Page 39

Chapter

4

Configuring the DeviceNet Network

What This Chapter Contains This chapter describes how to configure the DeviceNet network using RSLinx and RSNetWorx for DeviceNet software. The following table describes what this chapter contains and where to find specific information.

Installing the Software

For information about

See page

Installing the Software

4-1

Using RSLinx to Configure the DeviceNet Driver

4-2

Using RSNetWorx to Configure the 1756-DNB Module Scanlist

4-4

Setting Up an Online Connection

4-4

Setting the 1756-DNB Node Address

4-6

Configuring the Scanlist

4-9

Verifying the RediSTATION Configuration

4-14

AutoMapping the Devices into the Scanlist

4-15

Saving the DeviceNet Configuration

4-18

For both the RSLinx and RSNetWorx software. 1. Insert the installation CD in the CD-ROM drive. Note: The CD-ROM supports Windows Autorun. Once inserted into the CD-ROM drive, if you have Autorun configured, the installation will automatically start at the first setup screen. If Autorun is not configured for your CD-ROM drive, go to step 2. 2. From the Start menu, choose Run. You will see the Run pop-up window. 3. Type d:/setup (if it doesn’t appear automatically), where d: is your CD-ROM driver letter. 4. Click on OK. You will see the progress bar, followed by the welcome screen.

1

Publication 1756-6.5.19 - May 2000

Page 40

4-2

Configuring the DeviceNet Network

Using RSLinx to Configure the DeviceNet Driver

After you install the software, you use RSLinx to configure your DeviceNet driver and RSNetWorx for DeviceNet to configure the network. 1. Start RSLinx. The RSLinx main window will appear.

2. From the Communications menu, select Configure Drivers. The following window will appear.

3. Select DeviceNet Drivers from the above pull-down list and click on Add/New. You will see the following choices.

4. Select the Allen-Bradley 1770-KFD driver.

Publication 1756-6.5.19 - May 2000

Page 41

Configuring the DeviceNet Network

4-3

The 1770-KFD Driver Configuration window will appear. Your driver setup will vary according to your particular system setup (COM port, Data Rate, Node Address). Choose the appropriate settings for your system. We set the Serial Port Setup Data Rate to 500K for the example application.

5. Configure the driver using the example above as a guide and click on OK. The software will take a few seconds to configure the driver. When it is done the following prompt will appear:

6. Select the default driver name 1770-KFD-1 and click on OK. 7. Close RSLinx. You will use the driver you just configured to browse and configure the network with RSNetWorx for DeviceNet.

Publication 1756-6.5.19 - May 2000

Page 42

4-4

Configuring the DeviceNet Network

Using RSNetWorx to Configure the 1756-DNB Module Scanlist

Setting Up an Online Connection Follow the procedure below to set up the DeviceNet network using the 1770-KFD driver. 1. Start RSNetWorx.

2. From the File menu, select New. If you have RSNetWorx for ControlNet installed on your computer you may see the following window. Otherwise, proceed to step 4.

3. Highlight DeviceNet Configuration and click on OK. 4. Click on the Online button

Publication 1756-6.5.19 - May 2000 on the toolbar.

Page 43

Configuring the DeviceNet Network

4-5

A list of the available drivers in RSLinx will appear. (Your list may appear different from that shown below, depending upon the drivers you have installed on your system.)

5. Select the 1770-KFD-1, DeviceNet driver and click on OK. You will be prompted to upload or download devices before going online.

6. Click on OK to go online and upload the network. RSNetWorx for DeviceNet will begin browsing for network devices. When the software is finished browsing, the network displayed on your screen should look similar to the one shown below.

Publication 1756-6.5.19 - May 2000

Page 44

4-6

Configuring the DeviceNet Network

TIP

RSNetWorx for DeviceNet performs a one-shot browse when you go online or choose the browse feature. The software will poll for devices once and display the results. If a node which was online later goes offline, there will be no “live” indication in RSNetWorx. You must manually perform a browse to detect the missing node. To perform a manual browse, press the button.

Setting the 1756-DNB Node Address Once the devices are uploaded, their node addresses appear below their icons. For the example application, the 1756-DNB interface module should have a node address of 0 (or 00). If you need to change the module’s node address, use the following procedure. TIP

You can use this procedure to change the node address of other devices on the network (e.g., the Photoeye). You can also change the network data rate (baud rate) of some devices. Power must be recycled for baud rate changes to take effect.

If "00" appears to the right of the 1756-DNB icon and you do not need to change the node address of any other device, skip the remainder of this section and go to “Configuring the Scanlist” on page 4-9.

IMPORTANT

The network must not be active when performing node commissioning on the 1756-DNB module. Make sure the controller is in Program mode. (Note that this applies only to the 1756-DNB. You may commission other devices with the controller in Run mode.)

Publication 1756-6.5.19 - May 2000

Page 45

Configuring the DeviceNet Network

4-7

To change the node address of a device perform the following steps: 1. From the Tools menu select Node Commissioning. You will see the Node Commissioning window. Note: You can also use the Manual Configuration button on the front of the 1756-DNB module to change its node address and data rate. See the ControlLogix DeviceNet Scanner Module Installation Instructions for more information.

2. Click on the Browse button. You will see the Device Selection window.

3. Select the 1770-KFD driver (1770-KFD-1 above).

Publication 1756-6.5.19 - May 2000

Page 46

4-8

Configuring the DeviceNet Network

The devices on the network will appear in the right panel.

4. Select the device from the right panel. 5. Click on OK. You will see the Node Commissioning window with the current settings for the device. Your window will look similar to the one shown below.

6. In the New Device Settings: Node Address box, enter the new node address (e.g., a 0 as shown above). 7. Click on Apply. 8. Click on Exit to close the window.

Publication 1756-6.5.19 - May 2000

Page 47

Configuring the DeviceNet Network

4-9

Configuring the Scanlist 1. Double-click on the 1756-DNB module icon.

The following window will appear:

2. Select the Module tab. You will be prompted to upload or download the configuration.

3. Click on Upload.

Publication 1756-6.5.19 - May 2000