Page 48

4-10

Configuring the DeviceNet Network

After uploading the following window will appear:

4. Make sure the 1756-DNB module’s Slot number is correct. We used Slot 1 for the example application.

TIP

We used the Module Defaults for the other parameters. For an explanation of these parameters click on the Help button.

5. Select the Scanlist tab.

Publication 1756-6.5.19 - May 2000

Page 49

Configuring the DeviceNet Network

4-11

You will see Scanlist window with the RediSTATION and photoeye in the list of Available Devices.

6. For this example, uncheck the Automap on Add box, as shown above. You will do the mapping later. 7. Click on the double arrow button to add the photoeye and RediSTATION to the Scanlist. The photoeye and the RediSTATION will then appear in the Scanlist on the right side of the window.

Publication 1756-6.5.19 - May 2000

Page 50

4-12

Configuring the DeviceNet Network

8. Click on OK. You will be prompted to download the changes to the device (i.e., the scanner).

9. Click on Yes.

Verifying the Photoeye Configuration 1. Double-click on the 1756-DNB module icon and again select the Scanlist tab.

2. Double-click on the photoeye in the Scanlist.

Publication 1756-6.5.19 - May 2000

Page 51

Configuring the DeviceNet Network

4-13

The Edit I/O Parameters window will appear for the photoeye.

The I/O parameters define the configuration for the device in terms of how much and what data the device will exchange with the 1756-DNB module. By default, the photoeye will send 1 byte when it receives the strobe request. Recall from chapter 3 that the output of the photoeye will be returned in bit 0 of this byte. 3. Verify that the photoeye parameters are set as shown above. 4. Make any changes as necessary and click on OK. 5. Close the Edit I/O Parameters window for the photoeye.

Publication 1756-6.5.19 - May 2000

Page 52

4-14

Configuring the DeviceNet Network

Verifying the RediSTATION Configuration 1. Double-click on the RediSTATION in the Scanlist window. The Edit I/O Parameters window will appear for the RediSTATION.

2. Make sure that the Polled box is checked and that the Rx Size and Tx Size are each 1 byte. 3. Make any changes as necessary and click on OK. 4. Close the Edit I/O Parameters window for the RediSTATION.

Publication 1756-6.5.19 - May 2000

Page 53

Configuring the DeviceNet Network

4-15

AutoMapping the Devices into the Scanlist Follow the procedure below to automatically map the photoeye and RediSTATION to the Logix5550 controller. TIP

If you want to know how to map the devices manually, click on the Help button at the bottom of the screen and select “Map device input data manually".

1. Select the Input tab.

2. Highlight the RediSTATION and the photoeye as shown above and click on the AutoMap button.

Publication 1756-6.5.19 - May 2000

Page 54

4-16

Configuring the DeviceNet Network

The resulting device mapping will appear in the lower panel:

Slot 1 Double word 0 Photoeye inputs

RediSTATION inputs

I = Input

In chapter 3 the 1756-DNB module was installed in slot 1 in the ControlLogix chassis. In this example the inputs from the RediSTATION are mapped to double word 0 for slot 1 as bits 0-7 of the low word (L). Recall from chapter 2 that the START button is bit 1 and the STOP button is bit 0. Therefore, the addresses for the RediSTATION inputs are: START Local:1:I.Data[0].1 STOP

Local:1:I.Data[0].0

The input from the photoeye is mapped to double word 0 for slot 1 as bits 8-15 of the low word. Recall from chapter 3 that the input bit is bit 0. Therefore, the address of the photoeye input is: Local:1:I.Data[0].8 3. Note the addresses assigned to the START and STOP buttons and the photoeye in your system. You will use these addresses in the example application program. 4. Select the Output tab.

Publication 1756-6.5.19 - May 2000

Page 55

Configuring the DeviceNet Network

4-17

You will see the following window:

5. Highlight the RediSTATION and click on the AutoMap button. The output mapping of the RediSTATION will appear in the lower panel of the window.

Slot 1 Double word 0

After mapping, the RediSTATION’s output address will appear here.

O = Output

In this example, the output to the RediSTATION is mapped to double word 0 for slot 1 as the lower byte (bits 0-7) of the low word. Recall from chapter 2 that the indicator light is output bit 0. Therefore, the address for the RediSTATION indicator light is: Local:1:O.Data[0].0 6. Note the address assigned to this output in your system. You will use this address in the example application program.

Publication 1756-6.5.19 - May 2000

Page 56

4-18

Configuring the DeviceNet Network

7. Click on OK. You will be prompted to download the changes to the device (the scanner):

8. Click on Yes.

Saving the DeviceNet Configuration 1. From the File menu, select Save As.

2. Save your DeviceNet configuration using an appropriate file name e.g., 1756-DNB). 3. Close or minimize RSNetWorx for DeviceNet.

What’s Next?

Publication 1756-6.5.19 - May 2000

The next chapter describes how to configure a DeviceNet network remotely from other networks: ControlNet, Ethernet, and Data Highway Plus.