Page 1
Technical Data
CompactLogix Controllers Specifications CompactLogix 5370 Controller Catalog Numbers 1769-L16ER-BB1B, 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B, 1769-L24ER-QB1B, 1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B,1769-L30ER, 1769-L30ER-NSE, 1769-L30ERM, 1769-L30ERMS, 1769-L33ER, 1769-L33ERM, 1769-L33ERMS, 1769-L36ERM, 1769-L36ERMS 1769 Packaged Controller Catalog Numbers 1769-L23-QBFC1B, 1769-L23E-QB1B, 1769-L23E-QBFC1B 1769 Modular Controller Catalog Numbers 1769-L31, 1769-L32C, 1769-L35CR, 1769-L32E, 1769-L35E 1768 Controller Catalog Numbers 1768-L43, 1768-L43S, 1768-L45, 1768-L45S Memory Card Catalog Numbers 1784-CF128, 1784-SD1, 1784-SD2 Topic
Page
CompactLogix 5370 Controllers
5
1769 Packaged CompactLogix Controllers with Embedded I/O
37
1769 Modular CompactLogix Controllers
48
1768 CompactLogix Controllers
52
Controller Memory Use
59
Controller Compatibility
60
Controller Connections
63
Determine Total Connection Use
65
CompactLogix Controller Accessories
66
Page 2
CompactLogix Controllers Specifications
Table 1 - Environmental Specifications - 1769 CompactLogix Controllers and Compact GuardLogix 5370 Controllers
2
Attribute
1769-L16ER-BB1B, 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B
1769-L24ER-QB1B, 1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B
1769-L30ER, 1769-L30ER-NSE, 1769-L30ERM, 1769-L33ER, 1769-L33ERM, 1769-L36ERM
1769-L30ERMS, 1769-L33ERMS, 1769-L36ERMS
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Na, Operating Thermal Shock)
-20…60 °C (-4…140 °F)
0…60 °C (32…140 °F)
Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz(1)
5 g @ 10…500 Hz
5 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g(1)
20 g - DIN rail 30 g - Panel
20 g - DIN rail 30 g - Panel
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g(1), (2)
30 g - DIN rail 40 g - Panel
30 g - DIN rail 40 g - Panel
Emissions CISPR 11
IEC 61000-6-4
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
1769-L23-QBFC1B, 1769-L23E-QB1B, 1769-L23E-QBFC1B
4 kV contact discharges 8 kV air discharges
1769-L31, 1769-L32C, 1769-L35CR, 1769-L32E, 1769-L35E
6 kV contact discharges 8 kV air discharges
Page 3
CompactLogix Controllers Specifications
Table 1 - Environmental Specifications - 1769 CompactLogix Controllers and Compact GuardLogix 5370 Controllers Attribute
1769-L16ER-BB1B, 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B
1769-L24ER-QB1B, 1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
1769-L30ER, 1769-L30ER-NSE, 1769-L30ERM, 1769-L33ER, 1769-L33ERM, 1769-L36ERM
1769-L30ERMS, 1769-L33ERMS, 1769-L36ERMS
1769-L23-QBFC1B, 1769-L23E-QB1B, 1769-L23E-QBFC1B
1769-L31, 1769-L32C, 1769-L35CR, 1769-L32E, 1769-L35E
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
1769-L31, 1769-L32C, 1769-L35CR 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1769-L32E, 1769-L35E 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±3 kV at 5 kHz on power ports ±3 kV at 5 kHz on signal ports ±3 kV at 5 kHz on communication ports
±3 kV at 5 kHz on communication ports
Surge transient immunity IEC 61000-4-5
+ 1 kV line-line (DM) and + 2 kV line-earth (CM) on power ports + 1 kV line-line (DM) and + 2 kV line-earth (CM) on signal ports +2 kV line-earth (CM) on communication ports
±2 kV line-earth (CM) on communication ports
Conducted RF immunity IEC 61000-4-6
±1 kV line-line (DM) and +2 kV line-earth (CM) on power ports ±1 kV line-line (DM) and +2 kV line-earth (CM) on signal ports +2 kV line-earth (CM) on shielded ports ±2 kV line-earth (CM) on communication ports
±3 kV at 5 kHz on communication ports ±4 kV at 5 kHz on Protecctive Earth (PE)
±2 kV at 5 kHz on power ports ±2 kV at 5 kHz on signal ports ±2 kV at 5 kHz on communication ports
1769-L31, 1769-L32C, 1769-L35CR ±2 kV at 5 kHz on communication ports 1769-L32E, 1769-L35E ±3 kV at 5 kHz on power ports ±3 kV at 5 kHz on communication ports
±1 kV line-line (DM) and +2 kV line-earth (CM) on power ports ±1 kV line-line (DM) and +2 kV line-earth (CM) on signal ports +2 kV line-earth (CM) on shielded ports ±2 kV line-earth (CM) on communication ports
1769-L31 Channel 0: ±2 kV line-earth (CM) on shielded ports Channel 1: ±1 kV line-earth (CM) on shielded ports 1769-L32C, 1769-L35CR, 1769-L32E, 1769-L35E ±2 kV line-earth (CM) on communication ports
10Vrms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
(1) If you are mounting a CompactLogix™ 5370 L1 controller on an EN 50 022 - 35 x 15 mm (1.38 x 0.59 in.) DIN rail, you must first adhere a bumper on the back of the controller. Failure to install the bumper before mounting the controller results in the system failing to meet this specification. For more information, see the CompactLogix 5370 Controllers User Manual, publication 1769-UM021. (2) If you are mounting a CompactLogix 5370 L1 controller on an EN 50 022 - 35 x 15 mm (1.38 x 0.59 in.) DIN rail, the Shock, nonoperating specification = 30 g.
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
3
Page 4
CompactLogix Controllers Specifications
Table 2 - Environmental Specifications - 1768-CompactLogix Controllers
4
Attribute
1768-L43, 1768-L43S, 1768-L45, 1768-L45S
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Na, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
5 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions CISPR 11
IEC 61000-6-4
ESD immunity IEC 61000-4-2
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4
±4 kV at 5 kHz on communication ports
Surge transient immunity IEC 61000-4-5
±2 kV line-earth (CM) on communication ports
Conducted RF immunity IEC 61000-4-6
10 Vrms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
Page 5
CompactLogix Controllers Specifications
CompactLogix 5370 Controllers CompactLogix 5370 L1 Control System
CompactLogix 5370 L3 Control System
CompactLogix 5370 L2 Control System
Compact GuardLogix® 5370 Control System
CompactLogix 5370 controllers provide scalable controller solutions to address a wide variety of applications. All CompactLogix 5370 controllers provide the following functionality: • Two EtherNet™/IP ports • One USB port • Support for local expansion modules • Control of local and distributed I/O modules • Use of 1784-SD1 or 1784-SD2 Secure Digital (SD) card for nonvolatile memory • A battery is no longer necessary because of the internal energy-storage solution Some CompactLogix 5370 controllers provide the following functionality: • Built-in power supply • Some combination of embedded digital, analog, and high-speed counter modules • Support for Integrated Motion over an EtherNet/IP network • Access to DeviceNet™ networks The Compact GuardLogix controller is a 1769-L3 CompactLogix controller that provides safety control to achieve SIL CL3 according to EN62061 / EN 61511-1 / IEC 61508 and PLe according to EN ISO 13849-1. A major benefit of this system is that it’s still one project, safety and standard together. Application
Description
SIL 1, 2, 3
The Compact GuardLogix controller system is type-approved and certified for use in safety applications up to and including SIL 3 according to IEC 61508, and applications up to and including PLe/Cat.4 according to ISO 13849-1. For more information, see the following: • GuardLogix 5570 and Compact GuardLogix 5370 Controllers Systems Safety Reference Manual, publication 1756-RM099 • Compact GuardLogix 5370 Controllers User Manual, publication 1769-UM002 • GuardLogix Safety Application Instruction Set Reference Manual, publication 1756-RM095
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
5
Page 6
CompactLogix Controllers Specifications
During development, safety and standard have the same rules. The following are allowed: • Multiple programmers • Online editing • Forcing Once the project is tested and ready for final validation, you apply the safety application signature and safety-lock the application. This process sets the safety task to a SIL 3 integrity level. The Compact GuardLogix enforces the SIL 3 integrity level. When safety memory is locked and protected, the safety logic cannot be modified and all safety functions operate with SIL 3 integrity. On the standard side of the Compact GuardLogix controller, all functions operate like a regular Logix controller. Thus online editing, forcing, and other activities are all allowed. Standard logic and external devices, like HMIs or other controllers, can read safety memory with this level of integration. This level of integration removes the need to condition safety memory for use elsewhere. The result is easy system-wide
™ integration and the ability to display safety status on displays or marquees. Use Guard I/O modules for field device connectivity. For safety interlocking between Compact GuardLogix controllers, use Ethernet or ControlNet™ networks. Multiple Compact GuardLogix controllers can share safety data for zone to zone interlocking, or one Compact GuardLogix controller can use remote distributed safety I/O between different cells/areas. Table 3 - Features - CompactLogix 5370 Controllers and Compact GuardLogix 5370 Controllers Feature
1769-L16ER-BB1B, 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B
1769-L24ER-QB1B, 1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B
1769-L30ER, 1769-L30ER-NSE, 1769-L30ERM, 1769-L33ER, 1769-L33ERM, 1769-L36ERM
1769-L30ERMS, 1769-L33ERMS, 1769-L36ERMS
Controller tasks: • Continuous • Periodic
• 32 tasks • 100 programs/task
Built-in communication ports
• Two EtherNet/IP ports - CompactLogix 5370 controllers have two EtherNet/IP ports to connect to an EtherNet/IP network. The ports carry the same network traffic as part of the embedded switch of the controller. However, the controller uses only one IP address. • One USB port (only for temporary connection)
Communication options
EtherNet/IP
• EtherNet/IP • DeviceNet via 1769-SDN scanner
EtherNet/IP node, max
• 1769-L16ER-BB1B: Up to four nodes • 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B: Up to 8 nodes
• 1769-L24ER-QB1B, 1769-L24ERQBFC1B: Up to 8 nodes • 1769-L27ERM-QBFC1B: Up to 16 nodes
• 1769-L30ER, 1769-L30ER-NSE, 1769-L30ERM, 1769-L30ERMS: Up to 16 nodes • 1769-L33ER, 1769-L33ERM, 1769-L33ERMS: Up to 32 nodes • 1769-L36ERM, 1769-L36ERMS: Up to 48 nodes
Controller connections
256
Embedded I/O modules
• 16 DC digital inputs • 16 DC digital outputs
All controllers: • 16 DC digital inputs • 16 DC digital outputs
None
Only 1769-L24ER-QBFC1B and 1769-L27ERM-QBFC1B: • 4 high-speed counters • 4 high-speed counter outputs • 4 universal analog inputs • 2 analog output points Sockets, max
32
Integrated Motion over an EtherNet/IP network
1769-L18ERM-BB1B - 1 or 2 axes
Programming languages
• • • •
Integrated safety
N/A
1769-L27ERM-QBFC1B - As many as 4 axes
• 1769-L30ERM, 1769-L30ERMS - As many as 4 axes • 1769-L33ERM, 1769-L33ERMS - As many as 8 axes • 1769-L36ERM, 1769-L36ERMS - As many as 16 axes
Relay ladder(1) Structured Text Function block SFC Yes
(1) The Compact GuardLogix 5370 controllers support only the relay ladder programming language in the safety task. The Compact GuardLogix 5370 controllers support all listed programming languages in the standard task.
6
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
Page 7
CompactLogix Controllers Specifications
Table 4 - Technical Specifications - CompactLogix 5370 Controllers and Compact GuardLogix 5370 Controllers Attribute
1769-L16ER-BB1B, 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B
1769-L24ER-QB1B, 1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B
1769-L30ER, 1769-L30ER-NSE, 1769-L30ERM, 1769-L33ER, 1769-L33ERM, 1769-L36ERM
1769-L30ERMS, 1769-L33ERMS, 1769-L36ERMS
User memory
• 1769-L16ER: 384 KB • 1769-L18ER, 1769-L18ERM: 512 KB • 1769-L19ER-BB1B: 1 MB
• 1769-L24ER-QB1B, 1769-L24ER-QBFC1B: 750 KB • 1769-L27ERM-QBFC1B: 1 MB
• 1769-L30ER, 1769-L30ER-NSE, 1769-L30ERM: 1 MB • 1769-L33ER, 1769-L33ERM: 2 MB • 1769-L36ERM: 3 MB
• 1769-L30ERMS: 1 MB standard + 0.5 MB safety • 1769-L33ERMS: 2 MB standard + 1 MB safety • 1769-L36ERMS: 3 MB standard + 1.5 MB safety
Optional nonvolatile memory
1784-SD1 card with 1 Gb of available memory (shipped with controller) 1784-SD2 card with 2 Gb of available memory (available for separate ordering)
Number of local expansion modules, max(1)
• 1769-L16ER-BB1B: Six 1734 POINT I/O™ modules • 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B: Eight 1734 POINT I/O modules
Four 1769 Compact I/O modules
• 1769-L30ER, 1769-L30ER-NSE, 1769-L30ERM, 1769-L30ERMS: Eight 1769 Compact I/O™ modules • 1769-L33ER, 1769-L33ERM, 1769-L33ERMS: Sixteen 1769 Compact I/O modules • 1769-L36ERM, 1769-L36ERMS: Thirty 1769 Compact I/O modules
Number of I/O module banks, max
N/A
1
3
Current draw @ 5V DC, controller power
1A
• 1769-L24ER-QB1B: 1.54 A Value rated at the following ambient temperatures: 40 °C (104 °F), 55 °C (131 °F), 60 °C (140 °F).
500 mA
850 mA
225 mA
700 mA
4.5 W
6.5 W
• 1769-L24ER-QBFC1B and 1769-L27ERM-QBFC1B: 1 A Value rated at the following ambient temperatures: 40 °C (104 °F), 55 °C (131 °F), 60 °C (140 °F). Current draw @ 24V DC, controller power
N/A
• 1769-L24ER-QB1B: 0.95A Value rated at the following ambient temperatures: 40 °C (104 °F), 55 °C (131 °F), 60 °C (140 °F). • 1769-L24ER-QBFC1B and 1769-L27ERM-QBFC1B: 0.8 A Value rated at the following ambient temperatures: 40 °C (104 °F), 55 °C (131 °F), 60 °C (140 °F).
Current draw @ 24V DC, field power, max
3 A - Combined total for all devices that draw current from field power connections
N/A
Input: 5 mA Output: 500 mA Power dissipation, max
11.5 W
• 1769-L24ER-QB1B: 12 W • 1769-L24ER-QBFC1B, L27ERM-QBFC1B: 21 W
Isolation voltage
50V (continuous), Basic Insulation Type Tested at 500V AC for 60 s, System to Field
30V (continuous), Basic Insulation Type, USB to system, Ethernet to system and Ethernet to Ethernet Type tested at 500V AC for 60 s
Short circuit protection, field power
Internal fuse, Non-replaceable
N/A
Recommended external short circuit protection, field power
User-provided 4…5 A @ 3.15…5.5 A2t fuse
N/A
Weight, approx
0.66 kg (1.5 lb)
• 1769-L24ER-QB1B = 0.63 kg (1.39 lb)
0.31 kg (0.68 lb)
50V, Basic Insulation Type Tested at 500V AC for 60 s, System to Communication ports.
0.54 kg (1.18 lb)
• 1769-L24ER-QBFC1B and 1769-L27ERM-QBFC1B = 0.9 kg (1.9 lb)
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
7
Page 8
CompactLogix Controllers Specifications
Table 4 - Technical Specifications - CompactLogix 5370 Controllers and Compact GuardLogix 5370 Controllers Attribute
1769-L16ER-BB1B, 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B
1769-L24ER-QB1B, 1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B
1769-L30ER, 1769-L30ER-NSE, 1769-L30ERM, 1769-L33ER, 1769-L33ERM, 1769-L36ERM
1769-L30ERMS, 1769-L33ERMS, 1769-L36ERMS
Module width
100.00 mm (3.94 in.)
1769-L24ER-QB1B = 115.00 mm (4.53 in.) 1769-L24ER-QBFC1B and 1769-L27ERM-QBFC1B = 140 mm (5.51 in.)
55.00 mm (2.17 in.)
89.00 mm (3.50 in.)
Module location
DIN rail mount
DIN rail or panel mount
Panel-mounting screw torque
N/A
1.1…1.8 Nm (10…16 lbin) - use M4 or #8 screws
Embedded power supply
24V DC input, isolated
24V DC Input, isolated
Power supply distance rating
NA
• Controller and 1769-SDN: 4 • 1769 Compact I/O modules: 4…8, depending on module
Wire category(2)
1 - signal ports 1 - power ports 2 - communication ports
2 - communication ports
Wire type, Ethernet
RJ-45 connector according to IEC 60603-7, 2 or 4 pair Category 5e minimum cable according to TIA 568-B.1 or Category 5 cable according to ISO/IEC 24702
Wire type, power terminals and embedded I/O connections
Copper
Wire size, power terminals(3)
0.051…3.31 mm2 (30…12 AWG) solid or stranded copper wire rated at 75 °C (167 °F), or greater, 1.2 mm (3/64 in.) insulation, max Each terminal accepts 1 or 2 wires
0.25…2.50 mm2 (22…14 AWG) solid copper wire rated at 75 °C (167 °F), or greater 1.2 mm (3/64 in.) insulation, max Each terminal accepts only 1 wire
N/A
Wire stripping length, power terminals(3)
10 mm (0.39 in)
8 mm (0.31 in)
N/A
Screw torque, power terminals (3)
0.5…0.6 N•m (4.4…5.3 lb•in)
1.0…1.2 N•m (8.9…10.6 lb•in)
N/A
1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4 4 (3 I/O modules between controller and power supply)
N/A
2 (24…16 AWG) solid or stranded copper wire rated at
Wire size, embedded I/O connections
0.205…1.31 mm 75 °C (167 °F), or greater 1.2 mm (3/64 in.) insulation, max or 90 °C (194 °F) Each terminal accepts only 1 wire
N/A
Wire stripping length, embedded I/O connections
10 mm (0.39 in)
N/A
North American temperature code
T4A
IEC temperature code
T4
Enclosure type rating
None (open-style)
T3C
T5 T5
(1) You can use up to the maximum number of local expansion modules with the CompactLogix 5370 L1 controllers that are listed as long as the total current drawn by the embedded I/O and local expansion modules does not exceed both the available POINTBus backplane current of 1 A and the field power current of 3 A. For more information on POINTBus backplane current and field-power current considerations when installing local expansion modules, see page 11. (2) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 and the appropriate system-level installation manual. (3) Regarding the CompactLogix 5370 L1 controllers, this specification applies to connecting wires to the power connector that is inserted in the controller. Regarding the CompactLogix 5370 L2 controllers, this specification applies to connecting wires to power terminals built into the controller.
8
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
Page 9
CompactLogix Controllers Specifications
Real-time Clock Accuracy The following table lists the real-time clock accuracy specifications for the CompactLogix 5370 controllers. Ambient Temperature
Accuracy
0 °C (32 °F)
-143…42 s/mo
25 °C (77 °F)
-78…91 s/mo
40 °C (104 °F)
-101…73 s/mo
60 °C (140 °F)
-204…-4.50 s/mo
Real-time Clock Hold-up Times The following table lists the typical real-time clock hold-up specifications for the CompactLogix 5370 controllers. IMPORTANT
The values in the following table are typical and can vary with some CompactLogix 5370 control systems.
Ambient Temperature
Holdup Time, Typical
0 °C (32 °F)
40 days
25 °C (77 °F)
35 days
40 °C (104 °F)
28 days
60 °C (140 °F)
16 days
The I/O module support for CompactLogix 5370 controller systems varies by controller.
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015