For the Allen-Bradley 1747-SDN
Page 93
Chapter
8
DeviceNet Explicit Messaging
DeviceNet Explicit Message Instruction Overview
The DeviceNet Explicit Message (DEM) instruction allows generic Common Industrial Protocol (CIP) commands to be initiated to devices, such as drives, communicating on DeviceNet networks. This instruction requires RSLogix 500 software, version 7.10 or later, for programming. The DEM instruction utilizes the explicit message capability built into the 1747-SDN DeviceNet scanner module. While not adding any additional capability over what already exists in the scanner module, the DEM instruction greatly simplifies the programming, configuration, monitoring, and troubleshooting of explicit messages on the DeviceNet network. Unlike I/O configured in the scanner module’s scanlist, which is updated on a continual basis, explicit messages allow data to be sent and received on an as-needed basis, minimizing network traffic. For instance, you may only want to write configuration parameters to a drive once at machine start-up time. The DEM instruction can be used with any SLC 5/03, SLC 5/04, or SLC 5/05 processor that is at OS firmware level Series C, FRN 10 or later. The DEM instruction uses an integer control block for storing the instruction parameters and a configuration setup screen, similar to the MSG instruction. The CIP commands consist of a Service Code; the object Class, Instance, and Attribute; and Send and Receive Data (if required for the selected Service Code). The setup dialog provides a list of standard CIP Services to select from, including: • Read Assembly. • Write Assembly. • Read Parameter. • Write Parameter. • Generic Get Attribute Single. • Generic Set Attribute Single. In addition, a Custom setting lets you enter any Service Code. Send data and receive data are stored in separate data table files.
93
Publication 1747-UM655B-EN-P - June 2007
Page 94
94
DeviceNet Explicit Messaging
DeviceNet Explicit Message (DEM)
This is an output instruction that lets you initiate unconnected CIP Generic messages via a 1747-SDN module installed in the local chassis. These messages can be initiated to any node on the same DeviceNet network as the 1747-SDN module, as long as the node is in the scanner’s scanlist. The scanner can be in either Idle mode or Run mode. Each module can process only one DEM instruction at a time. The instruction is similar in operation to a standard MSG instruction.
DEM Instruction Parameters Enter the following parameters when programming this instruction: • Control Block is an integer file address that you select. It is a block of words, containing the status bits and other data associated with the DEM instruction. It also contains the Send and Receive data. • Control Block Length is a display-only field that indicates how many integer file words are being used by the control block. For the DEM instruction, the length is always 70 words.
DEM Instruction Setup Screen Parameters The following sections provide parameters for the DEM instruction setup screens.
Parameters for This Controller on the General Tab • 1747-SDN Slot This pull-down menu lists all of the local slots that contain DeviceNet scanner (1747-SDN) modules within the I/O Configuration. Select the slot number of the particular module that this explicit message will be initiated through. • Size in Send Data (Bytes) This field defines how many bytes of data are sent along with this explicit message command. If unsure of how much data will be sent, you may select up to the maximum size of 52 bytes when defining the instruction, and then reduce the size later based on experience.
Publication 1747-UM655B-EN-P - June 2007
Page 95
DeviceNet Explicit Messaging
95
Parameters for Target Device on the General Tab • Message Timeout(x1 sec) The amount of time in seconds that the processor will wait for a reply from the scanner to the explicit message command. Range is 0, 2…255. Like the Message Timeout in a standard MSG instruction, a value of 0 disables the Message Timeout and a value of 1 second gets bumped to 2 seconds upon instruction execution. If the built-in Message Timeout is disabled, user-programmed timeout logic must be included to avoid a message lockup in the case where a reply is lost. • DeviceNet Addr (dec) The target DeviceNet node address. Valid range is 0…63. If you enter in the local scanner’s DeviceNet node address, the command is executed by the local scanner. • Service This pull-down menu lets you select services based on name rather than Service Code. The Custom service lets you enter in any Service Code in the hexadecimal range of 1…7F. The services listed in the pull-down menu are: – Read Assembly. – Write Assembly. – Write Output Point. – Read Output Point. – Read Input Point. – Read Parameter. – Write Parameter. – Read Analog Input. – Write Analog Output. – Generic Get Attribute Single. – Generic Set Attribute Single. – Reset Identity Object. – Custom. • Service Code (hex) This field is read-only unless the Custom Service is selected. Possible Service Codes are 1…7F (hex). See Volume 1 of the CIP Common Specification, Appendix A, for the list of valid explicit messaging Service Codes.
Publication 1747-UM655B-EN-P - June 2007
Page 96
96
DeviceNet Explicit Messaging
• Class (hex)/(dec) Possible Classes are 0…FF (hex). See Volume 1 of the CIP Common Specification for the list of defined Classes. You may either enter in a hexadecimal Class value in the (hex) field or a decimal Class value in the (dec) field. • Instance (hex)/(dec) Possible Instances are 0…FFFF (hex). See Volume 1 of the CIP Common Specification for the list of valid Instances for each Class. You may either enter in a hexadecimal Instance value in the (hex) field or a decimal Instance value in the (dec) field. • Attribute (hex)/(dec) Possible Attributes are 0…FF (hex). See Volume 1 of the CIP Common Specification for the list of valid Attributes for each Class. You may either enter in a hexadecimal Attribute value in the (hex) field or a decimal Attribute value in the (dec) field. Note that if the value of the Attribute is set to 0, the DeviceNet scanner does not transmit an Attribute byte. Some Service Codes require that a zero-value Attribute byte be transmitted. For these Service Codes, the first byte of the Send Data must be set to zero and the Size of Send Data (Bytes) must include this additional byte.
Definitions for Message Status Bits on the General Tab The table below lists the various status bits associated with the DEM instruction as displayed in the DEM instruction setup screen. DEM Instruction Setup Screen Status Bits
Publication 1747-UM655B-EN-P - June 2007
Bit Definition
Bit Mnemonic
Bit Address
Abort
AB
08
Error
ER
12
Page 97
DeviceNet Explicit Messaging
97
DEM Instruction Setup Screen Status Bits Bit Definition
Bit Mnemonic
Bit Address
Done
DN
13
Enabled
EN
15
Waiting for slot
WS
10
• Abort bit AB (word 0, bit 8) lets you abort an executing DEM instruction by setting this bit. The ER bit will be set as soon as the AB bit is set. This bit is reset the next time the message rung goes from false to true. • Error bit ER (word 0, bit 12) is set when the message has failed to complete successfully. This bit is reset the next time the message rung goes from false to true. Do not set or reset this bit. It is informational only. • Done bit DN (word 0, bit 13) is set when the message has completed successfully. This bit is reset the next time the message rung goes from false to true. Do not set or reset this bit. It is informational only. • Enabled bit EN (word 0, bit 15) is set after the message rung goes from false to true AND the module accepts this message because it is not currently processing any other explicit messages. (The module can process only one DEM instruction at a time.) If the message rung goes false before the module accepts this message, then the enable bit will remain off and the message will not be executed. This bit is reset when the message has completed with either the Done bit set or the Error bit set and the message rung goes false. If the message rung conditions remain true, you may retrigger the message instruction by resetting this bit after either the ER or DN bit has been set, indicating that the previous execution has completed. • Waiting for Slot bit WS (word 0, bit 10) is set when the message rung goes from false to true, but the module is still processing another DEM instruction. To be sure that this message gets processed, you must leave the message rung conditions true until the WS bit is reset and the EN bit is set, indicating that the module has accepted this message for processing. Do not set or reset this bit. It is informational only.
Publication 1747-UM655B-EN-P - June 2007
Page 98
98
DeviceNet Explicit Messaging
Scanner Status, Error, and Error Description on the General Tab The error code displays the explicit message status returned by the module. An error code of 01h means Transaction completed successfully. DEM Instruction Scanner Codes Scanner Code
Description of Scanner Status
2H
Transaction in progress.
3H
Slave not in scanlist.
4H
Slave offline.
5H
DeviceNet port disabled/offline.
6H
Transaction TXID unknown.
7H
Slave not responding to explicit request.
8H
Invalid command code.
9H
Scanner out of buffers.
10H
Another transaction in progress.
11H
Could not connect to slave device.
12H
Response data too large for block.
13H
Invalid port.
14H
Invalid size specified.
15H
Connection busy.
All error codes listed above result in an error code of 2. Complete List of Valid DEM Error Codes Error Code
Description of Error Condition
0
No error.
1
Timeout error. DeviceNet explicit message timed out by processor.
2
Scanner error. See Scanner Status.
3
User error. DeviceNet explicit message aborted by user.
For error code 4, the error description displays the CIP response error code and description as documented in the CIP Response Error Codes table.
Publication 1747-UM655B-EN-P - June 2007
Page 99
DeviceNet Explicit Messaging
99
CIP Response Error Codes Numeric Code
Name
Description
02H
Resource unavailable
A needed resource was not available
08H
Service unsupported
Service is not defined or implemented for this class/instance
09H
Invalid attribute value
Data is invalid for the specified attribute
0BH
Already in requested state
Object is in the requested state - redundant request
0CH
Object state conflict
Not allowed with object in present state
0EH
Attribute cannot be set
Read-only attribute
0FH
Privilege violation
A permission/privilege check failed
10H
Device state conflict
Not allowed with device in present state
11H
Reply too big
Reply larger than buffer allocated when connection was established
13H
Too little data
Request included insufficient data
14H
Attribute not supported
Attribute number is incorrect
15H
Too much data
Request included extra data
16H
Object does not exist
Class/instance numbers are incorrect
18H
No stored attribute data
Attribute data was not saved prior to this request
19H
Store operation failure
Attribute data was not successfully saved
1FH
Vendor-specific error
Second byte may offer details - refer to vendor documentation
20H
Invalid parameter
Parameter associated with request is invalid
D0H
Reserved and service-specific errors
Used only when none of the standard error codes supplemented by the second byte accurately describes the problem
FFH
Any time the error code is non-zero, the DEM error (ER) bit is set.
Publication 1747-UM655B-EN-P - June 2007
Page 100
100
DeviceNet Explicit Messaging
Send Data Tab The Send Data Tab provides a convenient way of viewing and entering in data to be sent along with the explicit message command. The data is shown in byte format with a selectable radix of either decimal or hex/BCD. The display shows only the number of words that are defined in the Size of Send Data (Bytes) field, starting with the low byte of the first word. If the Size of Send Data is zero, then no data is displayed. You can also change the data being viewed, but only when offline or during an online edit. Click on the data and enter in a byte value based on the current radix (0…255 for decimal and 0 to FF for hex/BCD). The changed data gets copied to the DEM control block when the rung is accepted. To update the Send Data display with the current values stored in the DEM control block, click Refresh.
Receive Data Tab The Receive Data Tab provides a convenient way of viewing the data that is returned by the target device in response to the explicit message command sent. The data is shown in byte format with a selectable radix of either decimal or hex/BCD. The display shows 58 bytes of receive data, starting with the low byte of the first word. To update the Receive Data display with the current values stored in the DEM control block, click Refresh.
Publication 1747-UM655B-EN-P - June 2007
Page 101
DeviceNet Explicit Messaging
101
Control Block Layout The control block layout is shown below.
SLC 5/0x DeviceNet Explicit Message (DEM) Control Block Structure 15 Word 0
14
EN
13
12
DN
ER
Word 1
11
10 WS
09
08
07
06
05
04
AB
Error Code
IMR
Message Timeout Preset
Word 2
Message Timeout Accumulator
Word 3
Message Timer Scaled Zero
Word 4
Unused
Word 5
Unused
Word 6
Transaction ID
Scanner Command
Word 7
Scanner Port (always 0x00)
Size of Send Data (in bytes)
Word 8
Service Code
Target MAC ID
Word 9
Reserved (not transmitted)
Class
03
02
01
0
Word 10 Instance Word 11 Reserved (not transmitted)
Attribute (optional)
Word 12 Transaction Send Data …
(next 26 words)
Word 37 Word 38 Transaction ID
Scanner Status
Word 39 Scanner Port (always 0x00)
Size of Reply Data (in bytes)
Word 40 Reply Service Code
Target MAC ID
Word 41 Transaction Reply/Receive Data …
(next 29 words)
Word 69
Publication 1747-UM655B-EN-P - June 2007
Page 102
102
DeviceNet Explicit Messaging
Publication 1747-UM655B-EN-P - June 2007