ControlLogix DeviceNet Interface Module 1756-DNB User Manual: 3 - Hardware Setup

Pages 31 to 38 of 96, from ControlLogix DeviceNet Interface Module 1756-DNB User Manual

The original document is the PDF (1.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1756-DNB

Page 31

Chapter

3

Hardware Setup What This Chapter Contains This chapter describes how to set up the hardware for the example application. The following table describes what this chapter contains and where to find specific information. For information about

See page

Installing the 1770-KFD Communication Module

Installing the 1770-KFD Communication Module

3-1

Installing the Logix5550 Controller

3-2

Installing the 1756-DNB Interface Module

3-2

Installing a ControlNet, Ethernet, or DH+ Interface Module

3-3

Installing the RediSTATION Operator Interface

3-5

Installing the Series 9000 Photoeye

3-6

How Your Example System Will Look

3-7

Connect the RS-232 connector on the 1770-KFD interface module to one of the serial ports on your PC workstation (e.g., COM1). Connect the DeviceNet connector on the 1770-KFD module to a DeviceNet dropline or trunk cable. You can make the connection to the network in several ways; for example, using a DeviceNet Quad Tap (part no. 1492-DN3TW) as shown on page 3-7. to PC COM 1

1770-KFD RS-232 Interface Module DeviceNet Dropline or Trunk Cable

More

1

For detailed directions on how to install the 1770-KFD interface module, see the DeviceNet RS-232 Interface Module Installation Instructions, publication 1770-5.6.

Publication 1756-6.5.19 - May 2000

Page 32

3-2

Hardware Setup

Installing the Logix5550 Controller

Refer to the following illustration as you install the Logix5550 controller in the ControlLogix chassis.

a Align the circuit board with top and bottom guides in the chassis.

Important: For the example application, make sure you put the controller in slot 0 (the first slot from the left).

b Slide the module into the chassis. Make sure the module properly connects to the chassis backplane.

More

Installing the 1756-DNB Interface Module c The module is fully installed when it is flush with the power supply and other installed modules.

For detailed directions on how to install the controller, see the Logix5550 Controller User Manual, publication 1756-6.5.12.

For the example application, insert the 1756-DNB module into slot 1 (the second slot from the left).

41595

Publication 1756-6.5.19 - May 2000

Page 33

Hardware Setup

3-3

Refer to the following illustration as you connect the 1756-DNB module to the network.

10-position linear plug 1787-PLUGIOR

DeviceNet port connector DeviceNet drop line or trunk line

More

Installing a ControlNet, Ethernet, or DH+ Interface Module

For additional information about how to connect the 1756-DNB module to the network, see the ControlLogix DeviceNet Scanner Module Installation Instructions, publication 1756-5.66.

You cannot go online to the Logix5550 controller over the DeviceNet network. In order to download the example application program in chapter 6 you must use the controller’s RS-232 connector, or download over another network. Chapter 6 provides examples of downloading over ControlNet, Ethernet, and Data Highway Plus networks. To download over one of these networks you must have that network configured and running and one of the following interface modules installed in the ControlLogix chassis with the controller. For this network

Install this module

ControlNet

1756-CNB

Data Highway Plus

1756-DHRIO

Ethernet

1756-ENET

Install the module in any open slot in the ControlLogix chassis in the same way that you installed the controller and 1756-DNB module. Then connect the module to the appropriate network.

Publication 1756-6.5.19 - May 2000

Page 34

3-4

Hardware Setup

More

Refer to the following publications for more information on installing these modules: Publication

Publication Number

ControlLogix ControlNet Bridge Installation Instructions

1756-5.32

ControlLogix DHRIO Module Installation Instructions

1756-5.4

ControlLogix Ethernet Module Installation Instructions

1756-5.3

When you have completed installation, your ControlLogix chassis should resemble the following illustration:

Logix5550 Controller (1765-L1) 1756-DNB module

Publication 1756-6.5.19 - May 2000

CNB, DHRIO, or ENET interface modules

Page 35

Hardware Setup

Installing the RediSTATION Operator Interface

3-5

Begin installing the RediSTATION by removing the six screws fastening the cover and setting the DIP switches inside as follows: Set this position

To this value:

1 2 3 4 5 6

1 1 1 0 0 0

On On On (node Off address1) Off Off

7 8

0 1

Off (data On rate2)

9 10

0 0

Off Off

The DeviceNet address is 000111 (node 7). The data rate is 10 (500k bps). The output fault rate is 0 (outputs turned off). The output flash rate is 0 (outputs tuned off). 1 2

More

See Chapter 2 of the RediSTATION Operator Interface User Manual, publication 2705-804, for complete information about setting the DIP switches to configure the node address, data rate, output flash rate, and output fault state. Refer to the following illustration as you connect the RediSTATION to the network. TIP

You do not need to disconnect incoming power from the DeviceNet network before connecting the RediSTATION.

The DeviceNet cable connects directly to the mini connector on the top of the RediSTATION enclosure or through the conduit opening (open style).

DeviceNet Cable mini connector open style

Publication 1756-6.5.19 - May 2000

Page 36

3-6

Hardware Setup

Installing the Series 9000 Photoeye

Connect the photoeye to the network and configure the photoeye as follows: • Node Address: 9 • Operating Mode: Light Operate (default) • Baud Rate: 500 kb Top View of Series 9000 Photoeye Programming Pushbutton Sensitivity Adjustment

Yellow - Output Green - Margin Red/Green - Status

More

Publication 1756-6.5.19 - May 2000

For detailed directions, see the instructions that came with your photoeye.

Page 37

Hardware Setup

How Your Example System Will Look

3-7

When you have finished installing all the devices, your example system should appear similar to the one shown below.

PC running Windows NT 4.0 with RSNetWorx RSLinx, and RSLogix 5000 software

Series 9000 Photoelectric Sensor Node 9

PC Serial Port

1770-KFD Communications Module 1492-DN3TW Quad Tap Node 0

Node 62

1756-DNB module

24V Node 7

ControlLogix Chassis

Logix5550 Controller (1756-L1)

IMPORTANT

What’s Next?

CNB, DHRIO, or ENET interface modules

RediSTATION Operator Interface

Make sure each end of your DeviceNet trunk cable is properly terminated with a resistor. Refer to the DeviceNet Cable Planning and Installation Manual, publication DN-6.7.2 for information.

The next step is to configure the 1756-DNB module and perform I/O data mapping using RSNetWorx for DeviceNet software.

Publication 1756-6.5.19 - May 2000

Page 38

3-8

Hardware Setup

Publication 1756-6.5.19 - May 2000