Manual · Allen-Bradley
1747-SDN DeviceNet Scanner Module Installation Instructions
Manual20 pagesPDF 562 KB
Installation instructions for the Allen-Bradley 1747-SDN Series D DeviceNet scanner module for SLC 500 chassis.
Covers · 1 model
The models it covers
Summary
What is in it
Rockwell Automation installation instructions for the Allen-Bradley 1747-SDN, Series D DeviceNet Scanner Module for SLC 500 controllers. It describes the module's firmware enhancements and software features (slave mode, poll, strobe, change of state, cyclic I/O, pass-through), what you need before you begin, EDS files and ControlFLASH updates, installing the module and wiring the 10-pin DeviceNet plug, reading the LED indicators and numeric codes, and the specifications.
Its parts
- Important User Information
- Safety Guidelines
- About the 1747-SDN, Series D DeviceNet Scanner Module
- Before You Begin
- Install DeviceNet Scanner Module
- Interpret the LED Indicators
- Numeric Codes and Descriptions
- Specifications
- Additional Resources
- North American Hazardous Location Approval
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Installation instructions (publication 1747-IN058F-EN-P, December 2010) for the Allen-Bradley 1747-SDN, Series D DeviceNet Scanner Module for SLC 500 chassis. They describe its features and modes, what is needed before installing, installing and wiring the module, the status indicators and numeric codes, and the specifications.
- What it is
- DeviceNet scanner module (Series D) for the SLC 500; null, master, slave or dual (master and slave) mode p. 1, 5
- Processors
- SLC 1746 chassis with SLC 5/02, SLC 5/03, SLC 5/04 or SLC 5/05 processor p. 7
- Slot
- Any slot except the leftmost; not in a remote I/O chassis with a 1747-ASB adapter p. 9
- Defaults
- Node address 63, 125 Kbps p. 16
- Data rates
- 125, 250 or 500 Kbps; node address 00 to 63, set with RSNetWorx for DeviceNet p. 12
- Power consumption
- 5V DC, 500 mA and 24V DC, 90 mA Class 2 p. 16
- Network plug
- 10-pin linear plug 1787-PLUG10R, 0.6 to 0.8 Nm (5 to 7 lb-in) p. 17
- Drop line colors
- +24V red, Can_H white, drain/shield, Can_L blue, +24V return black p. 11
- Messaging
- Poll (0 to 255 bytes), strobe (64 bits, replies up to 8 bytes), change of state and cyclic I/O p. 5
- Firmware
- Series D: FRN 9.001 and later; Series C: FRN 8.001 to 8.006; Series A and B: up to FRN 7.006 p. 9
- Series D additions
- ADR user memory raised from 64K to 256K, online scanlist changes in Run mode, scanner CCV attribute p. 4
- Software
- RSNetWorx for DeviceNet 2.22 or later and RSLogix 500, on Microsoft Windows 2000 or later p. 7
- PC interfaces
- 1784-U2DN USB adapter, 1770-KFD RS-232 adapter, or 1784-PCD, 1784-PCID or 1784-PCIDS PC card p. 8
- Operating temperature
- 0 to 60 °C (32 to 140 °F); humidity 5 to 95% non-condensing p. 16
What this manual walks you through
- Installing the module in the SLC chassis p. 9, 10
- Wiring the DeviceNet drop line to the 10-pin linear plug p. 11
- Reading the displays at power-up p. 12
- Interpreting the MODULE and NET status indicators p. 12, 13
- Looking up numeric error codes and their corrective actions p. 14, 15, 16
- Installing the EDS file in RSLinx Classic or RSNetWorx p. 8
- Updating firmware with ControlFLASH p. 8, 9
- Using the SLC 500 pass-through feature p. 6
Good to know
- Inserting or removing the module with backplane power on can cause an electrical arc. p. 9
- Do not disconnect the module during an application FLASH update (code 95), or existing data in its memory is lost. p. 15
- Pass-through is meant for fine tuning and is not a replacement for a 1784-U2DN, 1770-KFD or PC card connection. p. 6
- The module is sensitive to electrostatic discharge. p. 3
Questions this manual answers
What does error code 72 mean on a 1747-SDN?
A slave device stopped communicating (its node number flashes alternately); inspect the field devices and verify connections. p. 14
What does code 91 mean on the 1747-SDN display?
A bus-off condition on the comm port; check DeviceNet connections, media, failed slaves and sources of interference. p. 15
What does code 92 mean on the 1747-SDN?
No network power on the communication port; provide network power through the module drop cable. p. 15
What are the 1747-SDN default node address and baud rate?
Node address 63 and 125 Kbps. p. 16
What does a flashing red MODULE light on the 1747-SDN mean?
There is an invalid configuration; check the configuration setup. Solid red means an unrecoverable fault and the module should be replaced. p. 12
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 2 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file