For the Allen-Bradley 1747-SDN

Page 47

Chapter

4

Configuring the DeviceNet Network

What This Chapter Contains This chapter describes how to configure the DeviceNet network by using RSLinx and RSNetWorx for DeviceNet software.

Installing the Software

Topic

Page

Installing the Software

47

Use RSLinx Software to Configure the DeviceNet Driver

48

Using RSNetWorx for DeviceNet Software to Configure the 1747-SDN Module Scanlist

50

Set Up an Online Connection

50

Set the 1747-SDN Node Address

52

Configure the I/O Devices

55

Verify the Photoeye Configuration

57

Verify the RediSTATION Configuration

57

AutoMap the Devices into the Scanlist

58

Download and Save Your Configuration

62

Follow these steps to install the RSLinx and RSNetWorx for DeviceNet software. 1. Insert the software CD-ROM in the drive. The CD-ROM supports Windows Autorun. If you have Autorun configured, the installation automatically starts when you insert the CD-ROM in your drive. If you do not have Autorun configured, perform steps 2 and 3. 2. Select Run from the Windows Start menu. 3. Browse for the Setup program on the CD ROM and open it. 4. Follow the prompts that appear as you install the software. After software installation is complete, you use RSLinx software to configure your DeviceNet driver and RSNetWorx for DeviceNet software to configure the network.

47

Publication 1747-UM655B-EN-P - June 2007

Page 48

48

Configuring the DeviceNet Network

Use RSLinx Software to Configure the DeviceNet Driver

Follow these steps to configure your DeviceNet driver. 1. Start RSLinx software. The RSLinx main dialog opens. 2. Select Configure Drivers from the Communication menu.

The following dialog appears.

3. Select DeviceNet Drivers from the above pull-down menu and click Add/New. You see the following choices.

Publication 1747-UM655B-EN-P - June 2007

Page 49

Configuring the DeviceNet Network

49

4. Select the Allen-Bradley 1770-KFD driver. The Driver Configuration dialog appears. TIP

Your driver setup depends on your particular system setup (COM port, communication rate, node address). Choose the appropriate settings for your system.

5. Configure the driver by using the example above as a guide and click on OK. The software takes a few seconds to configure the driver. When it is done the following prompt appears.

6. Select the default driver name 1770-KFD-1 and click OK. 7. Close RSLinx software. Use the driver you just configured to browse and configure the network with RSNetWorx for DeviceNet software. Publication 1747-UM655B-EN-P - June 2007

Page 50

50

Configuring the DeviceNet Network

Using RSNetWorx for DeviceNet Software to Configure the 1747-SDN Module Scanlist

Use RSNetWorx for DeviceNet software to do the following tasks: • Set up an online connection • Set the 1747-SDN node address • Configure the I/O devices • Download and save your configuration

Set Up an Online Connection Follow these steps to set up an online connection to the DeviceNet network by using the 1770-KFD driver. 1. Start RSNetWorx for DeviceNet software. The following dialog appears.

2. From the File menu, choose New. If you have a ControlNet network configured on your system you may see the following dialog. Otherwise, proceed to step 4.

3. Highlight DeviceNet Configuration and click OK.

Publication 1747-UM655B-EN-P - June 2007

Page 51

Configuring the DeviceNet Network

4. Click Online

51 on the toolbar.

A list of the available drivers in RSLinx software appears. Your list may appear different from that shown below, depending upon the drivers you have configured on your system.

5. Select the 1770-KFD-1, DeviceNet driver and click OK. You are prompted to upload or download devices before going online.

Publication 1747-UM655B-EN-P - June 2007

Page 52

52

Configuring the DeviceNet Network

6. Click OK to upload the devices and go online. RSNetWorx for DeviceNet software begins browsing for network devices. When the software is done browsing, the network displayed on your screen should appear similar to the one shown below.

TIP

RSNetWorx for DeviceNet software performs a one-shot browse when you go online or choose the browse feature. The software polls for devices one time and displays the results. If a node which was online later goes offline, there is no live indication in RSNetWorx for DeviceNet software. You must manually perform a browse to detect the missing node. To manually perform the browse, press the

TIP button.

If RSNetWorx for DeviceNet software fails to find a device, check the physical connection to the device. If the physical connection is intact, verify that the device’s communication rate is the same as the 1770-KFD driver’s communication rate.

Set the 1747-SDN Node Address Once the devices are uploaded, their node addresses appear to the right of their icons. For the example application, the 1747-SDN module should have a node address of 0 (or 00). If you need to change a module’s node address, use the following procedure. TIP

Publication 1747-UM655B-EN-P - June 2007

You can use this procedure to change the node address of other devices on the network (for example, the photoeye). You can also change the network data rate (communication rate) of some devices. Power must be cycled for baud rate changes to take effect.

Page 53

Configuring the DeviceNet Network

53

If 00 appears to the right of the 1747-SDN icon and you do not need to change the node address or baud rate of any device, skip the remainder of this section and go to Configure the I/O Devices on page 55.

IMPORTANT

The network must not be active when performing node commissioning on the 1747-SDN module. Make sure the processor is in Program mode. (Note that this applies only to the 1747-SDN module. You may commission other devices with the processor in Run mode.)

Follow these steps to set the node address. 1. From the Tools menu, choose Node Commissioning. The Node Commissioning dialog appears.

2. Click Browse. The Device Selection dialog appears.

Publication 1747-UM655B-EN-P - June 2007

Page 54

54

Configuring the DeviceNet Network

3. Select the 1770-KFD driver. The devices on the network appear in the right panel of the dialog.

4. Select the device you are commissioning in the right panel and click OK. The Node Commissioning dialog appears with the current settings for your 1747-SDN module. Your dialog should look similar to the one shown below.

5. Enter a 0 in the New Device Settings: Node Address box. 6. Click Apply and exit the dialog.