1747-SDN DeviceNet Scanner Module Installation Instructions, pages 1 to 10

Pages 1 to 10 of 20: 1747-IN058F-EN-P 1747-SDN DeviceNet Scanner Module Installation Instructions; Back Cover

The original document is the PDF (562 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1747-SDN

Page 1

Installation Instructions

1747-SDN DeviceNet Scanner Module

Catalog Number 1747-SDN, Series D

Topic

Page

Important User Information

2

Safety Guidelines

2

About the 1747-SDN, Series D DeviceNet Scanner Module

4

Before You Begin

7

Install DeviceNet Scanner Module

9

Interpret the LED Indicators

12

Numeric Codes and Descriptions

14

Specifications

16

Additional Resources

18

Publication 1747-IN058F-EN-P - December 2010

Page 2

2

1747-SDN DeviceNet Scanner Module

Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING

IMPORTANT ATTENTION

Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. Identifies information that is critical for successful application and understanding of the product. Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you to identify a hazard, avoid a hazard, and recognize the consequences.

SHOCK HAZARD

Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.

BURN HAZARD

Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.

Safety Guidelines Publication 1747-IN058F-EN-P - December 2010

Page 3

1747-SDN DeviceNet Scanner Module

3

Follow these guidelines for environment and enclosure information for this equipment. ATTENTION

This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance. This equipment is supplied as open type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. In addition to this publication, see: • Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1, for additional installation requirements. • NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.

Follow these guidelines when you handle this equipment. ATTENTION

This equipment is sensitive to electrostatic discharge that can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment. • Touch a grounded object to discharge potential static. • Wear an approved grounding wrist strap. • Do not touch connectors or pins on component boards. • Do not touch circuit components inside the equipment. • Use a static-safe workstation if available. • Store the equipment in appropriate static-safe packaging when not in use.

Publication 1747-IN058F-EN-P - December 2010

Page 4

4

1747-SDN DeviceNet Scanner Module

ATTENTION

To comply with UL restrictions, this equipment must be powered from a source compliant with the following: Class 2 or Limited Voltage/Current.

About the 1747-SDN, Series D DeviceNet Scanner Module The 1747-SDN, Series D module includes these firmware enhancements. • ADR user memory space increased from 64K to 256K • Support added for Online Scanlist Changes in Run Mode. This feature allows scanlist changes to be downloaded to the scanner when the both the SLC processor and the scanner are in RUN mode. • Scanner CCV attribute supported, provides optimization for RSNetWorx. Refer to the SLC 500 DeviceNet Scanner Module User Manual, publication 1747-UM655, for additional information on these new enhancements. The 1747-SDN Series D module includes all features provided in the Series C module. The module has the following software and hardware features.

Software Features The module has these software features.

Slave Mode Slave mode allows processor-to-processor communication and enables the scanner to perform as a slave device to another master on the network. When the scanner module is in slave mode, it exchanges data with only one master. You control what information is exchanged through scan list configuration and associated mapping functions of RSNetWorx for DeviceNet software.

Publication 1747-IN058F-EN-P - December 2010

Page 5

1747-SDN DeviceNet Scanner Module

5

This feature has the following variations. Module Mode

Description

Null

Contains an empty or disabled scan list (default)

Master

Serves as a master to one or more slaves but is not simultaneously serving as a slave to another master

Slave

Serves as a slave to another master

Dual

Serves as both a master to one or more slaves and as a slave to another master simultaneously

Poll A poll message is a point-to-point transfer of data (0…255 bytes) sent by the scanner module that solicits a response from a single device. The device responds with its input data (0…255 bytes).

Strobe A strobe message is a multicast transfer of data (64 bits in length) sent by the scanner module that solicits a response from each strobed slave device. There is one bit for each of the possible 64 node addresses. The devices respond with their data, which can be as much as 8 bytes.

Change of State Change of state enables the scanner module to perform a scan: • whenever a network data change occurs. • at a user-configurable heartbeat rate. Because data is only sent on an as-needed basis, this feature increases system performance by reducing network traffic.

Cyclic I/O Cyclic I/O allows you to instruct the scanner module to perform a scan at a specific send rate. Because data is only sent at a periodic rate, this feature increases system performance by reducing network traffic.

Publication 1747-IN058F-EN-P - December 2010

Page 6

6

1747-SDN DeviceNet Scanner Module

Pass-through The SLC 500 pass-through feature allows communication with the DeviceNet network from another network. This feature can be used to adjust and fine tune the nodes on your network. The pass-through feature is not intended to replace a 1770-KFD, 1784-PCD, 1784-PCID, or 1784-PCIDS connection to the network. To use the pass-through feature you must meet the following hardware, software and firmware requirements.

Pass-through Requirements SLC 500 Processor

1747-SDN Firmware

RSLinx Software

M0 and M1 Files

SLC 5/03 or later

4.015…5.001

2.10 or later

Configured for 361 words

SLC 5/03 or later

6.001 or later

2.31 or later

Configured for 395 words

U2DN module The pass-through feature is not intended to replace a 1784-U2DN, 1770-KFD, 1784-PCD, 1784-PCID, or 1784-PCIDS connection to the network.

Publication 1747-IN058F-EN-P - December 2010

Page 7

1747-SDN DeviceNet Scanner Module

7

Hardware Features Use this illustration to identify the external features of the scanner module. DeviceNet STATUS Module Status indicator indicates module status

MODULE NET

Node address and status displays numeric codes and indicates scanner node address or error

ADDRESS/ERROR

Network Status indicator indicates status of DeviceNet channel communication link

Access door

Wiring color codes

10-pin linear plug inserted into DeviceNet port

Before You Begin Before you install your module you need the following items. • Personal computer with Microsoft Windows 2000 or later operating system • RSNetWorx for DeviceNet software, version 2.22 or later • RSLogix 500 software • SLC 1746 chassis with SLC 5/02, SLC 5/03, SLC 5/04, or SLC 5/05 processor

Publication 1747-IN058F-EN-P - December 2010

Page 8

8

1747-SDN DeviceNet Scanner Module

For network communication, you have three options. • Use the pass-through feature to communicate with the DeviceNet network from another network. This method is intended for fine tuning and adjustment of network devices. • Use a 1770-KFD RS-232 DeviceNet adapter or 1784-PCD, 1784-PCID, or 1784-PCIDS DeviceNet PC card. This method is necessary for a complete network configuration and real time monitoring of your network devices. • Use a 1784-U2DN USB adapter, a 1770-KFD RS-232 DeviceNet adapter or 1784-PCD, 1784-PCID, or 1784-PCIDS DeviceNet PC card. This method is necessary for a complete network configuration and real time monitoring of your network devices. Before you install your module you must know how to: • program and operate an Allen-Bradley SLC 500 programmable controller. • install and configure the devices on your DeviceNet network.

Electronic Data Sheet Requirement This release of the scanner module requires the latest EDS file for RSLinx Classic and RSNetWorx for DeviceNet software. If the software displays the device as an Unrecognized Device, the EDS file must be installed. You can download the latest EDS file online at: http://www.ab.com/networks/eds For FRN 8.002 and later, you can upload the embedded EDS file from the scanner module itself. 1. Open RSLinx Classic or RSNetWorx for DeviceNet software and right click on the Unrecognized Device. 2. Select Upload EDS file from device for RSLinx Classic software or Register Device for RSNetWorx for DeviceNet software. 3. Follow the instructions in the EDS wizard to complete the installation.

Perform a ControlFLASH Update If you want to upgrade the scanner module to a newer firmware release, you must perform a ControlFLASH update. To get the kit, contact Rockwell Automation Technical Support at

Publication 1747-IN058F-EN-P - December 2010

Page 9

1747-SDN DeviceNet Scanner Module

9

440.646.5800. To install the kit, refer to the ControlFLASH Firmware Upgrade Kit User Manual, publication 1756-QS105. IMPORTANT

You can update Series A and B scanner modules up to FRN 7.006. Series C scanner modules support only FRN 8.001 to 8.006. Series D scanner modules support FRN 9.001 and later.

Confirm Processor and Adapter Compatibility Make sure that your processor and adapter are compatible. You can use the 1747-SDN scanner module in any slot in an I/O chassis except for the leftmost, which is reserved for the SLC 500 processor. IMPORTANT

You cannot use the scanner module in a remote I/O chassis with a 1747-ASB adapter module. The adapter module does not support M-file transfer.

Install DeviceNet Scanner Module Follow these steps to install the module. 1. Turn off the chassis power supply. WARNING

If you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

2. Select a slot for the module in the chassis. You may use any slot except the leftmost slot, which is reserved for the SLC 500 processor.

Publication 1747-IN058F-EN-P - December 2010

Page 10

10

1747-SDN DeviceNet Scanner Module

3. Insert the module into the slot you have selected. 4. Apply firm, even pressure to seat the module in the I/O chassis backplane connectors.

Connect the Module to the DeviceNet Network ATTENTION

To comply with the CE Low Voltage Directive (LVD), DeviceNet must be powered from a source compliant with the following: • Safety Extra Low Voltage (SELV) • Protected Extra Low Voltage (PELV). To comply with UL restrictions, DeviceNet must be powered from a source compliant with the following: • Class 2 • Limited Voltage/Current.

Follow these steps to connect the module to the DeviceNet network. 1. Turn off the network power supply.

Publication 1747-IN058F-EN-P - December 2010