1747-SDN DeviceNet Scanner Module User Manual: 5 - Communicating with the DeviceNet Network from Another Network, pages 63 to 70

Pages 63 to 70 of 160, from 1747-SDN DeviceNet Scanner Module User Manual

The original document is the PDF (3.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1747-SDN

Page 63

Chapter

5

Communicating with the DeviceNet Network from Another Network

What This Chapter Contains This chapter describes how to communicate with the DeviceNet network from another network, by using the SLC 500 pass-through feature. This feature can be used to adjust and fine tune the nodes on your network. Examples are provided for communicating from an Ethernet network and a Data Highway Plus network.

ATTENTION

The pass-through feature is not intended to replace a 1770-KFD, 1770-PCD, 1770-PCID, or 1770-PCIDS connection to the network. Pass-through is intended only for fine tuning and adjustment of your network devices. Do not attempt to configure your entire network by using a pass-through driver or a time-out may occur. The pass-through method is not suitable for real-time monitoring of your network devices.

The following table describes what this chapter contains and where to find specific information.

63

Topic

Page

Additional Resources

64

System Requirements

64

Communicating with the DeviceNet Network via an Ethernet Network

65

Communicate with the DeviceNet Network via a DH+ Network

73

What’s Next?

78

Publication 1747-UM655B-EN-P - June 2007

Page 64

64

Communicating with the DeviceNet Network from Another Network

Additional Resources

These documents contain additional information on configuring other networks.

Resource

Description

SLC Modular Style Hardware Installation and Operation Manual, publication 1747-UM011

Provides information about the Data Highway Plus network.

Ethernet SLC 500 Processors Quick Start for Experienced Users, publication 1747-10.4

Provides information about the Ethernet interface.

Comer, Douglas E., Internetworking with TCP-IP, Volume 1: Protocols Provides information about TCP/IP protocol and networking in and Architecture, 2nd ed. Englewood Cliffs, N.J.:Prentice-Hall, general. 1995. ISBN 0-13-216987-8 Tannebaum, Andrew S. Computer Networks, 2nd ed. Englewood Cliffs, N.J.: Prentice-Hall, 1989. ISBN 0-13-162959-X

You can view or download publications at http://literature.rockwellautomation.com. To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative.

System Requirements

To use the pass-through feature, you must have RSLinx software, version 2.10 or later, and a 1747-SDN module at firmware revision 4.015 or later. IMPORTANT

To enable pass-through access with a SLC 500 processor, you must use RSLogix 500 software to configure the M0 and M1 files associated with the 1747-SDN module with a length of 395 words. You can access the M file configuration by launching I/O Configuration within RSLogix 500 software, and then selecting the 1747-SDN module. The SLC 500 processor must be placed in Run mode at least once since its last power cycle for 1747-SDN pass-through transactions to succeed.

IMPORTANT

Publication 1747-UM655B-EN-P - June 2007

You must have previously set up the network you will use to communicate with the DeviceNet network and have installed and configured the appropriate drivers and interface hardware.

Page 65

Communicating with the DeviceNet Network from Another Network

65

The SLC 500 chassis used for these examples was set up with the following hardware mapping. The SLC 5/04 processor was used for the DH+ example. The SLC 5/05 processor was used for the Ethernet example. Hardware Mapping

Communicating with the DeviceNet Network via an Ethernet Network

Module

Slot

DH+ Address

Ethernet Address

DeviceNet Address

SLC 500 5/04 Processor

0

1

-

-

SLC 500 5/05 Processor

0

-

130.130.130.2

-

1747-SDN

2

-

-

0

Before performing this example, the Ethernet network must be configured and running. You must use an Ethernet SLC 5/05 processor (catalog number 1747-L551, 1747-L552, or 1747-L553). Establishing Ethernet pass-through communication involves four main steps. 1. Configure the Ethernet to SLC-5 driver to communicate with the SLC 5/05 processor over the Ethernet Network by using RSLinx software. This procedure is described starting on page 66. 2. Configure the DeviceNet pass-through driver to communicate with the 1747-SDN module via the SLC 5/05 processor and the Ethernet network by using RSLinx software. This procedure is described starting on page 68. 3. Configure the SLC 5/05 processor’s Ethernet communication channel by using RSLogix 500 software when you create the example ladder program. The Ethernet channel configuration is described in Appendix B. 4. Use the pass-through driver with RSNetWorx for DeviceNet software to adjust and tune your DeviceNet network. The procedure for doing this is described starting on page 73.

Publication 1747-UM655B-EN-P - June 2007

Page 66

66

Communicating with the DeviceNet Network from Another Network

Configure the Ethernet Devices Driver To communicate with your SLC 500 processor over the Ethernet network you must configure the Ethernet to SLC 500 driver. Follow these steps to configure the driver by using RSLinx software. 1. Start RSLinx software. 2. From the Communication menu, choose Configure Drivers.

The Configure Drivers dialog appears.

3. From the Available Driver Types pull-down menu, select Ethernet to PLC-5/SLC-5/5820-E and click Add New.

Publication 1747-UM655B-EN-P - June 2007

Page 67

Communicating with the DeviceNet Network from Another Network

67

You are prompted to choose a name for the new driver.

4. Enter an appropriate driver name (for example, AB_ETH-1) and click OK. The Configure driver for Ethernet to PLC-5/SLC-5/5820-EI dialog opens.

5. Enter the IP address of the SLC 5/05 processor in the IP address or hostname field (130.130.130.2 in this example).

IMPORTANT

You must configure channel 0 of the SLC 5/05 processor with the same IP address you enter here.

Publication 1747-UM655B-EN-P - June 2007

Page 68

68

Communicating with the DeviceNet Network from Another Network

6. Click Accept and then OK. The new driver is added to the list of Configured Drivers in RSLinx software. (Your list contains the drivers you have configured.)

Configure the DeviceNet Network Pass-through Driver Before you can communicate with the 1747-SDN module via the Ethernet network, you must configure the DeviceNet pass-through driver (catalog number 1747-SDNPT) by using RSLinx software, version 2.10 or later. You must also have configured the Ethernet to PLC-5/SLC-5/5820-EI driver as described in the previous section and configured the SLC 5/05 processor’s Ethernet communication channel as described in Appendix B. Follow these steps to configure the DeviceNet network Pass-through driver. 1. Start RSLinx software.

Publication 1747-UM655B-EN-P - June 2007

Page 69

Communicating with the DeviceNet Network from Another Network

69

2. From the Communication menu, choose Configure Driver. The Configure Drivers dialog appears.

3. From the Available Driver Types pull-down menu, select DeviceNet Drivers and click Add New. The following list of drivers appears.

4. Select the Allen-Bradley 1747-SDNPT driver. The Allen-Bradley 1747-SDNPT Driver Configuration dialog opens.

5. From the 1747-SDN Slot pull-down menu, select a pass-through port to be configured, for example Slot 2. 6. Expand your Ethernet driver (AB_ETH-1) and highlight the SLC 5/05 processor. 7. Verify that the 1747-SDN Slot is correct.

Publication 1747-UM655B-EN-P - June 2007

Page 70

70

Communicating with the DeviceNet Network from Another Network

8. Click OK. You are prompted to enter a name for the driver.

9. Enter an appropriate driver name (for example, 1747-SDNPT-2) and click OK. The new driver is added to the list of Configured Drivers in RSLinx software. (Your list contains the drivers you have configured for your system.)

10. Close or minimize RSLinx software.

Communicate with the DeviceNet Network You can use RSNetWorx for DeviceNet software to communicate with the DeviceNet network via the Ethernet network once the Ethernet pass-through driver is configured. Follow these steps to communicate with the DeviceNet network.

Publication 1747-UM655B-EN-P - June 2007