Page 31

Chapter

3

Hardware Setup

What This Chapter Contains This chapter describes how to set up the hardware for the example application. The following table describes what this chapter contains and where to find specific information.

Installing the 1770-KFD Module

Topic

Page

Installing the 1770-KFD Module

31

Installing the SLC 500 Processor

32

Installing the ControlNet RS-232 Interface Module

35

Installing the 1747-SDN Module

40

Installing the RediSTATION Operator Interface

43

Installing the Series 9000 Photoeye

44

How Your Network Will Look

45

Connect the RS-232 connector on the 1770-KFD communication interface module to one of the serial ports on your computer workstation (COM1). Connect the DeviceNet connector on the 1770-KFD module to a DeviceNet drop or trunk cable. You can make this connection in several ways; for example, by using a DeviceNet Quad Tap (catalog number 1492-DN3TW) as shown on page 45.

To computer COM 1770-KFD RS-232 Interface Module DeviceNet Dropline or Trunk Cable

31

To DeviceNet Network

Publication 1747-UM655B-EN-P - June 2007

Page 32

32

Hardware Setup

For detailed directions on how to install the 1770-KFD module, see the DeviceNet RS-232 Interface Module Installation Instructions, publication 1770-5.6.

Installing the SLC 500 Processor

These sections give you information on installing your processor and getting it connected.

Identifying Processor Features Refer to the following figures to identify the features of your SLC 5/04 or SLC 5/05 processor. Processor Features SLC 5/04 CPU

SLC 5/05 CPU

RUN FLT BATT

RUN FLT BATT RUN REM

FORCE DH+ RS232 RUN REM PROG

FORCE ENET RS232 PROG

Channel 1 DH+

Channel 1 Ethernet (10/100Base-T)

Channel 0 RS232 (optional DH485, DF1, or ASCII)

Channel 0 RS232 (optional DH485, DF1, or ASCII)

SLC 5/04 Processor

SLC 5/05 Processor

Make sure system power is off; then insert the processor into slot 0 of the 1746 I/O chassis.

Publication 1747-UM655B-EN-P - June 2007

Page 33

Hardware Setup

33

Chassis Install

IMPORTANT

Insert the SLC 500 processor into the left slot (slot 0), as shown above. Remove the protective wrap after installing the processor.

Establishing Data Highway Plus Communication For the examples using the Data Highway Plus (DH+) network in Chapters 5 and 6 of this manual, we installed a 1784-PKTX communication card in the host platform and an SLC 5/04 processor with these default Channel 1 DH+ configurations: • DH+ node address = 1 • Communication rate = 57.6 Kbps Connect Channel 1 of the SLC 5/04 processor to the DH+ network by using the three-pin connector on the front of the module.

Publication 1747-UM655B-EN-P - June 2007

Page 34

34

Hardware Setup

DH+ Network Connection

Terminating Resistor

See Chapter 5 for information on configuring the SLC 5/04 processor’s DH+ communication.

Installing an Ethernet SLC 500 Processor (SLC 5/05 Processor) In order to communicate with your SLC 500 processor over an Ethernet network, you must install an Ethernet version of the processor (SLC 5/05 processor, catalog numbers 1747-L551, 1747-L552, or 1747-L553). Connect channel 1 of the Ethernet SLC 5/05 processor to an Ethernet hub by using 10 Base-T cable as shown below. Ethernet Hub Connection Ethernet Hub to Host Platform Ethernet Card

RJ45 Connectors on Both Ends of Cable (10Base-T)

to SLC 5/05 Channel 1

See Chapter 5 for information on configuring the SLC 5/05 processor’s Ethernet communication.

Publication 1747-UM655B-EN-P - June 2007

Page 35

Hardware Setup

35

Configuring the RS-232 Port for the ControlNet Interface If you need to communicate with your SLC 500 processor via a ControlNet network, you must install a 1747-KFC15 ControlNet interface module in the chassis with your processor. You can use either a SLC 5/04 or a SLC 5/05 processor. The 1747-KFC15 module connects to the SLC 500 processor via the processor’s RS-232 port (channel 0).

TIP

Installing the ControlNet RS-232 Interface Module

You can use your RSLogix 500 programming software to set the SLC 5/04 processor’s RS-232 channel configuration.

To communicate with the SLC 500 processor via a ControlNet network, you must install a 1747-KFC15 ControlNet RS-232 interface module in the 1746 I/O chassis close to the processor.

Configuring the 1747-KFC15 Module’s RS-232 Port

IMPORTANT

The communication parameters of 1747-KFC15 module must match those of the SLC 500 processor.

The RS-232 serial port on the 1747-KFC15 module is configured by using three banks (S1, S2, and S3) of DIP switches mounted on the module’s printed circuit board.

Publication 1747-UM655B-EN-P - June 2007

Page 36

36

Hardware Setup

Dip Switch Setting

The upper position as shown above is ON. The lower position is OFF.

For the example application, we used the following configuration to match the configuration of the SLC 500 processor’s RS-232 port described in the previous section. Channel 0 Configuration Attribute

Value

DF1 station address

0

Communication rate

19.2 Kbps

Full/Half-duplex

Full-duplex

Parity

None

Handshake

No handshaking

Diagnostic command execution

Disabled

Duplicate detect

Enabled

Error detect

CRC

Retries

3

DF1 ACK timeout

1.0 s

For this configuration, set the switches as shown in these tables.

Publication 1747-UM655B-EN-P - June 2007

Page 37

Hardware Setup

37

Bank S1 DIP Switches Switch

Setting

Position

Switches 1…3

Upper digit of DF1 station address

SW1

SW2

SW3

Digit

ON

ON

ON

0

Switches 4…6

Lower digit of DF1 station address

SW4

SW5

SW6

Digit

ON

ON

ON

0

Switches 7…8

Both OFF

Bank S2 DIP Switches Switch

Setting

Position

Switches 1…3

Upper digit of DF1 station address

SW1

SW2

SW3

Digit

ON

OFF

OFF

19200

Switch 4

Full/Half-dup OFF = Full-duplex lex

Switch 5

Parity

OFF = No parity

Switch 6

Odd/even parity

Not applicable

Switch 7

Handshake

OFF = Hardware handshake disabled

Switch 8

Diagnostic command execution

OFF = Disabled

Bank S3 DIP Switches Switch

Setting

Position

Switch 1

Duplicate detect

ON = Duplicate detect on

Switch 2

Error detect

OFF = CRC error check

Switches 3…4

Number of SW3 retries ON

SW4

Number of retries

ON

0

Switches 5…8

DF1 ACK time-out

SW5

SW6

SW7

SW8

Time Out

OFF

OFF

OFF

OFF

3.2

Publication 1747-UM655B-EN-P - June 2007

Page 38

38

Hardware Setup

Refer to the SLC 500 ControlNet RS-232 Interface User Manual, publication 1747-5.34, for information on setting and verifying the 1747-KFC15 and SLC 500 processor communication parameters.

Configuring the 1747-KFC15 Module’s ControlNet Node Address The 1747-KFC15 modules’s ControlNet node address is set by rotary switches S4 and S5 on the top of the module. Switch S5 sets the upper digit of the address and S4 the lower. These switches can be turned by hand while holding the module in the orientation illustrated below. Switch Location

Back of Module

S4

Front of Module

S5

Rotary Switches

We set the ControlNet node address to 16 for the example application. Switch Setting ControlNet Node Address = 16 20

2

30 40

1

00

50

0

90

60

9

10

80

70

3 4 5 6

8

7

Refer to Chapter 5 for more information on configuring ControlNet communication for the example application.

Publication 1747-UM655B-EN-P - June 2007