For the Allen-Bradley 1756-DNB
Page 31
Chapter
3
Hardware Setup What This Chapter Contains This chapter describes how to set up the hardware for the example application. The following table describes what this chapter contains and where to find specific information. For information about
See page
Installing the 1770-KFD Communication Module
Installing the 1770-KFD Communication Module
3-1
Installing the Logix5550 Controller
3-2
Installing the 1756-DNB Interface Module
3-2
Installing a ControlNet, Ethernet, or DH+ Interface Module
3-3
Installing the RediSTATION Operator Interface
3-5
Installing the Series 9000 Photoeye
3-6
How Your Example System Will Look
3-7
Connect the RS-232 connector on the 1770-KFD interface module to one of the serial ports on your PC workstation (e.g., COM1). Connect the DeviceNet connector on the 1770-KFD module to a DeviceNet dropline or trunk cable. You can make the connection to the network in several ways; for example, using a DeviceNet Quad Tap (part no. 1492-DN3TW) as shown on page 3-7. to PC COM 1
1770-KFD RS-232 Interface Module DeviceNet Dropline or Trunk Cable
More
1
For detailed directions on how to install the 1770-KFD interface module, see the DeviceNet RS-232 Interface Module Installation Instructions, publication 1770-5.6.
Publication 1756-6.5.19 - May 2000
Page 32
3-2
Hardware Setup
Installing the Logix5550 Controller
Refer to the following illustration as you install the Logix5550 controller in the ControlLogix chassis.
a Align the circuit board with top and bottom guides in the chassis.
Important: For the example application, make sure you put the controller in slot 0 (the first slot from the left).
b Slide the module into the chassis. Make sure the module properly connects to the chassis backplane.
More
Installing the 1756-DNB Interface Module c The module is fully installed when it is flush with the power supply and other installed modules.
For detailed directions on how to install the controller, see the Logix5550 Controller User Manual, publication 1756-6.5.12.
For the example application, insert the 1756-DNB module into slot 1 (the second slot from the left).
41595
Publication 1756-6.5.19 - May 2000
Page 33
Hardware Setup
3-3
Refer to the following illustration as you connect the 1756-DNB module to the network.
10-position linear plug 1787-PLUGIOR
DeviceNet port connector DeviceNet drop line or trunk line
More
Installing a ControlNet, Ethernet, or DH+ Interface Module
For additional information about how to connect the 1756-DNB module to the network, see the ControlLogix DeviceNet Scanner Module Installation Instructions, publication 1756-5.66.
You cannot go online to the Logix5550 controller over the DeviceNet network. In order to download the example application program in chapter 6 you must use the controller’s RS-232 connector, or download over another network. Chapter 6 provides examples of downloading over ControlNet, Ethernet, and Data Highway Plus networks. To download over one of these networks you must have that network configured and running and one of the following interface modules installed in the ControlLogix chassis with the controller. For this network
Install this module
ControlNet
1756-CNB
Data Highway Plus
1756-DHRIO
Ethernet
1756-ENET
Install the module in any open slot in the ControlLogix chassis in the same way that you installed the controller and 1756-DNB module. Then connect the module to the appropriate network.
Publication 1756-6.5.19 - May 2000
Page 34
3-4
Hardware Setup
More
Refer to the following publications for more information on installing these modules: Publication
Publication Number
ControlLogix ControlNet Bridge Installation Instructions
1756-5.32
ControlLogix DHRIO Module Installation Instructions
1756-5.4
ControlLogix Ethernet Module Installation Instructions
1756-5.3
When you have completed installation, your ControlLogix chassis should resemble the following illustration:
Logix5550 Controller (1765-L1) 1756-DNB module
Publication 1756-6.5.19 - May 2000
CNB, DHRIO, or ENET interface modules
Page 35
Hardware Setup
Installing the RediSTATION Operator Interface
3-5
Begin installing the RediSTATION by removing the six screws fastening the cover and setting the DIP switches inside as follows: Set this position
To this value:
1 2 3 4 5 6
1 1 1 0 0 0
On On On (node Off address1) Off Off
7 8
0 1
Off (data On rate2)
9 10
0 0
Off Off
The DeviceNet address is 000111 (node 7). The data rate is 10 (500k bps). The output fault rate is 0 (outputs turned off). The output flash rate is 0 (outputs tuned off). 1 2
More
See Chapter 2 of the RediSTATION Operator Interface User Manual, publication 2705-804, for complete information about setting the DIP switches to configure the node address, data rate, output flash rate, and output fault state. Refer to the following illustration as you connect the RediSTATION to the network. TIP
You do not need to disconnect incoming power from the DeviceNet network before connecting the RediSTATION.
The DeviceNet cable connects directly to the mini connector on the top of the RediSTATION enclosure or through the conduit opening (open style).
DeviceNet Cable mini connector open style
Publication 1756-6.5.19 - May 2000
Page 36
3-6
Hardware Setup
Installing the Series 9000 Photoeye
Connect the photoeye to the network and configure the photoeye as follows: • Node Address: 9 • Operating Mode: Light Operate (default) • Baud Rate: 500 kb Top View of Series 9000 Photoeye Programming Pushbutton Sensitivity Adjustment
Yellow - Output Green - Margin Red/Green - Status
More
Publication 1756-6.5.19 - May 2000
For detailed directions, see the instructions that came with your photoeye.
Page 37
Hardware Setup
How Your Example System Will Look
3-7
When you have finished installing all the devices, your example system should appear similar to the one shown below.
PC running Windows NT 4.0 with RSNetWorx RSLinx, and RSLogix 5000 software
Series 9000 Photoelectric Sensor Node 9
PC Serial Port
1770-KFD Communications Module 1492-DN3TW Quad Tap Node 0
Node 62
1756-DNB module
24V Node 7
ControlLogix Chassis
Logix5550 Controller (1756-L1)
IMPORTANT
What’s Next?
CNB, DHRIO, or ENET interface modules
RediSTATION Operator Interface
Make sure each end of your DeviceNet trunk cable is properly terminated with a resistor. Refer to the DeviceNet Cable Planning and Installation Manual, publication DN-6.7.2 for information.
The next step is to configure the 1756-DNB module and perform I/O data mapping using RSNetWorx for DeviceNet software.
Publication 1756-6.5.19 - May 2000
Page 38
3-8
Hardware Setup
Publication 1756-6.5.19 - May 2000