Page 11
1747-SDN DeviceNet Scanner Module
WARNING
11
If you connect or disconnect the communications cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.
2. Connect the DeviceNet drop line to the 10-pin linear plug by matching the wire insulation colors to the colors shown on the label. +24V Red Can_H White Drain/Shield Can_L Blue +24V Return Black
10-pin linear plug
Red White Shield Blue Black
Front of Module
3. Locate the DeviceNet port connector on the front of the module. 4. Insert the 10-pin linear plug into the DeviceNet port connector.
10-pin Linear plug
DeviceNet port connector
DeviceNet drop line
You have installed and wired your module. To operate the module you must apply power and then configure and program the SLC processor to communicate with it.
Publication 1747-IN058F-EN-P - December 2010
Page 12
12
1747-SDN DeviceNet Scanner Module
Apply Chassis Power When you apply chassis power, the module numeric indicators cycle through the following displays. DeviceNet STATUS MODULE NET
Module Numeric Indicators
ADDRESS/ERROR
• Seven-segment lamp test (88) • Firmware major revision (01…7F hexadecimal) • Firmware minor revision (01…FF hexadecimal) • Communication rate (indicates 00 for the default of 125, 01 for 250, or 02 for 500 Kbps) • Node address (00…63 with 63 as the default) Use the RSNetWorx for DeviceNet software to change the communication rate and node address. Refer to the Numeric Code Display Summary table on page 14 for a complete listing of numeric displays.
Interpret the LED Indicators The bicolor (green/red) module status indicator (MODULE) on the front of your module displays module status. It indicates whether the module has power and is functioning properly.
Module Status LED Indicator Indicator Color
Description
Corrective Action
Off
There is no power applied to the module.
Verify power connections and apply power.
Green
The module is operating normally.
No action required.
Flashing Green
The module is not configured.
Configure the module.
Flashing Red
There is an invalid configuration.
Check configuration setup.
Red
The module has an unrecoverable fault.
Replace the module.
Publication 1747-IN058F-EN-P - December 2010
Page 13
1747-SDN DeviceNet Scanner Module
13
The DeviceNet channel has a bicolor (green/red) network status indicator (NET). The following table provides troubleshooting information about the DeviceNet channel communication link.
DeviceNet Channel Communication Indicator Color
Description
Device Operation
Corrective Action
Off
The channel is disabled for DeviceNet communication.
The device has no power or the channel is disabled for communication due to bus off condition, loss of network power, or has been intentionally disabled.
Power-up the module, provide network power to the channel, and be sure the channel is enabled in both the module configuration table and the module command word.
Green
All slave devices in the scan list table are communicating normally with the module.
Normal operation.
None.
Flashing Green
The channel is enabled but no communication is occurring.
The two-digit numeric display for the channel indicates an error code that provides more information about the condition of the channel.
Configure the scan list table for the channel to add devices.
Flashing Red
At least one of the slave devices in the module’s scan list table has failed to communicate with the module.
The two-digit numeric display for the channel displays an error code that provides more information about the condition of the channel.
Examine the failed device and the scan list table for accuracy.
Red
The module may be defective.
The communications channel has failed. The two-digit numeric display for the channel displays an error code that provides more information about the condition of the channel.
Reset module. If failures persist, replace module.
Publication 1747-IN058F-EN-P - December 2010
Page 14
14
1747-SDN DeviceNet Scanner Module
Numeric Codes and Descriptions Your module uses numeric displays to indicate diagnostic information about the status of your module. The display flashes at 1-second intervals. The following table summarizes the meanings of the numeric codes. Numeric Code
Description
Corrective Action
0…63
Normal operation. The numeric display indicates the 1747-SDN node address on the DeviceNet network.
None.
70
Module failed Duplicate Node Address check.
Change the module channel address to another available one. The node address you selected is already in use on that channel.
71
Illegal data in scan list table (node number alternately flashes).
Reconfigure the scan list table and remove any illegal data.
72
Slave device stopped communicating (node number alternately flashes).
Inspect the field devices and verify connections.
73
Identity information for the device does not match electronic key in scan list table entry.
Verify that the correct device is at this node number. Make sure that the device at the scrolling node address matches the desired electronic key (vendor, product code, product type).
74
Data overrun on port detected.
Modify your configuration and check for invalid data. Check network communication traffic.
75
No traffic from other modules detected on the network.
Check the network configuration. Scanlist may be empty.
76
No direct network traffic for module detected.
None. The module detects other network communication.
77
Data size expected by the device does not match scan list entry.
Reconfigure your module for the correct transmit and receive data sizes.
78
Slave device in scan list table does not exist.
Add the device to the network, or delete the scan list entry for that device.
79
Module has failed to transmit a message.
Make sure that your module is connected to a valid network. Check for disconnected cables.
80
Module is in Idle mode.
Put controller in Run mode. Enable Run bit in module command register.
81
Module is in Fault mode.
Check Module Command Register for fault bit set.
Publication 1747-IN058F-EN-P - December 2010
Page 15
1747-SDN DeviceNet Scanner Module
15
Numeric Code
Description
Corrective Action
82
Error detected in sequence of fragmented I/O messages from device.
Check scan list table entry for slave device to make sure that input and output data lengths are correct. Check slave device configuration.
83
Slave device is returning error responses when module attempts to communicate with it.
Check accuracy of scan list table entry. Check slave device configuration. Slave device may be in another master’s scan list. Reboot slave device.
84
Module is initializing the DeviceNet network.
None. This code clears itself once module attempts to initialize all slave devices on the network.
85
Data size was incorrect for this device at runtime.
Slave device is transmitting incorrect length data. Verify device is not configured for variable poll connection size. Try replacing the device.
86
Device is producing zero length data (idle state) while module is in Run mode.
Check device configuration and slave node status.
87
The primary owner has not allocated the slave.
Put the primary owner online.
88
The connection choices (polled, strobed) between the primary connection and the shared input only connection do not match.
Reconfigure the shared input-only connection choices to be the same as, or a subset of, the choices for the primary connection.
89
Slave device initialization using Auto Device Replacement parameters failed.
Put the slave device into configurable mode. If the slave is configured offline, check its EDS file. Check to see if the slave device has been replaced with an incompatible device.
90
User has disabled communication port.
Check Module Command Register for DISABLE bit set.
91
Bus-off condition detected on comm port. Module is detecting communication errors.
Check DeviceNet connections and physical media integrity. Check system for failed slave devices or other possible sources of network interference.
92
No network power detected on communication port.
Provide network power. Make sure that module drop cable is providing network power to module comm port.
95
Application FLASH update in progress.
None. Do not disconnect the module while application FLASH is in progress. You will lose existing data in the module memory.
97
Module operation halted by user command.
Check Module Command Register for HALT bit set.
Publication 1747-IN058F-EN-P - December 2010
Page 16
16
1747-SDN DeviceNet Scanner Module
Numeric Code
Description
Corrective Action
98
Unrecoverable firmware failure.
Service or replace your module.
99
Unrecoverable hardware failure.
Service or replace your module.
E2
RAM Test Failure
Service or replace your module.
E4
Lost power during FLASH upgrade
Service or replace your module.
E5
No application code
Service or replace your module.
E9
Module memory has been flushed for factory default settings.
Cycle module power to recover.
Specifications SLC DeviceNet Scanner, 1747-SDN Attribute
Value
Module location
SLC 5/02 or later chassis
Module defaults
Node Address – 63 Baud Rate – 125 Kbps
Power consumption - Backplane current - DeviceNet
5V DC, 500 mA 24V DC, 90 mA Class 2
Isolation voltage
30V (continuous), Basic Insulation Type Tested at 500V AC for 60 s, DeviceNet to backplane
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 0…60 oC (32…140 oF)
Temperature, non-operating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bc, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): -40…85 oC (-40…185 oF)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat): 5…95% non-condensing
Vibration
IEC60068-2-6 (Test Fc, Operating): 2 g @10…500 Hz
Shock
IEC60068-2-27:1987, Test Ea (Unpackaged shock, ES#002) Operating, 30 g Non-operating, 50 g
Publication 1747-IN058F-EN-P - December 2010
Page 17
1747-SDN DeviceNet Scanner Module
17
SLC DeviceNet Scanner, 1747-SDN Attribute
Value
Emissions
CISPR 11: Group 1, Class A (with appropriate enclosure)
ESD immunity
IEC 61000-4-2: 6 kV contact discharges 8 kV air discharges
Radiated RF immunity
IEC 61000-4-3: 10 V/m with 1 kHz sine-wave 80% AM from 80…2000 Mhz
EFT/B immunity
IEC 61000-4-4: +2 kV at 5 kHz on communication ports
Surge transient immunity
IEC 61000-4-5: ±2 kV line-earth(CM) on communications ports
Conducted RF immunity
IEC 61000-4-6: 10 Vrms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Magnetic field immunity
IEC 61000-4-8 30A/m long duration at 50 Hz
Enclosure type rating
None (open style)
Wiring - Size - Category(1)
Refer to DeviceNet Media Design Installation Guide, publication DNET-UM072 2, on communication ports
10-pin Linear plug - Torque - Catalog number
0.6…0.8 Nm (5…7 lb-in) 1787-PLUG10R
North American temperature code
T5
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Publication 1747-IN058F-EN-P - December 2010
Page 18
18
1747-SDN DeviceNet Scanner Module
Certifications - 1747-SDN Certification (when product is
Value marked)(1) c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E113724. UL Listed for Class I, Division 2 Group A, B, C, D Hazardous Locations, certified for US and Canada. See UL File E10314.
CE
European Union 89/336/EEC EMC Directive, compliant with: EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
ODVA
ODVA conformance tested to ODVA DeviceNet specifications
(1)
See the Product Certification link at http://www.ab.com for Declaration of Conformity, Certificates, and other certification details.
Additional Resources Resource
Description
SLC 500 DeviceNet Scanner Module User Manual, publication 1747-UM655
Provides application examples for the DeviceNet scanner module.
ControlFlash Firmware Upgrade Kit User Manual, publication 1756-QS105
Provides instructions on using ControlFlash to upgrade the firmware.
Getting Results with RSLogix 500, publication LG500-GR002
Provides information on RSLogix 500 software.
Getting Results with RSLinx, publication LINX-GR001
Provides information on RSLinx software.
DeviceNet Media Design and Installation Guide, DNET-UM072
Provides information on using DeviceNet communication network.
Getting Results with RSNetWorx for DeviceNet, publication DNET-GR001
Provides information on using RSNetWorx for DeviceNet software.
You can view or download publications at http://literature.rockwellautomation.com. To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative.
Publication 1747-IN058F-EN-P - December 2010
Page 19
1747-SDN DeviceNet Scanner Module
19
North American Hazardous Location Approval The following information applies when operating this equipment in hazardous locations:
Informations sur l’utilisation de cet équipement en environnements dangereux:
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
WARNING
EXPLOSION HAZARD •
Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
•
AVERTISSEMENT
RISQUE D’EXPLOSION •
Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement.
Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
•
Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
•
Substitution of any component may impair suitability for Class I, Division 2.
•
•
If this product contains batteries, they must only be changed in an area known to be nonhazardous.
La substitution de tout composant peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
•
S'assurer que l'environnement est classé non dangereux avant de changer les piles.
Publication 1747-IN058F-EN-P - December 2010
Page 20
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a . knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com.
Installation Assistance If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running. United States
1.440.646.3434 Monday – Friday, 8 a.m. – 5 p.m. EST
Outside United States
Please contact your local Rockwell Automation representative for any technical support issues.
New Product Satisfaction Return Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures. United States
Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor in order to complete the return process.
Outside United States
Please contact your local Rockwell Automation representative for the return procedure.