Page 10
CompactLogix Controllers Specifications
I/O Module Support - CompactLogix 5370 L1 Controllers The CompactLogix 5370 L1 controllers offer an embedded I/O module and the option to use 1734 POINT I/O modules as local expansion modules. The embedded I/O module provides the following: • 16 sinking 24V DC digital input points • 16 sourcing 24V DC digital output points To use 1734 POINT I/O modules as local expansion modules, keep in mind the following: • Local expansion modules must be installed in the same system as the CompactLogix 5370 L1 controller. • The modules are installed to the right of the controller. • The maximum number of local expansion modules available depends on the controller catalog of that system. Table 5 lists the number of 1734 POINT I/O modules the CompactLogix 5370 L1 controllers support. The minimum RPI of each I/O module is 1.0 ms and can be changed by 0.5 ms increments. Table 5 - 1769-L16ER-BB1B, 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B Controllers - Local I/O Module Support Cat. No.
Local 1734 POINT I/O Modules Supported, max
1769-L16ER-BB1B
6
1769-L18ER-BB1B
8
1769-L18ERM-BB1B 1769-L19ER-BB1B
Embedded I/O Module
10
Local Expansion Modules
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
Page 11
CompactLogix Controllers Specifications
You can use the maximum number of 1734 POINT I/O modules with the CompactLogix 5370 L1 controllers that are listed in Table 5. The total current drawn by the embedded I/O and local expansion modules cannot exceed both the available POINTBus backplane current of 1 A and the field power current of 3 A. Depending on the configuration of your application, you can use one of the following devices to make additional POINTBus backplane current or field power current available: • 1734-EP24DC POINT I/O Expansion Power Supply - An expansion power supply is installed between embedded I/O modules and local expansion modules or between local expansion modules. The expansion power supply breaks the available POINTBus backplane current between the modules to its left and right. With the expansion power supply installed, the modules to its left can draw up to 1 A of POINTBus backplane current. The modules to the right of the expansion power supply can draw as much current as the current provided by the expansion power supply. Additionally, the expansion power supply breaks the available field power current between the modules to its left and right. With the expansion power supply installed, the modules to its left can draw up to 3 A of field power current. The modules to the right of the expansion power supply can draw as much field power current as allowed by the expansion power supply. For more information on the 1734-EP24DC expansion power supply, see the POINT I/O 24V DC Expansion Power Supply Installation Instructions, publication 1734-IN058. • 1734-FPD POINT I/O Field Power Distributor Module - A field power distributor module can also be installed between embedded I/O modules and local expansion modules or between local expansion modules. The field power distributor module breaks the available field power current between the modules to its left and right. With the field power distributor module installed, the modules to its left can draw up 3 A of field power current. The modules to the right of the field power distributor can draw as much field power current as allowed by the field power distributor. For more information on the 1734-FPD POINT I/O Field Power Distributor module, see the POINT I/O Field Power Distributor Module Installation Instructions, publication 1734-IN059. IMPORTANT
Remember, the field power distributor module changes only the level of field power current available in the system. The module does not affect the level of POINTBus backplane current available.
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
11
Page 12
CompactLogix Controllers Specifications
Local I/O Performance of the CompactLogix 5371 L1 Controllers The requested packet interval (RPI) defines the frequency at which the controller sends data to and receives data from I/O modules. You set an RPI rate for each I/O module in your system. CompactLogix 5370 L1 controllers always attempt to scan an I/O module at the configured RPI rate. For individual I/O modules, a Module RPI Overlap minor fault occurs if there are enough I/O modules with RPI rates set too fast that they cannot all be serviced in the allotted interval. The specific configuration parameters for a system determine the impact on actual RPI rates. These configuration factors can impact the effective scan frequency for any individual module: • Rates at which the RPI rates of other 1734 POINT I/O module are set • Number of other 1734 POINT I/O modules in the system • Types of other 1734 POINT I/O modules in the system • Application user task priorities In general, follow these guidelines when setting the RPI rates in a CompactLogix 5370 L1 control system: • For digital modules: – 1…2 modules can be scanned in 2 ms. – 3…4 modules can be scanned in 4 ms. – 5…8 modules can be scanned in 8 ms. IMPORTANT
When considering digital I/O modules, remember that they can be the embedded I/O module on the controller or 1734 POINT I/O modules that are used as local expansion modules. Therefore, the consideration for using two modules can be the embedded I/O module and a 1734 POINT I/O module or two 1734 POINT I/O modules.
• For specialty and analog modules (except 1734-485ASC modules): – 1 module can be scanned at 20 ms. – For each additional module, add 20 ms. For example, if a CompactLogix 5370 L1 control system uses two analog modules, the module can be scanned in 40 ms. • For 1734-485ASC modules, the total data size for all ASC modules determines the RPI rates: – For total data size less than 20 bytes, each module can be scanned in 20 ms. – For data size greater than 20 bytes, use the size value as the RPI. For example, if the total data size is 40 bytes, each ASC module can be scanned in 40 ms. You are not required to set the RPI values of individual 1734 POINT I/O module to the values listed previously. For example, if your application scans one or two modules, you do not have to use RPI rates of 2 ms. Remember, though, that higher RPI rates result in scanning the data less frequently. The RPI shows how quickly modules can be scanned, not how quickly an application can use the data. The RPI is asynchronous to the program scan. Other factors, such as program execution duration, affect I/O throughput.
12
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
Page 13
CompactLogix Controllers Specifications
Table 6 - Embedded DC Input Specifications Attribute
1769-L16ER-BB1B, 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B
Inputs
16
Voltage category
24V DC sink
Operating voltage range
10…28.8V DC 24V DC nom
Digital filter, off to on
0.5 ms hardware plus 0…65 ms (user selectable)
Input delay, off to on Digital filter, on to off
0.5 ms hardware plus 0…65 ms (user selectable)
Input delay, on to off Off-state voltage, max
5V DC
Off-state current, max
1 mA
On-state current, min
2 mA @ 24V DC
Input impedance, max
5.4 k
Cyclic update time
1…750 ms
Isolation voltage
50V DC (continuous), Basic Insulation Type Tested at 500V AC for 60 s, system to field No isolation between individual channels
IEC input compatibility
Type 3
Isolated groups
None
Table 7 - Embedded DC Output Specifications Attribute
1769-L16ER-BB1B, 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B
Outputs
16
Voltage category
24V DC source
Operating voltage range
10…28.8V DC 24V DC nom
Output delay, off to on
0.1 ms
Output delay, on to off
0.1 ms
Off-state leakage current, max
0.5 mA @ 24V DC
On-state current, min
1 mA per channel
On-state voltage drop, max
0.6V DC
Current per point, max
0.5 A
Current per module, max
3A
Surge current per point, max
1 A for 100 ms per point, repeatable every 2 s
Isolation voltage
50V DC (continuous), Basic Insulation Type Tested at 500V AC for 60 s, system to field No isolation between individual channels
Isolated groups
None
Pilot duty rating
0.5 A
Table 8 - Embedded Power Supply Attribute
1769-L16ER-BB1B, 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B
Input voltage range
10…28.8V DC
Input voltage, nom
24V DC
Line requirement (VDC), min
30VA
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
13
Page 14
CompactLogix Controllers Specifications
Table 8 - Embedded Power Supply Attribute
1769-L16ER-BB1B, 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B
Available 5V DC POINTBus backplane current
1 A @ 5V DC
Current draw @ 24V DC, field power, max
3 A(1)
Inrush, max
10 A
Line loss ride through
10 ms…10 s
Output bus current capacity, max
0.1…3 A @ 5V DC
Load current, min
300 mA
Power dissipation, max
12 W
Short circuit protection
Internal fuse Not user replaceable
Overvoltage protection
Yes
(1) Combined total for all devices that draw current from field power connections.
I/O Module Support - CompactLogix 5370 L2 Controllers The CompactLogix 5370 L2 controllers offer embedded I/O modules and the option to use 1769 Compact I/O modules as local expansion modules. The following table describes the embedded I/O modules and local expansion modules that the CompactLogix 5370 L2 controllers support. Embedded I/O Module Support
Local Expansion Modules Support
Cat. No.
Sinking/Sourcing 24V DC Digital Input Points
Sourcing 24V DC Digital Output Points
High-speed Counters
High-speed Counter Output Points
Universal Analog Input Points
Analog Output Points
1769 Compact I/O Modules
1769-L24ER-QB1B
16
16
-
-
-
-
4
4
4
2
As many as 4 modules
1769-L24ER-QBFC1B 1769-L27ERM-QBFC1B
IMPORTANT
14
Remember the following when using the embedded I/O modules on CompactLogix 5370 L2 controllers: • 1769-L24ER-QB1B controller - The digital input points and digital output points are on one embedded I/O module. Therefore, the 1769-L24ER-QB1B controller is considered to have one embedded I/O module. • 1769-L24ER-QBFC1B and 1769-L27ERM-QBFC1B controllers - The digital input points and digital output points are on one embedded I/O module. The high-speed counter input/output points, universal analog input points, and analog output points are on another single embedded I/O module. Therefore, the 1769-L24ER-QBFC1B and 1769-L27ERM-QBFC1B controllers are considered to have two embedded I/O modules.
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
Page 15
CompactLogix Controllers Specifications
You configure an RPI rate for the embedded I/O modules to establish specific time intervals at which data is transmitted between the controller and the embedded I/O modules. The available RPI range of the embedded I/O modules is 0.5…750.0 ms and can be changed by 0.5 ms increments. The default setting is 20 ms. To use 1769 Compact I/O modules as local expansion modules, keep in mind the following: • Local expansion modules must be installed in the same system as the CompactLogix 5370 L2 controller. • Local expansion modules are installed to the right of the embedded I/O modules. • You must install a 1769-ECR Compact I/O end cap on the right side of control system. The end cap can be installed on the right side of the embedded I/O module. If local expansion modules are used, the end cap can be installed on the right side of 1769 Compact I/O module. Embedded I/O Modules
Local Expansion Modules
CompactLogix 5370 L2 Controller Local I/O Performance The requested packet interval (RPI) defines the frequency at which the controller sends data to and receives data from I/O modules. You set an RPI rate for each I/O module in your system in the programming software. You also set RPI rates through the programming software for embedded I/O modules, local expansion modules, and distributed I/O modules over an EtherNet/IP network. The CompactLogix 5370 L2 controllers always attempt to scan an I/O module at the configured RPI rate. The controller scans distributed I/O modules at the configured RPI rates. With embedded I/O modules and local expansion modules, however, some specific system-configuration parameters determine the actual rate at which the controller scans the modules. That is, the controller can be configured to scan an I/O module at one rate, but actually scan the module at another rate. For individual I/O modules, a Module RPI Overlap minor fault occurs if there is at least one I/O module that cannot be serviced within its RPI time.
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
15
Page 16
CompactLogix Controllers Specifications
The specific configuration parameters for a system determine the impact on actual RPI rates. These configuration factors can impact the effective scan frequency for any individual embedded or local expansion module: • Rates at which the RPI values of the embedded I/O modules are set • Number of embedded I/O modules that are used in the system • Types of embedded I/O modules that are used in the system • Rates at which RPI values for the 1769 Compact I/O module are set • Number of 1769 Compact I/O modules in the system • Types of 1769 Compact I/O modules in the system • Application user task priorities Table 9 describes RPI rate guidelines. Table 9 - RPI Rate Guidelines Type of Module
Guidelines
Digital and analog (any mix)
The following guidelines apply: • 1…2 modules can be scanned in 0.5 ms. • 3…4 modules can be scanned in 1 ms. • 5…6 modules can be scanned in 2 ms. • Some input modules have a fixed 8 ms filter, so selecting a faster RPI has no effect.
Specialty
The following conditions apply: • For every full-sized 1769-SDN module in the system, increase the RPI of every other module by 2 ms. • For every 1769-HSC module in the system, increase the RPI of every other module by 1 ms. • For every full-sized 1769-ASCII module system, increase the RPI of every other module by 1 ms. • For every 1769-SM2 module in the system, increase the RPI of every other module by 2 ms. For example, if the system includes four I/O modules that are configured with an RPI = 1 ms and you add a 1769-SDN module to the system, increase the RPI value for all four I/O modules by 2 ms. Therefore, when the 1769-SDN module is added to the system, the four I/O modules use an RPI = 3 ms. If, in the same system, you add a second 1769-SDN module, the RPI value of the four I/O modules is increased to 5 ms.
IMPORTANT
The number of I/O modules can be the embedded I/O modules on the controller or 1769 Compact I/O modules that are used as local expansion modules. Therefore, the consideration for using modules can be any of the following system configurations: • Only embedded I/O modules • Only 1769 Compact I/O modules • Some combination of embedded I/O modules and 1769 Compact I/O modules
You can set individual RPI rates for 1769 Compact I/O modules higher than those values listed in Table 9. The RPI shows how quickly modules can be scanned, not how quickly an application can use the data. The RPI is asynchronous to the program scan. Other factors, such as program execution duration, affect I/O throughput. Table 10 - Embedded DC Input Specifications Attribute
1769-L24ER-QB1B
Inputs
16
Voltage category
24V DC sink/source
Operating voltage range
10…28.8V DC @ 40 °C (104 °F) 10…26.4V DC @ 60 °C (140 °F) 24V DC nom
16
1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B
10…28.8V DC @ 40 °C (104 °F) 10…27.0V DC @ 55 °C (131 °F) 10…26.4V DC @ 60 °C (140 °F) 24V DC nom
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
Page 17
CompactLogix Controllers Specifications
Table 10 - Embedded DC Input Specifications Attribute
1769-L24ER-QB1B
1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B
Digital filter, off to on
0 s, 100 s, 500 s, 1 ms, 2 ms, 4 ms, 8 ms
Input delay, off to on
100 s, min 8 ms, max
Digital filter, on to off
0 s, 100 s, 500 s, 1 ms, 2 ms, 4 ms, 8 ms
Input delay, on to off
100 s, min 8 ms, max
Off-state voltage, max
5V DC
Off-state current, max
1.5 mA
On-state current, min
2 mA @ 24V DC per channel
On-state current, max
5 mA @ 24V DC per channel
Input impedance, max
5.2 k @ 24V DC 6.1 k @ 30V DC
Cyclic update time
0.5…750 ms
Isolation voltage
75V (continuous), Reinforced Insulation Type Type tested at 1200V AC for 1 s and at 1700V DC for 1 s; group to system, group to group
IEC input compatibility
Type 3
Isolated groups
Group 1: inputs 0…7 Group 2: inputs 8…15 Isolated groups operate in either sink or source configurations
Table 11 - Embedded DC Output Specifications Attribute
1769-L24ER-QB1B
Outputs
16
1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B
Voltage category
24V DC source
Operating voltage range
20.4…26.4V DC 24V DC nom
Output delay, off to on
0.05 ms
Output delay, on to off
0.5 ms
Off-state leakage current, max
0.1 mA @ 26.4V DC
On-state current, max
0.5 mA @ 24V DC per channel
On-state voltage drop, max
1.0V DC @ 1.0 A
Current per point, max
0.83 A @ 40 °C (104 °F) 0.5 A @ 60 °C (140 °F)
0.83 A @ 40 °C (104 °F) 0.58 A @ 55 °C (131 °F) 0.5 A @ 60 °C (140 °F)
Current per module, max
6.64 A @ 40 °C (104 °F) 4.0 A @ 60 °C (140 °F)
6.64 A @ 40 °C (104 °F) 4.64 A @ 55 °C (131 °F) 4.0 A @ 60 °C (140 °F)
Surge current per point, max
2.0 A for 10 ms per point, repeatable every 2 s
Isolation voltage
75V (continuous), Reinforced Insulation Type Type tested at 1200V AC for 1 s and at 1700V DC for 1 s; group to system, group to group
Isolated groups
Group 1: inputs 0…7 Group 2: inputs 8…15
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
17
Page 18
CompactLogix Controllers Specifications
Embedded DC Output Temperature Derating The area within the curves represents the safe operating range for the embedded DC outputs under various conditions of user supplied voltages and ambient temperatures. Figure 1 - Embedded DC Outputs Maximum Amperes per Point Versus Temperature 1.00
Maximum Amperes per Point
0.95 0.90 0.85 0.80 0.75 0.70 0.65 0.60 0.55 0.50
40 °C (104 °F)
50 °C (122 °F)
60 °C (140 °F)
Ambient Temperature
Figure 2 - Embedded DC Outputs Maximum Amperes per Module Versus Temperature
Maximum Amperes per Module
8.00 7.50 7.00 6.50 6.00 5.50 5.00 4.50 4.00
40 °C (104 °F)
50 °C (122 °F)
60 °C (140 °F)
Ambient Temperature
18