The text of a manual · part 6 of 22
1747-SDN DeviceNet Scanner Module User Manual: 3 - Hardware Setup, pages 31 to 38
Pages 31 to 38 of 160, from 1747-SDN DeviceNet Scanner Module User Manual
The original document is the PDF (3.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1747-SDN
Page 31
Chapter
3
Hardware Setup
What This Chapter Contains This chapter describes how to set up the hardware for the example application. The following table describes what this chapter contains and where to find specific information.
Installing the 1770-KFD Module
Topic
Page
Installing the 1770-KFD Module
31
Installing the SLC 500 Processor
32
Installing the ControlNet RS-232 Interface Module
35
Installing the 1747-SDN Module
40
Installing the RediSTATION Operator Interface
43
Installing the Series 9000 Photoeye
44
How Your Network Will Look
45
Connect the RS-232 connector on the 1770-KFD communication interface module to one of the serial ports on your computer workstation (COM1). Connect the DeviceNet connector on the 1770-KFD module to a DeviceNet drop or trunk cable. You can make this connection in several ways; for example, by using a DeviceNet Quad Tap (catalog number 1492-DN3TW) as shown on page 45.
To computer COM 1770-KFD RS-232 Interface Module DeviceNet Dropline or Trunk Cable
31
To DeviceNet Network
Publication 1747-UM655B-EN-P - June 2007
Page 32
32
Hardware Setup
For detailed directions on how to install the 1770-KFD module, see the DeviceNet RS-232 Interface Module Installation Instructions, publication 1770-5.6.
Installing the SLC 500 Processor
These sections give you information on installing your processor and getting it connected.
Identifying Processor Features Refer to the following figures to identify the features of your SLC 5/04 or SLC 5/05 processor. Processor Features SLC 5/04 CPU
SLC 5/05 CPU
RUN FLT BATT
RUN FLT BATT RUN REM
FORCE DH+ RS232 RUN REM PROG
FORCE ENET RS232 PROG
Channel 1 DH+
Channel 1 Ethernet (10/100Base-T)
Channel 0 RS232 (optional DH485, DF1, or ASCII)
Channel 0 RS232 (optional DH485, DF1, or ASCII)
SLC 5/04 Processor
SLC 5/05 Processor
Make sure system power is off; then insert the processor into slot 0 of the 1746 I/O chassis.
Publication 1747-UM655B-EN-P - June 2007
Page 33
Hardware Setup
33
Chassis Install
IMPORTANT
Insert the SLC 500 processor into the left slot (slot 0), as shown above. Remove the protective wrap after installing the processor.
Establishing Data Highway Plus Communication For the examples using the Data Highway Plus (DH+) network in Chapters 5 and 6 of this manual, we installed a 1784-PKTX communication card in the host platform and an SLC 5/04 processor with these default Channel 1 DH+ configurations: • DH+ node address = 1 • Communication rate = 57.6 Kbps Connect Channel 1 of the SLC 5/04 processor to the DH+ network by using the three-pin connector on the front of the module.
Publication 1747-UM655B-EN-P - June 2007
Page 34
34
Hardware Setup
DH+ Network Connection
Terminating Resistor
See Chapter 5 for information on configuring the SLC 5/04 processor’s DH+ communication.
Installing an Ethernet SLC 500 Processor (SLC 5/05 Processor) In order to communicate with your SLC 500 processor over an Ethernet network, you must install an Ethernet version of the processor (SLC 5/05 processor, catalog numbers 1747-L551, 1747-L552, or 1747-L553). Connect channel 1 of the Ethernet SLC 5/05 processor to an Ethernet hub by using 10 Base-T cable as shown below. Ethernet Hub Connection Ethernet Hub to Host Platform Ethernet Card
RJ45 Connectors on Both Ends of Cable (10Base-T)
to SLC 5/05 Channel 1
See Chapter 5 for information on configuring the SLC 5/05 processor’s Ethernet communication.
Publication 1747-UM655B-EN-P - June 2007
Page 35
Hardware Setup
35
Configuring the RS-232 Port for the ControlNet Interface If you need to communicate with your SLC 500 processor via a ControlNet network, you must install a 1747-KFC15 ControlNet interface module in the chassis with your processor. You can use either a SLC 5/04 or a SLC 5/05 processor. The 1747-KFC15 module connects to the SLC 500 processor via the processor’s RS-232 port (channel 0).
TIP
Installing the ControlNet RS-232 Interface Module
You can use your RSLogix 500 programming software to set the SLC 5/04 processor’s RS-232 channel configuration.
To communicate with the SLC 500 processor via a ControlNet network, you must install a 1747-KFC15 ControlNet RS-232 interface module in the 1746 I/O chassis close to the processor.
Configuring the 1747-KFC15 Module’s RS-232 Port
IMPORTANT
The communication parameters of 1747-KFC15 module must match those of the SLC 500 processor.
The RS-232 serial port on the 1747-KFC15 module is configured by using three banks (S1, S2, and S3) of DIP switches mounted on the module’s printed circuit board.
Publication 1747-UM655B-EN-P - June 2007
Page 36
36
Hardware Setup
Dip Switch Setting
The upper position as shown above is ON. The lower position is OFF.
For the example application, we used the following configuration to match the configuration of the SLC 500 processor’s RS-232 port described in the previous section. Channel 0 Configuration Attribute
Value
DF1 station address
0
Communication rate
19.2 Kbps
Full/Half-duplex
Full-duplex
Parity
None
Handshake
No handshaking
Diagnostic command execution
Disabled
Duplicate detect
Enabled
Error detect
CRC
Retries
3
DF1 ACK timeout
1.0 s
For this configuration, set the switches as shown in these tables.
Publication 1747-UM655B-EN-P - June 2007
Page 37
Hardware Setup
37
Bank S1 DIP Switches Switch
Setting
Position
Switches 1…3
Upper digit of DF1 station address
SW1
SW2
SW3
Digit
ON
ON
ON
0
Switches 4…6
Lower digit of DF1 station address
SW4
SW5
SW6
Digit
ON
ON
ON
0
Switches 7…8
Both OFF
Bank S2 DIP Switches Switch
Setting
Position
Switches 1…3
Upper digit of DF1 station address
SW1
SW2
SW3
Digit
ON
OFF
OFF
19200
Switch 4
Full/Half-dup OFF = Full-duplex lex
Switch 5
Parity
OFF = No parity
Switch 6
Odd/even parity
Not applicable
Switch 7
Handshake
OFF = Hardware handshake disabled
Switch 8
Diagnostic command execution
OFF = Disabled
Bank S3 DIP Switches Switch
Setting
Position
Switch 1
Duplicate detect
ON = Duplicate detect on
Switch 2
Error detect
OFF = CRC error check
Switches 3…4
Number of SW3 retries ON
SW4
Number of retries
ON
0
Switches 5…8
DF1 ACK time-out
SW5
SW6
SW7
SW8
Time Out
OFF
OFF
OFF
OFF
3.2
Publication 1747-UM655B-EN-P - June 2007
Page 38
38
Hardware Setup
Refer to the SLC 500 ControlNet RS-232 Interface User Manual, publication 1747-5.34, for information on setting and verifying the 1747-KFC15 and SLC 500 processor communication parameters.
Configuring the 1747-KFC15 Module’s ControlNet Node Address The 1747-KFC15 modules’s ControlNet node address is set by rotary switches S4 and S5 on the top of the module. Switch S5 sets the upper digit of the address and S4 the lower. These switches can be turned by hand while holding the module in the orientation illustrated below. Switch Location
Back of Module
S4
Front of Module
S5
Rotary Switches
We set the ControlNet node address to 16 for the example application. Switch Setting ControlNet Node Address = 16 20
2
30 40
1
00
50
0
90
60
9
10
80
70
3 4 5 6
8
7
Refer to Chapter 5 for more information on configuring ControlNet communication for the example application.
Publication 1747-UM655B-EN-P - June 2007