Install the 1747-KFC15 Module in the Chassis
ATTENTION
Electrostatic discharge can damage semiconductor devices inside the 1747-KFC15 module. To guard against electrostatic damage, wear an approved wrist strap grounding device, or touch a grounded object to rid yourself of electrostatic charge before handling the products.
1. Remove power from your 1746 I/O chassis. 2. Install the 1747-KFC15 module into an empty I/O slot. The 1747-KFC15 module must be placed near enough to the SLC processor to connect the supplied RS-232 cable between them. We used slot 1 for the example application. 3. Connect the 1747-KFC15 module to your SLC 500 processor with the RS-232 cable.
RS-232 Cable
Connecting the 1747-KFC15 Module to the ControlNet Network Connect the 1747-KFC15 to the ControlNet cable system by using an approved ControlNet tap.
Publication 1747-UM655B-EN-P - June 2007
Page 40
40
Hardware Setup
Refer to the ControlNet Coax Media Planning and Installation Guide, publication CNET-IN002, for complete instructions on connecting the tap to the ControlNet cable system.
Installing the 1747-SDN Module
These sections give you information on installing your module and getting it connected.
Identifying Module Features Use the following figure to identify the features of the 1747-SDN module. 1747-SDN Module Features
Module Status Indicator indicates module status.
Network Status Indicator indicates status of the DeviceNet channel communication link.
Node Address and Status Display displays numeric codes and indicates scanner node address or error.
Access Door
Wiring Color Codes
10-pin Linear Plug inserted into DeviceNet port.
Publication 1747-UM655B-EN-P - June 2007
Page 41
Hardware Setup
41
Install the 1747-SDN Module In the Chassis
ATTENTION
Do not install the 1747-SDN module with the chassis power supply on. Installing the module with the chassis power supply on may damage the module.
Follow these steps to install your module into the chassis. 1. Turn off the chassis power supply. 2. Select a slot for the module in the chassis. You may use any slot except the leftmost slot, which is reserved for the SLC 500 processor. 3. Insert the module into the slot you have selected by applying firm, even pressure to seat the module in the chassis backplane connectors.
Publication 1747-UM655B-EN-P - June 2007
Page 42
42
Hardware Setup
Connect the 1747-SDN Module to the DeviceNet Network Follow these steps to connect your module to the DeviceNet network. 1. Turn off the network power supply.
ATTENTION
Do not wire the 1747-SDN module with the network power supply on. Wiring the module with the network power supply on may short your network or disrupt communication.
2. Connect the DeviceNet drop line to the 10-pin linear plug. Match the wire insulation colors to the colors shown on the label. Module label shows wiring color scheme.
10-pin Linear Plug
DeviceNet Drop Line
3. Locate the DeviceNet port connector on the front of the module, and insert the 10-pin linear plug into the connector.
Publication 1747-UM655B-EN-P - June 2007
Page 43
Hardware Setup
TIP
43
You use RSNetWorx for DeviceNet software to configure the module’s DeviceNet address and communication rate, if needed. This is done when configuring the DeviceNet network. See page 52.
For additional information about installing the 1747-SDN module, see the 1747-SDN DeviceNet Scanner Module Installation Instructions, publication 1747-IN058.
Installing the RediSTATION Operator Interface
Begin installing the RediSTATION operator interface by removing the six screws fastening the cover and setting the DIP switches inside. DIP Switch Settings Set this position
To this value
1 2 3 4 5 6
1 - On 1 - On 1 - On 0 - Off 0 - Off 0 - Off
Node Address(1)
7 8
0 - Off 1 - On
Data Rate(2)
9 10
0 - Off 0 - Off
(1)
The DeviceNet address is 000111 (node 7).
(2)
The data rate is 10 (500 KB). The output fault rate is 0 (outputs turned off). The output flash rate is 0 (outputs tuned off).
Publication 1747-UM655B-EN-P - June 2007
Page 44
44
Hardware Setup
See Chapter 2 of the RediSTATION Operator Interface User Manual, publication 2705-UM001, for complete information about setting the DIP switches to configure the node address, data rate, output flash rate, and output fault state. Refer to the following illustration as you connect the RediSTATION operator interface to the network.
TIP
You do not need to disconnect incoming power from the DeviceNet network before connecting the RediSTATION operator interface.
The DeviceNet cable connects directly to the mini connector on the top of the RediSTATION enclosure or through the conduit opening (open style). RediSTATION Connection DeviceNet Cable
Mini Connector
Installing the Series 9000 Photoeye
Open Style
Connect the photoeye to the network and configure the photoeye as follows: • Node address: 9 • Operating mode: Light Operate (default) • Communication rate: 500 Kbps
Publication 1747-UM655B-EN-P - June 2007
Page 45
Hardware Setup
45
Top View of Series 9000 Photoeye Programming Pushbutton
Sensitivity Adjustment
Yellow - Output Green - Margin Red/Green - Status
For detailed directions, see the instructions that came with your photoeye.
How Your Network Will Look
When you have finished installing all the devices, the network should look similar to this. Typical Network
Computer running Windows 2000 or later operating system, containing RSNetWorx for DeviceNet software.
Series 9000 Photoelectric Sensor Node 9 1770-KFD Communication Module
Computer Serial Port
Quad-tap 1492-DN3TW Node 62 Node 0
24 V Node 7
SLC 500 Chassis
RediSTATION Operator Interface
Publication 1747-UM655B-EN-P - June 2007
Page 46
46
Hardware Setup
IMPORTANT
What’s Next?
Publication 1747-UM655B-EN-P - June 2007
Make sure each end of the DeviceNet trunk cable is properly terminated with a resistor. Refer to the DeviceNet Media Design and Installation Guide, publication DNET-UM072, for information.
The next step is to configure the 1747-SDN module and perform I/O data mapping through RSNetWorx for DeviceNet software.