Page 1

Technical Data

CompactLogix Controllers Specifications CompactLogix 5370 Controller Catalog Numbers 1769-L16ER-BB1B, 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B, 1769-L24ER-QB1B, 1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B,1769-L30ER, 1769-L30ER-NSE, 1769-L30ERM, 1769-L30ERMS, 1769-L33ER, 1769-L33ERM, 1769-L33ERMS, 1769-L36ERM, 1769-L36ERMS 1769 Packaged Controller Catalog Numbers 1769-L23-QBFC1B, 1769-L23E-QB1B, 1769-L23E-QBFC1B 1769 Modular Controller Catalog Numbers 1769-L31, 1769-L32C, 1769-L35CR, 1769-L32E, 1769-L35E 1768 Controller Catalog Numbers 1768-L43, 1768-L43S, 1768-L45, 1768-L45S Memory Card Catalog Numbers 1784-CF128, 1784-SD1, 1784-SD2 Topic

Page

CompactLogix 5370 Controllers

5

1769 Packaged CompactLogix Controllers with Embedded I/O

37

1769 Modular CompactLogix Controllers

48

1768 CompactLogix Controllers

52

Controller Memory Use

59

Controller Compatibility

60

Controller Connections

63

Determine Total Connection Use

65

CompactLogix Controller Accessories

66

Page 2

CompactLogix Controllers Specifications

Table 1 - Environmental Specifications - 1769 CompactLogix Controllers and Compact GuardLogix 5370 Controllers

2

Attribute

1769-L16ER-BB1B, 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B

1769-L24ER-QB1B, 1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B

1769-L30ER, 1769-L30ER-NSE, 1769-L30ERM, 1769-L33ER, 1769-L33ERM, 1769-L36ERM

1769-L30ERMS, 1769-L33ERMS, 1769-L36ERMS

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Na, Operating Thermal Shock)

-20…60 °C (-4…140 °F)

0…60 °C (32…140 °F)

Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz(1)

5 g @ 10…500 Hz

5 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g(1)

20 g - DIN rail 30 g - Panel

20 g - DIN rail 30 g - Panel

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g(1), (2)

30 g - DIN rail 40 g - Panel

30 g - DIN rail 40 g - Panel

Emissions CISPR 11

IEC 61000-6-4

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

1769-L23-QBFC1B, 1769-L23E-QB1B, 1769-L23E-QBFC1B

4 kV contact discharges 8 kV air discharges

1769-L31, 1769-L32C, 1769-L35CR, 1769-L32E, 1769-L35E

6 kV contact discharges 8 kV air discharges

Page 3

CompactLogix Controllers Specifications

Table 1 - Environmental Specifications - 1769 CompactLogix Controllers and Compact GuardLogix 5370 Controllers Attribute

1769-L16ER-BB1B, 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B

1769-L24ER-QB1B, 1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

1769-L30ER, 1769-L30ER-NSE, 1769-L30ERM, 1769-L33ER, 1769-L33ERM, 1769-L36ERM

1769-L30ERMS, 1769-L33ERMS, 1769-L36ERMS

1769-L23-QBFC1B, 1769-L23E-QB1B, 1769-L23E-QBFC1B

1769-L31, 1769-L32C, 1769-L35CR, 1769-L32E, 1769-L35E

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

1769-L31, 1769-L32C, 1769-L35CR 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1769-L32E, 1769-L35E 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±3 kV at 5 kHz on power ports ±3 kV at 5 kHz on signal ports ±3 kV at 5 kHz on communication ports

±3 kV at 5 kHz on communication ports

Surge transient immunity IEC 61000-4-5

+ 1 kV line-line (DM) and + 2 kV line-earth (CM) on power ports + 1 kV line-line (DM) and + 2 kV line-earth (CM) on signal ports +2 kV line-earth (CM) on communication ports

±2 kV line-earth (CM) on communication ports

Conducted RF immunity IEC 61000-4-6

±1 kV line-line (DM) and +2 kV line-earth (CM) on power ports ±1 kV line-line (DM) and +2 kV line-earth (CM) on signal ports +2 kV line-earth (CM) on shielded ports ±2 kV line-earth (CM) on communication ports

±3 kV at 5 kHz on communication ports ±4 kV at 5 kHz on Protecctive Earth (PE)

±2 kV at 5 kHz on power ports ±2 kV at 5 kHz on signal ports ±2 kV at 5 kHz on communication ports

1769-L31, 1769-L32C, 1769-L35CR ±2 kV at 5 kHz on communication ports 1769-L32E, 1769-L35E ±3 kV at 5 kHz on power ports ±3 kV at 5 kHz on communication ports

±1 kV line-line (DM) and +2 kV line-earth (CM) on power ports ±1 kV line-line (DM) and +2 kV line-earth (CM) on signal ports +2 kV line-earth (CM) on shielded ports ±2 kV line-earth (CM) on communication ports

1769-L31 Channel 0: ±2 kV line-earth (CM) on shielded ports Channel 1: ±1 kV line-earth (CM) on shielded ports 1769-L32C, 1769-L35CR, 1769-L32E, 1769-L35E ±2 kV line-earth (CM) on communication ports

10Vrms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

(1) If you are mounting a CompactLogix™ 5370 L1 controller on an EN 50 022 - 35 x 15 mm (1.38 x 0.59 in.) DIN rail, you must first adhere a bumper on the back of the controller. Failure to install the bumper before mounting the controller results in the system failing to meet this specification. For more information, see the CompactLogix 5370 Controllers User Manual, publication 1769-UM021. (2) If you are mounting a CompactLogix 5370 L1 controller on an EN 50 022 - 35 x 15 mm (1.38 x 0.59 in.) DIN rail, the Shock, nonoperating specification = 30 g.

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

3

Page 4

CompactLogix Controllers Specifications

Table 2 - Environmental Specifications - 1768-CompactLogix Controllers

4

Attribute

1768-L43, 1768-L43S, 1768-L45, 1768-L45S

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Na, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Temperature, surrounding air, max

60 °C (140 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

5 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions CISPR 11

IEC 61000-6-4

ESD immunity IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity IEC 61000-4-4

±4 kV at 5 kHz on communication ports

Surge transient immunity IEC 61000-4-5

±2 kV line-earth (CM) on communication ports

Conducted RF immunity IEC 61000-4-6

10 Vrms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

Page 5

CompactLogix Controllers Specifications

CompactLogix 5370 Controllers CompactLogix 5370 L1 Control System

CompactLogix 5370 L3 Control System

CompactLogix 5370 L2 Control System

Compact GuardLogix® 5370 Control System

CompactLogix 5370 controllers provide scalable controller solutions to address a wide variety of applications. All CompactLogix 5370 controllers provide the following functionality: • Two EtherNet™/IP ports • One USB port • Support for local expansion modules • Control of local and distributed I/O modules • Use of 1784-SD1 or 1784-SD2 Secure Digital (SD) card for nonvolatile memory • A battery is no longer necessary because of the internal energy-storage solution Some CompactLogix 5370 controllers provide the following functionality: • Built-in power supply • Some combination of embedded digital, analog, and high-speed counter modules • Support for Integrated Motion over an EtherNet/IP network • Access to DeviceNet™ networks The Compact GuardLogix controller is a 1769-L3 CompactLogix controller that provides safety control to achieve SIL CL3 according to EN62061 / EN 61511-1 / IEC 61508 and PLe according to EN ISO 13849-1. A major benefit of this system is that it’s still one project, safety and standard together. Application

Description

SIL 1, 2, 3

The Compact GuardLogix controller system is type-approved and certified for use in safety applications up to and including SIL 3 according to IEC 61508, and applications up to and including PLe/Cat.4 according to ISO 13849-1. For more information, see the following: • GuardLogix 5570 and Compact GuardLogix 5370 Controllers Systems Safety Reference Manual, publication 1756-RM099 • Compact GuardLogix 5370 Controllers User Manual, publication 1769-UM002 • GuardLogix Safety Application Instruction Set Reference Manual, publication 1756-RM095

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

5

Page 6

CompactLogix Controllers Specifications

During development, safety and standard have the same rules. The following are allowed: • Multiple programmers • Online editing • Forcing Once the project is tested and ready for final validation, you apply the safety application signature and safety-lock the application. This process sets the safety task to a SIL 3 integrity level. The Compact GuardLogix enforces the SIL 3 integrity level. When safety memory is locked and protected, the safety logic cannot be modified and all safety functions operate with SIL 3 integrity. On the standard side of the Compact GuardLogix controller, all functions operate like a regular Logix controller. Thus online editing, forcing, and other activities are all allowed. Standard logic and external devices, like HMIs or other controllers, can read safety memory with this level of integration. This level of integration removes the need to condition safety memory for use elsewhere. The result is easy system-wide

™ integration and the ability to display safety status on displays or marquees. Use Guard I/O modules for field device connectivity. For safety interlocking between Compact GuardLogix controllers, use Ethernet or ControlNet™ networks. Multiple Compact GuardLogix controllers can share safety data for zone to zone interlocking, or one Compact GuardLogix controller can use remote distributed safety I/O between different cells/areas. Table 3 - Features - CompactLogix 5370 Controllers and Compact GuardLogix 5370 Controllers Feature

1769-L16ER-BB1B, 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B

1769-L24ER-QB1B, 1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B

1769-L30ER, 1769-L30ER-NSE, 1769-L30ERM, 1769-L33ER, 1769-L33ERM, 1769-L36ERM

1769-L30ERMS, 1769-L33ERMS, 1769-L36ERMS

Controller tasks: • Continuous • Periodic

• 32 tasks • 100 programs/task

Built-in communication ports

• Two EtherNet/IP ports - CompactLogix 5370 controllers have two EtherNet/IP ports to connect to an EtherNet/IP network. The ports carry the same network traffic as part of the embedded switch of the controller. However, the controller uses only one IP address. • One USB port (only for temporary connection)

Communication options

EtherNet/IP

• EtherNet/IP • DeviceNet via 1769-SDN scanner

EtherNet/IP node, max

• 1769-L16ER-BB1B: Up to four nodes • 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B: Up to 8 nodes

• 1769-L24ER-QB1B, 1769-L24ERQBFC1B: Up to 8 nodes • 1769-L27ERM-QBFC1B: Up to 16 nodes

• 1769-L30ER, 1769-L30ER-NSE, 1769-L30ERM, 1769-L30ERMS: Up to 16 nodes • 1769-L33ER, 1769-L33ERM, 1769-L33ERMS: Up to 32 nodes • 1769-L36ERM, 1769-L36ERMS: Up to 48 nodes

Controller connections

256

Embedded I/O modules

• 16 DC digital inputs • 16 DC digital outputs

All controllers: • 16 DC digital inputs • 16 DC digital outputs

None

Only 1769-L24ER-QBFC1B and 1769-L27ERM-QBFC1B: • 4 high-speed counters • 4 high-speed counter outputs • 4 universal analog inputs • 2 analog output points Sockets, max

32

Integrated Motion over an EtherNet/IP network

1769-L18ERM-BB1B - 1 or 2 axes

Programming languages

• • • •

Integrated safety

N/A

1769-L27ERM-QBFC1B - As many as 4 axes

• 1769-L30ERM, 1769-L30ERMS - As many as 4 axes • 1769-L33ERM, 1769-L33ERMS - As many as 8 axes • 1769-L36ERM, 1769-L36ERMS - As many as 16 axes

Relay ladder(1) Structured Text Function block SFC Yes

(1) The Compact GuardLogix 5370 controllers support only the relay ladder programming language in the safety task. The Compact GuardLogix 5370 controllers support all listed programming languages in the standard task.

6

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

Page 7

CompactLogix Controllers Specifications

Table 4 - Technical Specifications - CompactLogix 5370 Controllers and Compact GuardLogix 5370 Controllers Attribute

1769-L16ER-BB1B, 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B

1769-L24ER-QB1B, 1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B

1769-L30ER, 1769-L30ER-NSE, 1769-L30ERM, 1769-L33ER, 1769-L33ERM, 1769-L36ERM

1769-L30ERMS, 1769-L33ERMS, 1769-L36ERMS

User memory

• 1769-L16ER: 384 KB • 1769-L18ER, 1769-L18ERM: 512 KB • 1769-L19ER-BB1B: 1 MB

• 1769-L24ER-QB1B, 1769-L24ER-QBFC1B: 750 KB • 1769-L27ERM-QBFC1B: 1 MB

• 1769-L30ER, 1769-L30ER-NSE, 1769-L30ERM: 1 MB • 1769-L33ER, 1769-L33ERM: 2 MB • 1769-L36ERM: 3 MB

• 1769-L30ERMS: 1 MB standard + 0.5 MB safety • 1769-L33ERMS: 2 MB standard + 1 MB safety • 1769-L36ERMS: 3 MB standard + 1.5 MB safety

Optional nonvolatile memory

1784-SD1 card with 1 Gb of available memory (shipped with controller) 1784-SD2 card with 2 Gb of available memory (available for separate ordering)

Number of local expansion modules, max(1)

• 1769-L16ER-BB1B: Six 1734 POINT I/O™ modules • 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B: Eight 1734 POINT I/O modules

Four 1769 Compact I/O modules

• 1769-L30ER, 1769-L30ER-NSE, 1769-L30ERM, 1769-L30ERMS: Eight 1769 Compact I/O™ modules • 1769-L33ER, 1769-L33ERM, 1769-L33ERMS: Sixteen 1769 Compact I/O modules • 1769-L36ERM, 1769-L36ERMS: Thirty 1769 Compact I/O modules

Number of I/O module banks, max

N/A

1

3

Current draw @ 5V DC, controller power

1A

• 1769-L24ER-QB1B: 1.54 A Value rated at the following ambient temperatures: 40 °C (104 °F), 55 °C (131 °F), 60 °C (140 °F).

500 mA

850 mA

225 mA

700 mA

4.5 W

6.5 W

• 1769-L24ER-QBFC1B and 1769-L27ERM-QBFC1B: 1 A Value rated at the following ambient temperatures: 40 °C (104 °F), 55 °C (131 °F), 60 °C (140 °F). Current draw @ 24V DC, controller power

N/A

• 1769-L24ER-QB1B: 0.95A Value rated at the following ambient temperatures: 40 °C (104 °F), 55 °C (131 °F), 60 °C (140 °F). • 1769-L24ER-QBFC1B and 1769-L27ERM-QBFC1B: 0.8 A Value rated at the following ambient temperatures: 40 °C (104 °F), 55 °C (131 °F), 60 °C (140 °F).

Current draw @ 24V DC, field power, max

3 A - Combined total for all devices that draw current from field power connections

N/A

Input: 5 mA Output: 500 mA Power dissipation, max

11.5 W

• 1769-L24ER-QB1B: 12 W • 1769-L24ER-QBFC1B, L27ERM-QBFC1B: 21 W

Isolation voltage

50V (continuous), Basic Insulation Type Tested at 500V AC for 60 s, System to Field

30V (continuous), Basic Insulation Type, USB to system, Ethernet to system and Ethernet to Ethernet Type tested at 500V AC for 60 s

Short circuit protection, field power

Internal fuse, Non-replaceable

N/A

Recommended external short circuit protection, field power

User-provided 4…5 A @ 3.15…5.5 A2t fuse

N/A

Weight, approx

0.66 kg (1.5 lb)

• 1769-L24ER-QB1B = 0.63 kg (1.39 lb)

0.31 kg (0.68 lb)

50V, Basic Insulation Type Tested at 500V AC for 60 s, System to Communication ports.

0.54 kg (1.18 lb)

• 1769-L24ER-QBFC1B and 1769-L27ERM-QBFC1B = 0.9 kg (1.9 lb)

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

7

Page 8

CompactLogix Controllers Specifications

Table 4 - Technical Specifications - CompactLogix 5370 Controllers and Compact GuardLogix 5370 Controllers Attribute

1769-L16ER-BB1B, 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B

1769-L24ER-QB1B, 1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B

1769-L30ER, 1769-L30ER-NSE, 1769-L30ERM, 1769-L33ER, 1769-L33ERM, 1769-L36ERM

1769-L30ERMS, 1769-L33ERMS, 1769-L36ERMS

Module width

100.00 mm (3.94 in.)

1769-L24ER-QB1B = 115.00 mm (4.53 in.) 1769-L24ER-QBFC1B and 1769-L27ERM-QBFC1B = 140 mm (5.51 in.)

55.00 mm (2.17 in.)

89.00 mm (3.50 in.)

Module location

DIN rail mount

DIN rail or panel mount

Panel-mounting screw torque

N/A

1.1…1.8 Nm (10…16 lbin) - use M4 or #8 screws

Embedded power supply

24V DC input, isolated

24V DC Input, isolated

Power supply distance rating

NA

• Controller and 1769-SDN: 4 • 1769 Compact I/O modules: 4…8, depending on module

Wire category(2)

1 - signal ports 1 - power ports 2 - communication ports

2 - communication ports

Wire type, Ethernet

RJ-45 connector according to IEC 60603-7, 2 or 4 pair Category 5e minimum cable according to TIA 568-B.1 or Category 5 cable according to ISO/IEC 24702

Wire type, power terminals and embedded I/O connections

Copper

Wire size, power terminals(3)

0.051…3.31 mm2 (30…12 AWG) solid or stranded copper wire rated at 75 °C (167 °F), or greater, 1.2 mm (3/64 in.) insulation, max Each terminal accepts 1 or 2 wires

0.25…2.50 mm2 (22…14 AWG) solid copper wire rated at 75 °C (167 °F), or greater 1.2 mm (3/64 in.) insulation, max Each terminal accepts only 1 wire

N/A

Wire stripping length, power terminals(3)

10 mm (0.39 in)

8 mm (0.31 in)

N/A

Screw torque, power terminals (3)

0.5…0.6 N•m (4.4…5.3 lb•in)

1.0…1.2 N•m (8.9…10.6 lb•in)

N/A

1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4 4 (3 I/O modules between controller and power supply)

N/A

2 (24…16 AWG) solid or stranded copper wire rated at

Wire size, embedded I/O connections

0.205…1.31 mm 75 °C (167 °F), or greater 1.2 mm (3/64 in.) insulation, max or 90 °C (194 °F) Each terminal accepts only 1 wire

N/A

Wire stripping length, embedded I/O connections

10 mm (0.39 in)

N/A

North American temperature code

T4A

IEC temperature code

T4

Enclosure type rating

None (open-style)

T3C

T5 T5

(1) You can use up to the maximum number of local expansion modules with the CompactLogix 5370 L1 controllers that are listed as long as the total current drawn by the embedded I/O and local expansion modules does not exceed both the available POINTBus backplane current of 1 A and the field power current of 3 A. For more information on POINTBus backplane current and field-power current considerations when installing local expansion modules, see page 11. (2) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 and the appropriate system-level installation manual. (3) Regarding the CompactLogix 5370 L1 controllers, this specification applies to connecting wires to the power connector that is inserted in the controller. Regarding the CompactLogix 5370 L2 controllers, this specification applies to connecting wires to power terminals built into the controller.

8

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

Page 9

CompactLogix Controllers Specifications

Real-time Clock Accuracy The following table lists the real-time clock accuracy specifications for the CompactLogix 5370 controllers. Ambient Temperature

Accuracy

0 °C (32 °F)

-143…42 s/mo

25 °C (77 °F)

-78…91 s/mo

40 °C (104 °F)

-101…73 s/mo

60 °C (140 °F)

-204…-4.50 s/mo

Real-time Clock Hold-up Times The following table lists the typical real-time clock hold-up specifications for the CompactLogix 5370 controllers. IMPORTANT

The values in the following table are typical and can vary with some CompactLogix 5370 control systems.

Ambient Temperature

Holdup Time, Typical

0 °C (32 °F)

40 days

25 °C (77 °F)

35 days

40 °C (104 °F)

28 days

60 °C (140 °F)

16 days

The I/O module support for CompactLogix 5370 controller systems varies by controller.

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

9