The text of a manual · part 10 of 12
ControlLogix DeviceNet Interface Module 1756-DNB User Manual: 7 - Troubleshooting
Pages 81 to 86 of 96, from ControlLogix DeviceNet Interface Module 1756-DNB User Manual
The original document is the PDF (1.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1756-DNB
Page 81
Chapter
7
Troubleshooting
What This Chapter Contains This chapter describes the diagnostics provided by the LED diagnostic indicators on the 1756-DNB module’s front panel. For information about Power-Up Cycle Diagnostics Node Address/Status Indicator Interpreting the Three LED Status Indicators MOD/NET Status Indicator IO Status Indicator OK Status Indicator
TIP
Power-Up Cycle Diagnostics
See page: 7-1 7-2 7-4 7-4 7-5 7-6
The 1756-DNB module (firmware major revision 3) provides extended status information via the RSLogix 5000 Online Help menu. Access the Online Help for “Troubleshooting using the software” to obtain this information.
When you apply chassis power, check the module’s alphanumeric indicators to determine if the module is operating. The alphanumeric indicators will display the following: 1. Firmware major revision (01 through 128) 2. Firmware minor revision (01 through 255) 3. Baud rate (125, 250, or 500) Alphanumeric Display
4. MAC ID (00 to 63)
MOD/NET IO
1
OK
Publication 1756-6.5.19 - May 2000
Page 82
7-2
Troubleshooting
Node Address/Status Indicator
After power up the 1756-DNB interface module uses the alphanumeric display as a node address/status indicator that displays numeric codes providing diagnostic information about the module. The display flashes at approximately 1 second intervals. The following table summarizes the meanings of the numeric codes. Node Address/Status Indicator Numeric Description Code
Action
Network Normal operation. The numeric display Do nothing. Address matches the module’s node address on Displays the DeviceNet network. 0 to 63 70
Module failed Duplicate Node Address Change the module address to another check available one. The node address you selected is already in use on that network.
71
Illegal data in scan list table (node number alternately flashes).
72
Slave device stopped communicating Inspect the field devices and verify (node number alternately flashes). connections.
73
Device’s identity information does not match electronic key in scan list table entry (node number alternately flashes).
Verify that the correct device is at this node number. Make sure that the device at the flashing node address matches the desired electronic key (vendor, product code, product type).
74
Data overrun on port detected.
Modify your configuration and check for invalid data. Check network communication traffic.
75
No scan list is active in the module.
Enter a scan list.
76
No direct network traffic for module detected.
None. The module hears other network communication.
77
Data size expected by the device does Reconfigure your module for the not match scan list entry (node number correct transmit and receive data alternately flashes). sizes.
78
Slave device in scan list table does not Add the device to the network, or exist (node number alternately delete the scan list entry for that flashes). device.
79
Module has failed to transmit a message.
Make sure that your module is connected to a valid network.
80
Module is in IDLE mode.
Put controller in RUN mode. Enable RUN bit in module command register.
81
Module is in FAULT mode.
Check Module Command Register for fault bit set.
82
Error detected in sequence of Check scan list table entry for slave fragmented I/O messages from device device to make sure that input and (node number alternately flashes). output data lengths are correct. Check slave device configuration.
Reconfigure the scan list table and remove any illegal data.
Check for disconnected cables.
Publication 1756-6.5.19 - May 2000
Page 83
Troubleshooting
7-3
Node Address/Status Indicator Numeric Description Code
Action
83
Slave device is returning error responses when module attempts to communicate with it (node number alternately flashes).
Check accuracy of scan list table entry. Check slave device configuration. Slave device may be in another master’s scan list. Reboot slave device.
84
Module is initializing the DeviceNet network.
None. This code clears itself once module attempts to initialize all slave devices on the network.
85
Data size larger than 255 bytes (node Configure the device for a smaller data number alternately flashes). size.
86
Device is producing zero length data (idle state) while module is in Run Mode.
90
User has disabled communication port. Check Module Command Register for disable bit set.
91
Bus off condition detected on comm port. Module is detecting communication errors.
92
No network power detected on comm Provide network power. Make sure port. that module drop cable is providing network power to module comm port.
95
Application FLASH update in progress. None. Do not disconnect the module while application FLASH is in progress. You will lose any existing data in the module’s memory.
97
Module operation halted by user command.
Check device configuration and slave node status.
Check DeviceNet connections and physical media integrity. Check system for failed slave devices or other possible sources of network interference.
Check Module Command Register for halt bit set.
Publication 1756-6.5.19 - May 2000
Page 84
7-4
Troubleshooting
Interpreting the Three LED Status Indicators
The three LED status indicators on the module provide information about the network and its connections. The tables on pages 7-4 through 7-6 outline the indicator condition and the corresponding status, and explain what each condition means.
MOD/NET Status Indicator This bi-color (green/red) LED provides limited device and communication status. The combined Module/Network (or Mod/Net) Status LED indicates whether or not the device has power and is operating properly. MOD/NET Status Indicator Condition
Status
Indicates off not powered/not online
Device is not online. The device has not completed the Dup_MAC_ID test yet. The device may not be powered.
green device operational
Device is operating in a normal condition.
flashing green(1)
device in standby (device needs commissioning)
Device needs commissioning due to missing, incomplete, or incorrect configuration. Device may be in the standby state. Refer to the DeviceNet Specification, Volume II, Identity Object.
flashing red(1) minor fault
Recoverable fault.
red unrecoverable fault
Device has an unrecoverable fault and may need to be replaced.
flashing red/ green device self testing
Device is in self test. Refer to the DeviceNet Specification, Volume II, Identity Object.
(1)
Publication 1756-6.5.19 - May 2000
The flash rate of the LED is approximately 1 flash per second. The LED should be on for approximately 0.5 seconds and off for approximately 0.5 seconds.
Page 85
Troubleshooting
7-5
IO Status Indicator This bi-color (green/red) LED indicates the status of the communication link. IO Status Indicator Condition
Status
Indicates off not powered, not online
Device is not online. The device has not completed the Dup_MAC_ID test yet. The device may not be powered; look at the Module Status LED.
flashing green(1)
online, not connected
Device is online, but has no connections in the established state. The device has passed the Dup_MAC_ID test, is online, but has no established connections to other nodes. For a Group 2 Only device, it means that this device is not allocated to a master. For a UCMM capable device, it means that the device has no established connections.
green link okay, online, connected The device is online and has connections in the established state. For a Group 2 Only device, it means that the device is allocated to a master. For a UCMM capable device, it means that the device has one or more established connections.
flashing red(1) connection time-out
One or more I/O connections are in the timed-out state.
red
Failed communication device. The device has detected an error that has rendered it incapable of communicating on the network (Duplicate MAC ID or Bus-off).
(1)
critical link failure
The flash rate of the LED is approximately 1 flash per second. The LED should be on for approximately 0.5 seconds and off for approximately 0.5 seconds.
Publication 1756-6.5.19 - May 2000
Page 86
7-6
Troubleshooting
OK Status Indicator This bi-color (green/red) LED provides device status in the ControlLogix chassis. It indicates whether the device has power and is operating properly. OK Status Indicator Condition
Status
Indicates off no power
No power applied to device. Apply chassis power. Verify module is completely inserted into chassis and backplane.
green device operational
Device is operating in a normal condition. A controlling device has established connection to the module.
flashing green1 device in standby
The device is operating correctly; however, no controlling device has established connection to the module.
flashing red(1) minor fault
Recoverable fault. To recover, reconfigure the device, reset the device, or perform error recovery.
red
Device has an unrecoverable fault; repair or replace it; or device is in self test during power up.
(1)
Publication 1756-6.5.19 - May 2000 unrecoverable fault or device self testing
The flash rate of the LED is approximately 1 flash per second. The LED should be on for approximately 0.5 seconds and off for approximately 0.5 seconds.