For the Allen-Bradley 1747-SDN

Page 39

Hardware Setup

39

Install the 1747-KFC15 Module in the Chassis

ATTENTION

Electrostatic discharge can damage semiconductor devices inside the 1747-KFC15 module. To guard against electrostatic damage, wear an approved wrist strap grounding device, or touch a grounded object to rid yourself of electrostatic charge before handling the products.

1. Remove power from your 1746 I/O chassis. 2. Install the 1747-KFC15 module into an empty I/O slot. The 1747-KFC15 module must be placed near enough to the SLC processor to connect the supplied RS-232 cable between them. We used slot 1 for the example application. 3. Connect the 1747-KFC15 module to your SLC 500 processor with the RS-232 cable.

RS-232 Cable

Connecting the 1747-KFC15 Module to the ControlNet Network Connect the 1747-KFC15 to the ControlNet cable system by using an approved ControlNet tap.

Publication 1747-UM655B-EN-P - June 2007

Page 40

40

Hardware Setup

Refer to the ControlNet Coax Media Planning and Installation Guide, publication CNET-IN002, for complete instructions on connecting the tap to the ControlNet cable system.

Installing the 1747-SDN Module

These sections give you information on installing your module and getting it connected.

Identifying Module Features Use the following figure to identify the features of the 1747-SDN module. 1747-SDN Module Features

Module Status Indicator indicates module status.

Network Status Indicator indicates status of the DeviceNet channel communication link.

Node Address and Status Display displays numeric codes and indicates scanner node address or error.

Access Door

Wiring Color Codes

10-pin Linear Plug inserted into DeviceNet port.

Publication 1747-UM655B-EN-P - June 2007

Page 41

Hardware Setup

41

Install the 1747-SDN Module In the Chassis

ATTENTION

Do not install the 1747-SDN module with the chassis power supply on. Installing the module with the chassis power supply on may damage the module.

Follow these steps to install your module into the chassis. 1. Turn off the chassis power supply. 2. Select a slot for the module in the chassis. You may use any slot except the leftmost slot, which is reserved for the SLC 500 processor. 3. Insert the module into the slot you have selected by applying firm, even pressure to seat the module in the chassis backplane connectors.

Publication 1747-UM655B-EN-P - June 2007

Page 42

42

Hardware Setup

Connect the 1747-SDN Module to the DeviceNet Network Follow these steps to connect your module to the DeviceNet network. 1. Turn off the network power supply.

ATTENTION

Do not wire the 1747-SDN module with the network power supply on. Wiring the module with the network power supply on may short your network or disrupt communication.

2. Connect the DeviceNet drop line to the 10-pin linear plug. Match the wire insulation colors to the colors shown on the label. Module label shows wiring color scheme.

10-pin Linear Plug

DeviceNet Drop Line

3. Locate the DeviceNet port connector on the front of the module, and insert the 10-pin linear plug into the connector.

Publication 1747-UM655B-EN-P - June 2007

Page 43

Hardware Setup

TIP

43

You use RSNetWorx for DeviceNet software to configure the module’s DeviceNet address and communication rate, if needed. This is done when configuring the DeviceNet network. See page 52.

For additional information about installing the 1747-SDN module, see the 1747-SDN DeviceNet Scanner Module Installation Instructions, publication 1747-IN058.

Installing the RediSTATION Operator Interface

Begin installing the RediSTATION operator interface by removing the six screws fastening the cover and setting the DIP switches inside. DIP Switch Settings Set this position

To this value

1 2 3 4 5 6

1 - On 1 - On 1 - On 0 - Off 0 - Off 0 - Off

Node Address(1)

7 8

0 - Off 1 - On

Data Rate(2)

9 10

0 - Off 0 - Off

(1)

The DeviceNet address is 000111 (node 7).

(2)

The data rate is 10 (500 KB). The output fault rate is 0 (outputs turned off). The output flash rate is 0 (outputs tuned off).

Publication 1747-UM655B-EN-P - June 2007

Page 44

44

Hardware Setup

See Chapter 2 of the RediSTATION Operator Interface User Manual, publication 2705-UM001, for complete information about setting the DIP switches to configure the node address, data rate, output flash rate, and output fault state. Refer to the following illustration as you connect the RediSTATION operator interface to the network.

TIP

You do not need to disconnect incoming power from the DeviceNet network before connecting the RediSTATION operator interface.

The DeviceNet cable connects directly to the mini connector on the top of the RediSTATION enclosure or through the conduit opening (open style). RediSTATION Connection DeviceNet Cable

Mini Connector

Installing the Series 9000 Photoeye

Open Style

Connect the photoeye to the network and configure the photoeye as follows: • Node address: 9 • Operating mode: Light Operate (default) • Communication rate: 500 Kbps

Publication 1747-UM655B-EN-P - June 2007

Page 45

Hardware Setup

45

Top View of Series 9000 Photoeye Programming Pushbutton

Sensitivity Adjustment

Yellow - Output Green - Margin Red/Green - Status

For detailed directions, see the instructions that came with your photoeye.

How Your Network Will Look

When you have finished installing all the devices, the network should look similar to this. Typical Network

Computer running Windows 2000 or later operating system, containing RSNetWorx for DeviceNet software.

Series 9000 Photoelectric Sensor Node 9 1770-KFD Communication Module

Computer Serial Port

Quad-tap 1492-DN3TW Node 62 Node 0

24 V Node 7

SLC 500 Chassis

RediSTATION Operator Interface

Publication 1747-UM655B-EN-P - June 2007

Page 46

46

Hardware Setup

IMPORTANT

What’s Next?

Publication 1747-UM655B-EN-P - June 2007

Make sure each end of the DeviceNet trunk cable is properly terminated with a resistor. Refer to the DeviceNet Media Design and Installation Guide, publication DNET-UM072, for information.

The next step is to configure the 1747-SDN module and perform I/O data mapping through RSNetWorx for DeviceNet software.