1747-SDN DeviceNet Scanner Module User Manual: 7 - Troubleshooting

Pages 89 to 92 of 160, from 1747-SDN DeviceNet Scanner Module User Manual

The original document is the PDF (3.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1747-SDN

Page 89

Chapter

7

Troubleshooting

The 1747-SDN interface module is provided with status diagnostic indicators on its front panel. The diagnostics provided by these indicators are described in this chapter.

Module Status Indicator

Topic

Page

Module Status Indicator

89

Network Status Indicator

90

Numeric Display Code Summary

90

The bicolor (green/red) Module Status indicator (MODULE) indicates whether the 1747-SDN module has power and is functioning properly.

Module Status Indicator

Network Status Indicator

Top part of module.

If the MODULE indicator is

Then

Take this action

Off

There is no power applied to the module.

Verify power connections and apply power.

Green

The module is operating normally.

No action required.

Flashing Green

The module is not configured.

Configure the module.

Flashing Red

There is an invalid configuration.

Check configuration setup.

Red

The module has an unrecoverable fault.

Replace the module.

89

Publication 1747-UM655B-EN-P - June 2007

Page 90

90

Troubleshooting

Network Status Indicator

The bicolor (green/red) network status indicator (NET) provides troubleshooting information about the DeviceNet channel communication link.

If the NET indicator is

Then

Which indicates

Take this action

Off

The device has no power or the channel is disabled for communication due to bus off condition, loss of network power, or has been intentionally disabled.

The channel is disabled for DeviceNet communication.

Power-up the module, provide network power to the channel, and be sure the channel is enabled in both the module configuration table and the module command word.

Green

Normal operation.

All slave devices in the scanlist table are communicating normally with the module.

None.

The channel is enabled but no Flashing Green The two-digit numeric display for the channel indicates an error code that provides more communication is occurring. information about the condition of the channel.

Configure the scanlist table for the channel to add devices.

Flashing Red

The two-digit numeric display for the channel At least one of the slave devices Examine the failed device and the scanlist table for accuracy. displays an error code that provides more in the module’s scanlist table information about the condition of the channel. has failed to communicate with the module.

Red

The communication channel has failed. The two The module may be defective. digit numeric display for the channel displays an error code that provides more information about the condition of the channel.

Numeric Display Code Summary

Reset module. If failures continue, replace module.

The 1747-SDN module uses numeric codes to display diagnostic information about its status. The display flashes at one second intervals. The following table summarizes the meanings of the numeric codes.

Numeric Display

Top part of module.

Publication 1747-UM655B-EN-P - June 2007

Page 91

Troubleshooting

91

Numeric Display Numeric Code

Description

Corrective Action

0…63

Normal operation. The numeric display indicates the 1747-SDN module’s node address on the DeviceNet network.

None.

65

Normal operation when AutoScan is enabled.

None.

70

Module failed Duplicate Node Address check.

Change the module channel address to another available one. The node address you selected is already in use on that channel.

71

Illegal data in scanlist table (node number alternately flashes).

Reconfigure the scanlist table and remove any illegal data.

72

Slave device stopped communicating (node number alternately flashes).

Inspect the field devices and verify connections.

73

Device’s identity information does not match electronic key in scanlist table entry.

Verify that the correct device is at this node number. Make sure that the device at the scrolling node address matches the desired electronic key (vendor, product code, product type).

74

Data overrun on port detected.

Modify your configuration and check for invalid data. Check network communication traffic.

75

No traffic from other modules detected on the network.

Check the network configuration. (Scanlist may be empty.)

76

No direct network traffic for module detected.

None. The module hears other network communication.

77

Data size expected by the device does not match scanlist entry.

Reconfigure your module for the correct transmit and receive data sizes.

78

Slave device in scanlist table does not exist.

Add the device to the network, or delete the scanlist entry for that device.

79

Module has failed to transmit a message.

Make sure that your module is connected to a valid network. Check for disconnected cables.

80

Module is in Idle mode.

Put controller in Run mode. Enable Run bit in module command register.

81

Module is in Fault mode.

Check Module Command Register for fault bit set.

82

Error detected in sequence of fragmented I/O messages from device.

Check scanlist table entry for slave device to make sure that input and output data lengths are correct. Check slave device configuration.

83

Slave device is returning error responses when module attempts to communicate with it.

Check accuracy of scanlist table entry. Check slave device configuration. Slave device may be in another master’s scanlist. Reboot slave device.

84

Module is initializing the DeviceNet network.

None. This code clears itself once module attempts to initialize all slave devices on the network.

85

Data size was incorrect for this device at runtime.

Slave device is transmitting incorrect length data. Verify device is not configured for variable poll connection size. Try replacing the device.

Publication 1747-UM655B-EN-P - June 2007

Page 92

92

Troubleshooting

Numeric Display Numeric Code

Description

Corrective Action

86

Device is producing zero length data (idle state) while module is in Run mode.

Check device configuration and slave node status.

87

The primary owner has not allocated the slave.

Put the primary owner online.

88

The connection choices (polled, strobed) between the Reconfigure the shared input-only connection's choices to primary connection and the shared input only connection do be the same as, or a subset of, the primary connection's not match. choices.

89

Slave device initialization using Auto Device Replacement parameters failed.

Put the slave device into configurable mode. Check the slave's EDS file, if the slave is configured offline. Check to see if the slave device has been replaced with an incompatible device.

90

User has disabled communication port.

Check Module Command Register for DISABLE bit set.

91

Bus-off condition detected on comm port. Module is detecting communication errors.

Check DeviceNet connections and physical media integrity. Check system for failed slave devices or other possible sources of network interference.

92

No network power detected on communication port.

Provide network power. Make sure that module drop cable is providing network power to module comm port.

95

Application FLASH update in progress.

None. Do not disconnect the module while application FLASH is in progress. You will lose any existing data in the module’s memory.

97

Module operation halted by user command.

Check Module Command Register for HALT bit set.

98

Unrecoverable firmware failure.

Service or replace your module.

99

Unrecoverable hardware failure.

Service or replace your module.

E2

RAM test failure.

Service or replace your module.

E4

Lost power during FLASH upgrade.

Service or replace your module.

E5

No boot or main code.

Service or replace your module.

E9

Module memory has been flushed for factory default settings.

Cycle module power to recover.

Publication 1747-UM655B-EN-P - June 2007