as indicated in the following figure:

After the memory pak is in the compartment, press down on handle to secure connector in socket.

.. .

.. .. .. .. .. .. .. .. .. .. ..

Backside of HHT

1–4

Page 29

Chapter 1 Features, Installation, Powerup

2. Install the battery, catalog number 1747–BA. The battery compartment is next to the memory pak compartment.

!

ATTENTION: The letter B appears flashing on the prompt line of the HHT display if the battery is not installed correctly or the battery power is low; in addition, each time you power up, the self–diagnostic is interrupted, and the prompt BATTERY TEST FAILED appears. To prevent this from happening, leave the “battery low defeat jumper” inserted in the battery socket. The HHT is functional, but your user program is cleared from memory when you de–energize the HHT. If you do not download the user program to the processor before you de–energize the HHT, your program will be lost.

a. Remove the jumper from the battery socket, then connect the battery as shown in the figure below: Battery Compartment

. . Plug battery connector into socket (red wire up).

Secure battery between clips. Backside of HHT b. Replace the cover.

1–5

Page 30

Chapter 1 Features, Installation, Powerup

3. Locate the communication port on the SLC 500 controller, or peripheral port on the 1747–AIC Link Coupler. The figure below shows where it is located on the different devices:

Processor Module (Modular Controller)

SLC 500 Fixed Controller

Isolated Link Coupler

(Peripheral Port) (Cover Open)

(Communication Port)

The connectors are keyed. Connect one end of the 1747–C10 communication cable to the top of the HHT. The other connector plugs into the communication port on the SLC 500 controllers or the peripheral port on the 1747–AIC.

1747–C10 Cable

SLC Controller (Modular) HHT

If you are using a 1747–NP1 wall mount power supply or a 1747–NP2 desktop power supply, plug the communication cable connector into the socket provided.

1–6

Page 31

Chapter 1 Features, Installation, Powerup

HHT Powerup

After you install the memory pak and battery, and plug in the cable, you can test the operation of the HHT by applying power to the SLC 500 controller or plugging in the external power supply such as the 1747–NP1 or –NP2. When the HHT is energized, it performs a series of diagnostic tests. When the selftest is successfully completed, the following display appears: SLC 500 PROGRAMMING SOFTWARE Rel. 2.03 1747 – PTA1E Allen–Bradley Company Copyright 1990 All Rights Reserved PRESS A FUNCTION KEY SELFTEST TERM PROGMAINT F1

F2

F3

OFL UTILITY F4

F5

If any of the tests fail, the failure is indicated by the appropriate message on the display. For a detailed list of HHT messages and error definitions, refer to appendix A in this manual. After powerup, you may perform any of five diagnostic tests using the selftest function. Press [F1], SELFTEST. The following display appears:

SLC 500 SELFTEST UTILITY

DISPLAY

KEYPAD

RAM

ROM

OFL WTCHDOG

F1

F2

F3

F4

F5

From this menu, you may choose the test you wish to perform. Press [ESC] to return to the previous screen.

1–7

Page 32

Chapter 1 Features, Installation, Powerup

HHT Display Format

The HHT display format consists of the following: • display area • prompt/data entry/error message area • menu tree functions The figure below indicates what appears in these areas. To access this particular screen, press [F3], PROGMAINT.

Display Area Prompt/Data Entry/Error Area Menu tree functions are directly accessible.

File Name: 101 File Name 0 1 2 101

1–8

Indicates that the HHT is offline. When online, the node address and processor mode are shown.

OFL CHG_NAM CRT_FIL EDT_FIL DEL_FIL MEM_MAP > F1

Select menu function keys with [F1] to [F5] keys.

Prog Name: 1492 Type Size(Instr) System * Reserved * Ladder *

F2

F3

F4

F5

When the > symbol is present, pressing [ENTER] toggles additional menu functions.

Page 33

Chapter 1 Features, Installation, Powerup

The Keyboard F1 N

F3

F4

F5

U

SPACE

ESC

F2 S

I

PRE/LEN ACC/POS

O

This section is intended only as a brief preview of keyboard operation. Starting in chapter 6, you will become familiar with the keyboard as you are guided through various programming procedures.

A 7

B 8

C 9

Menu Function Keys (F1, F2, F3, F4, F5)

D 4

E 5

F 6

T 1

R 2

M 3

RUNG

# 0

–

.

SHIFT

The top row of purple keys, F1 through F5, are menu function keys. They select the menu functions shown on the bottom line of the display. Note that when the > symbol is present, the [ENTER] key will toggle additional menu functions (if any) at a particular menu level. The [ESC] key exits the display to the previous menu level.

:

/

ZOOM

ENTER

Data Entry Keys These blue keys (A 7, B 8, C 9...) include numbers, letters, and symbols used for addresses, password, file numbers, and other data. The data you enter always appears on the prompt/data entry/error message area of the display. To obtain the upper function of a key, press and release the [SHIFT] key, then press the desired key. If you make an error while entering data, press [ESC] and re–enter the data, or use the cursor (arrow) keys and/or the [SPACE] key to locate and correct the error. To complete a data entry, press [ENTER]. You can also use the [ESC] key to exit the data entry and return to the previous menu level.

Auto Shift When you enter an instruction address, the HHT automatically goes to SHIFT mode to enable you to enter the upper function of a key without first pressing the [SHIFT] key. This mode is indicated by a small arrow in the bottom right hand corner of the display. ] [

ZOOM on XIC NAME: BIT ADDR:

2.6.0.0.*

EXAMINE IF CLOSED

Indicates that the HHT is in SHIFT mode (e.g., to enter the letter “I” you do not have to first press SHIFT).

ENTER BIT ADDR: F1

F2

F3

F4

F5

The data you enter appears here, at the cursor location.

1–9

Page 34

Chapter 1 Features, Installation, Powerup

Cursor Keys

, , ,

Use the four arrow keys to: • change or modify instruction addresses • locate and correct data entry errors (either type over or use the [SPACE] key) • move the cursor left, right, up, and down in a ladder program (rungs not shown on the HHT display automatically scroll into view as you move the cursor up [or down] in the program) • scroll through controller and I/O configuration selections • scroll through program file directories • scroll through active node addresses • scroll through the elements and bits of individual data files The keys move the cursor left and right between the items of the address.

ZOOM on OTE –( )– NAME: OUTPUT ENERGIZE BIT ADDR:O0:2.0/7

2.1.1.0.2

ENTER BIT ADDR: O0:2.0/7 EDT_DAT F1

F2

XIC:I1:2.0/2 ] [ ] [

The keys move the cursor left, right, up, and down in a ladder diagram.

NO FORCE

INS RNG MOD RNG SEARCH F1

1–10

F3

F2

F3

ACCEPT F4

F5

2.4.0.0.1 ( ) ( ) ( ) ( ) ( ) OFL DEL RNG UND RNG > F4

F5

Page 35

Chapter 1 Features, Installation, Powerup

The keys scroll through the I/O module choices in this display. Similarly, these keys scroll through rack and CPU choices in the appropriate displays.

Rack 1 = 1746–A4 Rack 2 = NONE Rack 3 = NONE Slot 0 = 1747–L511 Slot 1 = 1746–IA4 Slot 1 = 1746–IA4 F1

The keys scroll through user program files.

File Name: File Name 0 1 2

4–INPUT 100/120 VAC 4–INPUT 100/120 VAC F3

F4

F5

Prog Name:2A Type Size(Instr) System 217 Reserved 0 Ladder 30

F2

F3

F4

F5

Node Addr. Device Max Addr./Owner 0 APS (31) 1 TERMINAL (31) *** 2 5/02 (31) *** 3 500–20 (31) Node Addr: 0 Baud Rate: 19200 OFL DIAGNSTC ATTACH NODE CFG OWNER F1

The keys move the cursor left, right, up and down in a data file display.

CPU–1K USER MEMORY

OFL CHG NAM CRT FIL EDT FIL DEL FIL MEM MAP > F1

The keys scroll through active node addresses.

F2

4–SLOT RACK

F2

F3

F4

F5

Address 15 data 0 B3:0 0010 0011 0100 1111 B3:1 1000 0010 0000 0000 B3:2 0000 0000 1110 0000 B3:3 0000 0000 0100 0000 B3:4 0101 1101 0100 1000 B3/31 = 1 RUN ADDRESS NEXT FL PREV FL NEXT PG PREV PG F1

F2

F3

F4

F5

1–11

Page 36

Chapter 1 Features, Installation, Powerup

ZOOM and RUNG Keys The [ZOOM] key brings up a display that shows the parameters of an instruction. The [RUNG] key moves the cursor to a particular rung. Using this key saves time when you have a long ladder diagram. When you press [RUNG], you are prompted for the rung number that you want to edit or monitor. Enter the rung number and press [ENTER], the cursor moves to the selected rung and the rung appears at the top of the display. TON:T4:2 ] [ ] [ ] [ ] [ ] [ INS RNG MOD RNG SEARCH F1

F2

F3

2.2.0.0.2 (TON) ( ) ( ) ( ) ( ) OFL DEL RNG UND RNG > F4

F5

ZOOM on TON –(TON)– 2.2.0.0.2 NAME: TIMER ON DELAY TIMER: T4:2 TIME BASE .01 SEC PRESET: 20 ACCUM: 0

EDT_DAT F1

F2

F3

TON:T4:2 ] [ ] [ ] [ ] [ ] [

Press [RUNG][6][ENTER]. The cursor moves from the Timer rung to the left power rail of rung 6.

1–12

INS RNG MOD RNG SEARCH F1

F2

F3

F4

F5

2.6.0.0.* (TON) ( ) ( ) ( ) ( ) OFL DEL RNG UND RNG > F4

F5

Press the [ZOOM] key with the cursor on an instruction. The Zoom display shows the instruction parameters. Exit the Zoom display by pressing [ESC] or [ZOOM].