The text of a manual · part 8 of 12
ControlLogix DeviceNet Interface Module 1756-DNB User Manual: 5 - Configuring DeviceNet From Another Network
Pages 57 to 66 of 96, from ControlLogix DeviceNet Interface Module 1756-DNB User Manual
The original document is the PDF (1.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1756-DNB
Page 57
Chapter
5
Configuring DeviceNet From Another Network
What This Chapter Contains This chapter describes how to configure a DeviceNet network remotely from another network. It provides examples of configuring the DeviceNet network from ControlNet, Ethernet, and Data Highway Plus networks. We assume that you have previously set up the network you will use to communicate with the DeviceNet network and that you have installed the appropriate interface hardware. For these examples we set up a 7-slot ControlLogix chassis with the following modules: Slot 0
1756-L1, Logix5550 controller
Slot 1
1756-DNB, DeviceNet Interface module
Slot 2
1756-DHRIO, Data Highway Plus Interface module
Slot 3
1756-CNB, ControlNet Interface module
Slot 4
1756-ENET, Ethernet Interface module
The following table describes what this chapter contains and where to find specific information. Refer to the section(s) that apply to your installation. For information about
1
See page
Where to Find More Information
5-2
Configuring DeviceNet from a ControlNet Network
5-2
Configuring DeviceNet from an Ethernet Network
5-5
Configuring DeviceNet From a Data Highway Plus Network
5-8
Publication 1756-6.5.19 - May 2000
Page 58
5-2
Configuring DeviceNet From Another Network
Where to Find More Information For information about:
More
Refer to the following publications as needed for information on configuring other ControlLogix networks:
See this publication:
Publication number: the ControlLogix ControlNet interface module ControlLogix ControlNet Scanner Installation Instructions 1756-5.32 ControlLogix ControlNet Interface Module User Manual 1756-6.5.3 the ControlLogix Data Highway Plus interface ControlLogix Data Highway Plus Communication Interface Module 1756-5.4 module Installation Instructions ControlLogix Data Highway Plus Communication Interface Module 1756-6.5.2 User Manual the ControlLogix Ethernet interface module ControlLogix Ethernet Communication Interface Module 1756-5.3 Installation Instructions ControlLogix Ethernet Communication Interface Module 1756-6.5.1 User Manual TCP/IP protocol and networking in general Comer, Douglas E., Internetworking with TCP-IP, Volume 1: n/a Protocols and Architecture, 2nd ed. Englewood Cliffs, N.J.:Prentice-Hall, 1995. ISBN 0-13-216987-8. Tannebaum, Andrew S. Computer Networks, 2nd ed. Englewood n/a Cliffs, N.J.: Prentice-Hall, 1989. ISBN 0-13-162959-X.
Configuring DeviceNet from Before performing this example the ControlNet network must be configured and running. A 1756-CNB module must be installed in the a ControlNet Network ControlLogix chassis with the 1756-DNB module. In this example the 1756-CNB module is in slot 3 of the ControlLogix chassis and is configured as ControlNet node 11. Use the actual configuration of your CNB module when performing this example. 1. Start RSNetWorx.
2. From the File menu, select New. Publication 1756-6.5.19 - May 2000
Page 59
Configuring DeviceNet From Another Network
5-3
If you have RSNetWorx for ControlNet installed on your computer you may see the following window. Otherwise, proceed to step 4.
3. Highlight DeviceNet Configuration and click on OK. 4. Click on the Online button on the toolbar.
A list of the available drivers in RSLinx will appear. (Your list may appear different from that shown below, depending upon what you have configured on your system.)
5. Select the “+” next to your ControlNet driver (AB_KTC-1 above) to expand the tree. 6. Navigate down the tree through the backplane until you reach the DeviceNet network on channel A of the 1756-DNB module.
Publication 1756-6.5.19 - May 2000
Page 60
5-4
Configuring DeviceNet From Another Network
Your window should appear similar to the following one:
7. Select the OK button to accept the path. You will be prompted to upload or download devices before going online.
8. Click on OK to go online. RSNetWorx will begin browsing for network devices. Note that this will take longer than in chapter 4 since you are doing a remote browse. When the software is finished browsing, the network displayed on your screen should look similar to the one shown below.
You are now online to the DeviceNet network via the ControlNet network. Perform the procedures described on pages 4-6 to 4-18 to configure the DeviceNet network before downloading and running the example program.
Publication 1756-6.5.19 - May 2000
Page 61
Configuring DeviceNet From Another Network
5-5
Configuring DeviceNet from Before performing this example the Ethernet network must be configured and running. A 1756-ENET module must be in the an Ethernet Network ControlLogix chassis with the 1756-DNB module. In this example the 1756-ENET module is in slot 4 of the ControlLogix chassis and is configured with an IP address of 130.130.130.1. Use the actual configuration of your ENET module when performing this example. 1. Start RSNetWorx.
2. From the File menu, select New. If you have RSNetWorx for ControlNet installed on your computer you may see the following window. Otherwise, proceed to step 4.
3. Highlight DeviceNet Configuration and click on OK. 4. Click on the Online button on the toolbar.
Publication 1756-6.5.19 - May 2000
Page 62
5-6
Configuring DeviceNet From Another Network
The Browse for network window will appear with the available drivers. (Your window may appear different from that shown below, depending upon the drivers you have configured on your system.)
5. Select the “+” next to your Ethernet driver (TCP-1 above) to expand it. 6. Navigate down the tree until you reach the DeviceNet network for channel A of the 1756-DNB module. Your screen should appear similar to the following one:
7. Select the OK button to accept the path.
Publication 1756-6.5.19 - May 2000
Page 63
Configuring DeviceNet From Another Network
5-7
You will be prompted to upload or download devices before going online.
8. Click on OK to go online. RSNetWorx for DeviceNet will begin browsing for network devices. Note that this will take longer than in chapter 4 since you are doing a remote browse. When the software is finished browsing, the network displayed on your screen should look similar to the one shown below.
You are now online to the DeviceNet network via the Ethernet network. Perform the procedures described on pages 4-6 to 4-18 to configure the DeviceNet network before downloading and running the example program.
Publication 1756-6.5.19 - May 2000
Page 64
5-8
Configuring DeviceNet From Another Network
Configuring DeviceNet From a Data Highway Plus Network
Before performing this example the Data Highway Plus network must be configured and running. A 1756-DHRIO module must be in the ControlLogix chassis with the 1756-DNB module. In this example, the 1756-DHRIO module is in slot 2 of the ControlLogix chassis and channel A is configured for DH+ as node 3. Use your actual DHRIO configuration when performing this example. 1. Open the RSNetWorx for DeviceNet software.
2. From the File menu, select New. If you have RSNetWorx for ControlNet installed on your computer you may see the following window. Otherwise, proceed to step 4.
3. Highlight DeviceNet Configuration and click on OK. 4. Click on the Online button
Publication 1756-6.5.19 - May 2000 on the toolbar.
Page 65
Configuring DeviceNet From Another Network
5-9
The Browse for network window will appear with the available drivers. (Your window may appear different from that shown below, depending upon the drivers you have configured on your system.)
5. Select the “+” next to the Data Highway Plus driver (AB_KT-1 above) to expand it. 6. Navigate down the tree until you reach the DeviceNet network for channel A of the 1756-DNB module. Your window should look similar to the following one:
7. Select the OK button to accept the path.
Publication 1756-6.5.19 - May 2000
Page 66
5-10
Configuring DeviceNet From Another Network
You will be prompted to upload or download devices before going online.
8. Click on OK to go online. RSNetWorx for DeviceNet will begin browsing for network devices. Note that this will take longer than in chapter 4 since you are doing a remote browse. When the software is finished browsing, the network displayed on your screen should look similar to the one shown below.
You are now online to the DeviceNet network via the Data Highway Plus network. Perform the procedures described on pages 4-6 to 4-18 to configure the DeviceNet network before downloading and running the example program.
What’s Next?
Publication 1756-6.5.19 - May 2000
The next chapter describes how to create and run the example application program to test the DeviceNet network.