For the Allen-Bradley 1747-SDN
Page 55
Configuring the DeviceNet Network
55
Configure the I/O Devices Follow these steps to configure the I/O devices. 1. Double-click the 1747-SDN module icon.
The following dialog appears.
2. Click the Module tab. You receive the following prompt.
Publication 1747-UM655B-EN-P - June 2007
Page 56
56
Configuring the DeviceNet Network
3. Click Upload. After uploading, the following dialog appears.
4. Verify the 1747-SDN module slot number is correct for your system. We used slot 2.
TIP
We used the Module Defaults for the other settings. For an explanation of these settings click Help.
5. Select the Scanlist tab.
6. Verify that the Automap on Add box is not checked.
Publication 1747-UM655B-EN-P - June 2007
Page 57
Configuring the DeviceNet Network
57
7. Click the double arrow to add the photoeye and RediSTATION operator interface to the Scanlist.
Verify the Photoeye Configuration 1. Double-click the photoeye in the Scanlist. The Edit I/O Parameters dialog appears for the photoeye.
The I/O parameters define the configuration for the device in terms of how much and what data the device exchanges with the 1747-SDN module. By default, the photoeye will send 1 byte when it receives the strobe request. 2. Verify that the photoeye parameters are set as shown above. 3. Click OK to close the photoeye Edit I/O Parameters dialog.
Verify the RediSTATION Configuration 1. Double-click the RediSTATION operator interface in the Scanlist dialog.
Publication 1747-UM655B-EN-P - June 2007
Page 58
58
Configuring the DeviceNet Network
The Edit I/O Parameters dialog appears for the RediSTATION operator interface.
2. Verify that the Polled box is checked and that the Rx Size and Tx Size are each 1 byte. 3. Click OK to close the Edit I/O Parameters dialog for the RediSTATION operator interface. 4. Click OK again. You are prompted to download the changes to the 1747-SDN module.
5. Click Yes to download the new configuration.
AutoMap the Devices into the Scanlist Follow these steps to automatically map the photoeye and RediSTATION operator interface to the SLC 500 processor.
TIP
Publication 1747-UM655B-EN-P - June 2007
If you want to know how to map the devices manually, click Help at the bottom of the dialog and select Map device input data manually.
Page 59
Configuring the DeviceNet Network
59
1. Double-click the 1747-SDN module icon and select the Input tab.
2. Select M File in the Memory field. 3. Highlight the RediSTATION operator interface and the photoeye and click AutoMap. The resulting device mapping appears in the lower panel.
Photoeye inputs
RediSTATION inputs
In this example, the inputs from the RediSTATION operator interface appear in the M1 file for the device in slot 2 as word 0, bits 0…7.
Publication 1747-UM655B-EN-P - June 2007
Page 60
60
Configuring the DeviceNet Network
Recall from Chapter 2 that the START button is bit 1 and the STOP button is bit 0. Therefore, the addresses for the RediSTATION inputs are: START - M1:2.0.1 STOP - M1:2.0.0 The input from the photoeye appears in the M1 file for the device in slot 2 as word 0, bits 8…15. Recall from chapter 3 that the input bit is bit 0. Therefore, the address of the photoeye input is: M1:2.0.8 4. Note the addresses assigned to the START and STOP buttons and the photoeye in your system. You enter these addresses in the example ladder program.
Publication 1747-UM655B-EN-P - June 2007
Page 61
Configuring the DeviceNet Network
61
5. Select the Output tab.
After mapping, the RediSTATION output address appears here.
6. Select M File in the Memory field. 7. Highlight the RediSTATION operator interface and click AutoMap. In this example, the output to the RediSTATION operator interface appears in the M0 file for the device in slot 2 as word 0, bits 0…7. Recall from Chapter 3 that the indicator light is output bit 0. Therefore, the address for the RediSTATION indicator light is: M0:2.0.0 8. Note the address assigned to this output in your system. You enter this address in the example ladder logic program in the following chapter.
Publication 1747-UM655B-EN-P - June 2007
Page 62
62
Configuring the DeviceNet Network
Download and Save Your Configuration 1. Click the Scanlist tab and then Download to Scanner.
2. Select All Records. 3. Click Download to download the configuration to the 1747-SDN module. 4. Click OK to complete the DeviceNet scanner configuration. 5. From the File menu, choose Save As.
6. Save the configuration to a DeviceNet file. 7. Close the RSNetWorx for DeviceNet software.
What’s Next?
Publication 1747-UM655B-EN-P - June 2007
The next chapter describes how to configure the DeviceNet network remotely from an Ethernet, ControlNet, or Data Highway Plus network.