Page 1 of 1747-SDN DeviceNet Scanner Module Installation Instructions

Manual · Allen-Bradley

1747-SDN DeviceNet Scanner Module Installation Instructions

Manual20 pagesPDF 562 KB

Installation instructions for the Allen-Bradley 1747-SDN Series D DeviceNet scanner module for SLC 500 chassis.

Download the PDF562 KB

Covers · 1 model

The models it covers

Summary

What is in it

Rockwell Automation installation instructions for the Allen-Bradley 1747-SDN, Series D DeviceNet Scanner Module for SLC 500 controllers. It describes the module's firmware enhancements and software features (slave mode, poll, strobe, change of state, cyclic I/O, pass-through), what you need before you begin, EDS files and ControlFLASH updates, installing the module and wiring the 10-pin DeviceNet plug, reading the LED indicators and numeric codes, and the specifications.

Its parts

  1. Important User Information
  2. Safety Guidelines
  3. About the 1747-SDN, Series D DeviceNet Scanner Module
  4. Before You Begin
  5. Install DeviceNet Scanner Module
  6. Interpret the LED Indicators
  7. Numeric Codes and Descriptions
  8. Specifications
  9. Additional Resources
  10. North American Hazardous Location Approval

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

Installation instructions (publication 1747-IN058F-EN-P, December 2010) for the Allen-Bradley 1747-SDN, Series D DeviceNet Scanner Module for SLC 500 chassis. They describe its features and modes, what is needed before installing, installing and wiring the module, the status indicators and numeric codes, and the specifications.

What it is
DeviceNet scanner module (Series D) for the SLC 500; null, master, slave or dual (master and slave) mode p. 1, 5
Processors
SLC 1746 chassis with SLC 5/02, SLC 5/03, SLC 5/04 or SLC 5/05 processor p. 7
Slot
Any slot except the leftmost; not in a remote I/O chassis with a 1747-ASB adapter p. 9
Defaults
Node address 63, 125 Kbps p. 16
Data rates
125, 250 or 500 Kbps; node address 00 to 63, set with RSNetWorx for DeviceNet p. 12
Power consumption
5V DC, 500 mA and 24V DC, 90 mA Class 2 p. 16
Network plug
10-pin linear plug 1787-PLUG10R, 0.6 to 0.8 Nm (5 to 7 lb-in) p. 17
Drop line colors
+24V red, Can_H white, drain/shield, Can_L blue, +24V return black p. 11
Messaging
Poll (0 to 255 bytes), strobe (64 bits, replies up to 8 bytes), change of state and cyclic I/O p. 5
Firmware
Series D: FRN 9.001 and later; Series C: FRN 8.001 to 8.006; Series A and B: up to FRN 7.006 p. 9
Series D additions
ADR user memory raised from 64K to 256K, online scanlist changes in Run mode, scanner CCV attribute p. 4
Software
RSNetWorx for DeviceNet 2.22 or later and RSLogix 500, on Microsoft Windows 2000 or later p. 7
PC interfaces
1784-U2DN USB adapter, 1770-KFD RS-232 adapter, or 1784-PCD, 1784-PCID or 1784-PCIDS PC card p. 8
Operating temperature
0 to 60 °C (32 to 140 °F); humidity 5 to 95% non-condensing p. 16

What this manual walks you through

  • Installing the module in the SLC chassis p. 9, 10
  • Wiring the DeviceNet drop line to the 10-pin linear plug p. 11
  • Reading the displays at power-up p. 12
  • Interpreting the MODULE and NET status indicators p. 12, 13
  • Looking up numeric error codes and their corrective actions p. 14, 15, 16
  • Installing the EDS file in RSLinx Classic or RSNetWorx p. 8
  • Updating firmware with ControlFLASH p. 8, 9
  • Using the SLC 500 pass-through feature p. 6

Good to know

  • Inserting or removing the module with backplane power on can cause an electrical arc. p. 9
  • Do not disconnect the module during an application FLASH update (code 95), or existing data in its memory is lost. p. 15
  • Pass-through is meant for fine tuning and is not a replacement for a 1784-U2DN, 1770-KFD or PC card connection. p. 6
  • The module is sensitive to electrostatic discharge. p. 3

Questions this manual answers

What does error code 72 mean on a 1747-SDN?

A slave device stopped communicating (its node number flashes alternately); inspect the field devices and verify connections. p. 14

What does code 91 mean on the 1747-SDN display?

A bus-off condition on the comm port; check DeviceNet connections, media, failed slaves and sources of interference. p. 15

What does code 92 mean on the 1747-SDN?

No network power on the communication port; provide network power through the module drop cable. p. 15

What are the 1747-SDN default node address and baud rate?

Node address 63 and 125 Kbps. p. 16

What does a flashing red MODULE light on the 1747-SDN mean?

There is an invalid configuration; check the configuration setup. Solid red means an unrecoverable fault and the module should be replaced. p. 12

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. 1747-IN058F-EN-P 1747-SDN DeviceNet Scanner Module Installation Instructions1
    1. Important User Information2
    2. Safety Guidelines2
    3. About the 1747-SDN, Series D DeviceNet Scanner Module4
    4. Before You Begin7
    5. Install DeviceNet Scanner Module9
    6. Interpret the LED Indicators12
    7. Numeric Codes and Descriptions14
    8. Specifications16
    9. Additional Resources18
    10. North American Hazardous Location Approval19
  2. Back Cover20

From the PDF’s own bookmarks.

The whole text · 2 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20

The file

Revision and size

RevisionPublication 1747-IN058F-EN-P, December 2010
PublisherRockwell Automation
Pages20
PDF562 KB
TextText from the PDF itself.

The first pages · 3 of 20

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 20
Page 2
Page 2of 20
Page 3
Page 3of 20

More documents · 1

For the same models