1747-SDN DeviceNet Scanner Module User Manual: 6 - Creating and Running the Example Application Program
Pages 79 to 88 of 160, from 1747-SDN DeviceNet Scanner Module User Manual
The original document is the PDF (3.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1747-SDN
Page 79
Chapter
6
Creating and Running the Example Application Program
What This Chapter Contains This chapter describes the procedure to create, download, and run an example ladder logic program to test the DeviceNet network. When the processor is put into Run mode, pressing the START button on the network’s RediSTATION operator interface will cause the red indicator light to come on and stay on until the STOP button is pressed. Passing an object in front of the photoeye will increment a counter. Recall that you cannot directly communicate with the SLC 500 processor over the DeviceNet network. This chapter shows how to download and run the program over a ControlNet, Ethernet, or Data Highway Plus network. The SLC 500 I/O chassis used for these examples was set up with the following hardware. Chassis Setup Module
Slot
DH+ Address
Ethernet Address
ControlNet Address
DeviceNet Address
SLC 500 5/04 Processor(1)
0
1
-
-
-
SLC 500 5/05 Processor(2)
0
-
130.130.130.2
-
-
1747-KFC15
1
-
-
16
-
1747-SDN
2
-
-
-
0
(1)
Used for Data Highway Plus and ControlNet examples.
(2)
Used for Ethernet example.
The following table describes what this chapter contains and where to find specific information.
79
Topic
Page
Install the Software
80
Create the Example Application Program
80
Download and Run the Program
82
Publication 1747-UM655B-EN-P - June 2007
Page 80
80
Creating and Running the Example Application Program
Install the Software
Follow these steps to install the software. 1. Insert the software CD-ROM installation disk in the drive. The CD-ROM supports Windows Autorun. If you have Autorun configured, the installation automatically starts when you insert the CD-ROM in your drive. If you do not have Autorun configured, perform steps 2 and 3. 2. From the Windows Start menu, choose Run. 3. Browse for the Setup program on the CD ROM and open it. 4. Follow the prompts that appear as you install the software.
Create the Example Application Program
Follow these steps to create the example application program. 1. Start the RSLogix 500 programming software. You see the following dialog.
Publication 1747-UM655B-EN-P - June 2007
Page 81
Creating and Running the Example Application Program
81
2. From the File menu, choose New. The Select Processor Type dialog opens.
3. Select your processor type from the list (for example, 1747-L542A) and click OK. 4. Enter the following ladder program. Note that the program uses the addresses mapped to the devices by RSNetWorx for DeviceNet software in chapter 4.
5. Save the program by using an appropriate name, for example, 1747-SDN.
Publication 1747-UM655B-EN-P - June 2007
Page 82
82
Creating and Running the Example Application Program
Download and Run the Program
You cannot go online to the processor directly over the DeviceNet network. The following sections provide examples of downloading and running the program by using these networks: • ControlNet • Ethernet • Data Highway Plus
Download and Run the Program via a ControlNet Network Follow these steps to download and run the example program via a ControlNet network. 1. From the RSLogix 500 Communication menu, choose System Comms. The Communication dialog appears. Your dialog may look different depending upon the drivers and other devices you have installed.
2. Click the + next to your ControlNet driver (AB_KTC-1) to expand the tree. 3. Select the 1747-KFC15 module as shown above and click Download. Your program is downloaded to the controller.
Publication 1747-UM655B-EN-P - June 2007
Page 83
Creating and Running the Example Application Program
83
4. Change the SLC 500 processor mode to Run after the download is complete. IMPORTANT
You must also place the 1747-SDN module in Run mode by setting the Run Bit (bit 0) in the scanner’s command register. The command register is located at word 0 in the Output image table.
5. In the Data Files folder, double-click O0-Output. You see the 1747-SDN module’s command register (file O:2.0 below).
6. Set bit 0 in the command register to 1, as shown above. 7. Press and release the START button on the RediSTATION operator interface. The red light should turn on. On your screen, you see rung 1 in your ladder program being energized as you press the button. 8. Pass your hand back and forth over the photoeye several times. On your screen you should see the counter increment. 9. Press and release the STOP button on the RediSTATION operator interface. The red light should turn off. On your screen, you see rung 2 in your ladder program being energized as you press the button. This completes the ControlNet example. Publication 1747-UM655B-EN-P - June 2007
Page 84
84
Creating and Running the Example Application Program
Download and Run the Program via an Ethernet Network
IMPORTANT
To communicate with your SLC 5/05 processor over an Ethernet network you must first configure the processor’s Ethernet communication channel and assign it a unique IP address. See Appendix B for information on configuring the Ethernet communication channel.
Follow the procedure below to download and run the example program via an Ethernet network. 1. From the RSLogix 500 Communication menu, choose System Comms. The Communication dialog opens. Your dialog may look different depending upon the drivers you have installed.
2. Click the + next to your Ethernet driver (AB-ETH-1 above) to expand the tree. 3. Select the SLC 500 processor as shown above and click Download. 4. Put the processor in Run mode after the download is complete.
IMPORTANT
Publication 1747-UM655B-EN-P - June 2007
You must also place the 1747-SDN module in Run mode by setting the Run Bit (bit 0) in the scanner’s command register. The command register is located at word 0 in the Output image table.
Page 85
Creating and Running the Example Application Program
85
5. Double-click the O0 - OUTPUT file under the Data Files folder. You see the 1747-SDN module’s command register (file O:2.0 below).
6. Set bit 0 in the command register to 1, as shown above. 7. Press and release the START button on the RediSTATION operator interface. The red light should turn on. On your screen, you see rung 1 in your ladder program being energized as you press the button. 8. Pass your hand back and forth over the photoeye several times. On your screen you should see the counter increment. 9. Press and release the STOP button on the RediSTATION operator interface. The red light should turn off. On your screen, you see rung 2 in your ladder program being energized as you press the button. This completes the Ethernet example.
Publication 1747-UM655B-EN-P - June 2007
Page 86
86
Creating and Running the Example Application Program
Download and Run the Program via a DH+ Network Follow the procedure below to download and run the example program via a DH+ network. 1. From the RSLogix 500 Communication menu, choose System Communication. RSLinx software starts, and the Communication dialog opens.
2. Select your Data Highway Plus driver (AB_KT-1, Data Highway Plus in the above example). 3. Select the + next to your Data Highway Plus driver (AB_KT-1 above) to expand the tree. 4. Select the SLC 500 processor and click Download. 5. Go Online and put the SLC 500 processor in Run mode after the download is complete.
IMPORTANT
Publication 1747-UM655B-EN-P - June 2007
You must also place the 1747-SDN module in Run mode by setting the Run bit (bit 0) in the scanner’s command register. The command register is located at word 0 in the Output image table.
Page 87
Creating and Running the Example Application Program
87
6. Double-click the O0 - OUTPUT file under the Data Files folder. You see the 1747-SDN module’s command register (file O:2.0 below).
7. Set bit 0 in the command register to 1. 8. Press and release the START button on the RediSTATION operator interface. The red indicator light should turn on. On your screen, you should see rung 0 in your ladder program being energized when you press the button. 9. Pass your hand back and forth over the photoeye several times. On your screen you should see the counter incrementing. 10. Press and release the STOP button on the RediSTATION operator interface. The red indicator light should turn off. On your screen, you should see rung 1 in your ladder program being energized when you press the button. This completes the Data Highway Plus example.
What’s Next?
This concludes the application examples. The following chapter describes how the diagnostic indicators on the 1747-SDN module can be used for troubleshooting.
Publication 1747-UM655B-EN-P - June 2007
Page 88
88
Creating and Running the Example Application Program
Publication 1747-UM655B-EN-P - June 2007