The text of a spec sheet · part 3 of 8
CompactLogix Controllers Specifications, pages 19 to 27
Pages 19 to 27 of 72
The original document is the PDF (3.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Allen-Bradley 1769-IQ6X0W4
Page 19
CompactLogix Controllers Specifications
Table 12 - Embedded Analog Input Specifications Attribute
1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B
Inputs
4 channels of thermocouple/voltage/current 2 channels of RTD/Resistance inputs
Operating voltage range
2.6…30.0V DC @ 40 °C (104 °F) 2.6…26.4V DC @ 55 °C (131 °F) 2.6…5V DC @ 60 °C (140 °F)
Input types
• • • •
Input ranges(1)
Thermocouple: • K at 1370…1372 °C (2498…2501.6 °F) • K at -170…1370 °C (-274…2498 °F) • K at -200…1370 °C (-328…2498 °F) • S and R at 0…1768 °C (32…3214.4 °F) • S and R at -50…0 °C (-58…32 °F) • B at 300…1820 °C (572…3308 °F) • B at 250…300 °C (482…572 °F) • J at -210…1200 °C (-328…2192 °F) • T at -170…400 °C (-274…752 °F) • T at -200…-170 °C (-328…-274 °F) • E at -200…1000 °C (-328…1832 °F) • N at -110…1300 °C (-166…2372 °F) • N at -200…-110 °C (-328…-166 °F) • C at 0…2315 °C (32…4199 °F) Voltage: • -50…50 mV • -100…100 mV • 0…5V • 1…5V • 0…10V • -10V…10V Current: • 0…20 mA • 4…20 mA RTD: • 0…100 Platinum 385 • 0…200 Platinum 385 • 0…500 Platinum 385 • 0…1000 Platinum 385 • 0…100 Platinum 3916 • 0…200 Platinum 3916 • 0…500 Platinum 3916 • 0…1000 Platinum 3916 • 0…10 Copper 426 • 0…120 Nickel 618 • 0…120 Nickel 672 • 0…604 Nickel-Iron 518 Resistance: • 0…150 • 0…500 • 0…1000 • 0…3000
Resolution, max
15 bits plus sign (Bipolar) 16 bits (Unipolar)
Input impedance
Voltage: 10 M Current: 250
Converter type
Sigma-Delta
Thermocouple: J, K, T, E, R, S, B, N, and C Voltage Current RTD: Platinum 385, Platinum 3916, Copper 426, Nickel 672, Nickel 618, Nickel-Iron 518 • Resistance
Cyclic update time
11…5000 ms dependent on user configuration
Rated working voltage
30V AC/30V DC
Common mode voltage
±10V DC per channel
Common mode rejection ratio, min
115 dB at 50 Hz at 10V 115 dB at 60 Hz at 10V
Normal mode rejection ratio, min
85 dB at 50 Hz at 1.5V 85 dB at 60 Hz at 1.5V
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
19
Page 20
CompactLogix Controllers Specifications
Table 12 - Embedded Analog Input Specifications Attribute
1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B
Accuracy, overall at 25 °C (77 °F)(2)
Thermocouple types: • J at -210…1200 °C (-328…2192 °F): +0.6 °C (1.1 °F) • N at -110…1300 °C (-166…2372 °F): +1.0 °C (1.8 °F) • N at -200…-110 °C (-328…-166 °F): +1.0 °C (1.8 °F) • T at -170…400 °C (-274…752 °F): +1.0 °C (1.8 °F) • T at -200…-170 °C (-328…-274 °F): +1.0 °C (1.8 °F) • K at 1370…1372 °C (2498…2501.6 °F): +1.2 °C (2.2 °F) • K at -200…1370 °C (-328…2498 °F): +1.0 °C (1.8 °F) • E at -200…1000 °C (-328…1832 °F): +0.5 °C (0.9 °F) • S and R at 0…1768 °C (32…3214.4 °F): +1.7 °C (3.1°F) • S and R at -50…0 °C (-58…32 °F): +4.0 °C (7.2 °F) • B at 300…1820 °C (572…3308 °F): +3.0 °C (5.4 °F) • B at 250…300 °C (482…572 °F): +6.0 °C (10.8 °F) • C at 0…2315 °C (32…4199 °F): +1.8 °C (3.2 °F) Voltage inputs: • +50 mV: +15 V • +100 mV: +20 V • 0…5V: +2.5 mV • 1…5V: +2 mV • 0…10V: +5 mV • ±10V: +10 mV Current inputs: • 0…20 mA: +20 A • 4…20 mA: +16 A RTD types: • Platinum 385: +0.5 °C (0.9 °F) • Platinum 3916: +0.4 °C (0.7 °F) • Nickel: +0.2 °C (0.4 °F) • Nickel-Iron: +0.3 °C (0.5 °F) • Copper: +0.6 °C (1.1 °F) Resistance types: • 0…150 : +0.15 • 0…500 : +0.5 • 0…1000 : +1.0 • 0…3000 : +1.5
Accuracy, overall at 0…60 °C (32…140 °F)(2)
Thermocouple types: • J at -210…1200 °C (-328…2192 °F): ±0.9 °C (1.6 °F) • N at -110…1300 °C (-166…2372 °F): +1.5 °C (2.7 °F) • N at -200…-110 °C (-328…-166 °F): +1.5 °C (2.7 °F) • T at -170…400 °C (-274…752 °F): +1.5 °C (2.7 °F) • T at -200…-170 °C (-328…-274 °F): +1.5 °C (2.7 °F) • K at 1370…1372 °C (2498…2501.6 °F): +1.8 °C (3.2 °F) • K at -200…1370 °C (-328…2498 °F): +1.5 °C (2.7 °F) • E at -200…1000 °C (-328…1832 °F): +0.8 °C (1.4 °F) • S and R at 0…1768 °C (32…3214.4 °F): +3.5 °C (6.3 °F) • S and R at -50…0 °C (-58…32 °F): +4.0 °C (7.2 °F) • B at 300…1820 °C (572…3308 °F): +4.5 °C (8.1 °F) • B at 250…300 °C (482…572 °F): +9.0 °C (16.2 °F) • C at 0…2315 °C (32…4199 °F): +3.5 °C (6.3 °F) Voltage inputs: • +50 mV: +25 V • +100mV: +30 V • 0…5V: +5 mV • 1…5V: +4 mV • 0…10V: +10 mV • ±10V: +20 mV Current inputs: • 0…20 mA: +50 A • 4…20 mA: +40 A RTD types: • Platinum 385: +0.9 °C (1.6 °F) • Platinum 3916: +0.8 °C (1.4 °F) • Nickel: +0.4 °C (0.7 °F) • Nickel-Iron: +0.5 °C (0.9 °F) • Copper: +1.1 °C (2.0 °F) Resistance types:(2) • 0…150 : +0.25 • 0…500 : +0.8 • 0…1000 : +1.5 0…3000 : +2.5
20
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
Page 21
CompactLogix Controllers Specifications
Table 12 - Embedded Analog Input Specifications Attribute
1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B
Cold junction compensation accuracy at 0…60 °C (32…140 °F)(2)
+1.3 °C (34.34 °F)
Calibration
Cyclic calibration by user configuration
Non-linearity (in percent full scale)
±0.05%
Repeatability at 25 °C (77 °F) with 10 Hz filter
Thermocouple types: • J at -210…1200 °C (-328…2192 °F): +0.1 °C (0.2 °F) • N at -110…1300 °C (-166…2372 °F): +0.1 °C (0.2 °F) • N at -200…-110 °C (-328…-166 °F): +0.25 °C (0.5 °F) • T at -170…400 °C (-274…752 °F): +0.1 °C (0.2 °F) • T at -200…-170 °C (-328…-274 °F): +1.5 °C (2.7 °F) • K at 1370…1372 °C (2498…2501.6 °F): +0.15 °C (0.3 °F) • K at -170…1370 °C (-274…2498 °F): +0.1° (0.2 °F) • K at -200…-170 °C (-328…-274 °F): +2.0 °C (3.6 °F) • E at -200…1000 °C (-328…1832 °F): +0.1° (0.2 °F) • S and R at 0…1768 °C (32…3214.4 °F): +0.4 °C (0.7 °F) • S and R at -50…0 °C (-58…32 °F): +1.0 °C (1.8 °F) • B at 300…1820 °C (572…3308 °F): +0.7 °C (1.3 °F) • B at 250…300 °C (482…572 °F): +1.5 °C (2.7 °F) • C at 0…2315 °C (32…4199 °F): +0.2 °C (0.4 °F) Voltage inputs: • +50 mV: +6 A • +100mV: +6 V • 0…5V: +150 mV • 1…5V: +150 mV • 0…10V: +150 mV • ±10V: +150 mV Current inputs: • 0…20 mA: +0.3 A • 4…20 mA: +0.3 A RTD types: • Platinum 385: +0.2 °C (0.4 °F) • Platinum 3916: +0.2 °C (0.4 °F) • Nickel: +0.01 °C (0.02 °F) • Nickel-Iron: +0.01 °C (0.02 °F) • Copper: +0.2 °C (0.4 °F) Resistance types: • 0…150 : +0.04 • 0…500 : +0.2 • 0…1000 : +0.2 • 0…3000 : +0.2
Overload at input terminals, max
Voltage: +35V DC continuous Current: 32 mA continuous, +7.6V DC
Channel diagnostics
Invalid configuration, Over- or under-range by bit reporting, open circuit
Isolation voltage
30V AC/30V DC (continuous), reinforced insulation type Type tested at 720V DC for 60 s; inputs to system backplane
(1) Values for these input types rated at the following ambient temperatures: 40 °C (104 °F), 55 °C (131 °F), 60 °C (140 °F). (2) These specification values are based on cyclic calibration and connecting a 4-wire device to the module.
Table 13 - Embedded Analog Output Specifications Attribute
1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B
Outputs
2 single-ended
Output types
• Voltage • Current
Output ranges(1)
Voltage: • 0…5V • 1…5V • 0…10V • -10V…10V Current: • 0…20 mA • 4…20 mA
Converter type
R-2R Ladder Voltage Switching
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
21
Page 22
CompactLogix Controllers Specifications
Table 13 - Embedded Analog Output Specifications Attribute
1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B
Resolution, max
15 bits plus sign (Bipolar) 16 bits (Unipolar)
Cyclic update time, nom
2.5 ms
Cyclic update time, max
9.5 ms
Current load on voltage output
10 mA max
Resistive load on current output
0…300
Load range on voltage output
> 1 kat 10V DC
Inductive load, max (current outputs)
0.1 mH
Capacitive load, max (Voltage Outputs)
1 μF
Accuracy, overall at 25 °C (77 °F)
Voltage: ±0.5% full scale Current: ±0.5% full scale
Accuracy, overall at 0…60 °C (32…140 °F)
Voltage: ±0.8% full scale Current: ±0.8% full scale
Accuracy drift with temperature
Voltage: ±0.0086% full scale per °C Current: ±0.0086% full scale per °C
Output ripple range 0…50 kHz (referred to output range)
±0.05%
Non-linearity
±0.05% (in percent full scale)
Repeatability
+ 0.05%
Output impedance
Voltage: <1 Current: >1 M
Short-circuit protection
Yes
Short-circuit, nom
Current: 16 mA
Open circuit, max
16V
Output response at system powerup and powerdown
Current: + 1.0V spike for < 5 ms Voltage: + 1.0V DC spike < 5 ms
Isolation voltage
30V AC/30V DC (continuous), reinforced insulation type Type tested at 500V AC or 710V DC for 60 s; outputs to system backplane
(1) Values for these input types rated at the following ambient temperatures: 40 °C (104 °F), 55 °C (131 °F), 60 °C (140 °F).
Table 14 - Analog Input Ranges Input Type Normal Op. Range
Full Range(1)
-10…10V DC
-10.5V… +10.5V
0…5V DC
Raw/Prop. Data Units for Full Range
Eng. Unit Values for Full Range x 10
°C
°C
°F
Scaled-forPID Values for Normal Operating Range
Scaled-for-PID Values for Full Range
Percent of Normal Op. Range Values
Percent of Full Range Values
0…16,383
-410…16793
-10000… 10000
-10500… 10500
0…10000
-1000… 10500
°F
-10500…10500
-1050…1050
-0.5V…5.25V
-500…5250
-50…525
-1638…17202
0…10V DC
-0.5V…10.5V
-500…10500
-50…1050
-819…17202
-500… 10500
4…20 mA
3.2…21 mA
3200…21000
320…2100
-819…17407
-500… 10625
22
-32767… +32767
Eng. Unit Values for Full Range x 1
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
Page 23
CompactLogix Controllers Specifications
Table 14 - Analog Input Ranges Input Type Normal Op. Range
Full Range(1)
1…5V DC
0.5V…5.25V
0…20 mA
0…21 mA
Raw/Prop. Data Units for Full Range
-32767… 32767
Eng. Unit Values for Full Range x 1
Eng. Unit Values for Full Range x 10
°C
°C
°F
500…5250
50…525
0…21000
0…2100
Scaled-forPID Values for Normal Operating Range
Scaled-for-PID Values for Full Range
Percent of Normal Op. Range Values
Percent of Full Range Values
0…16,383
-2048…17407
0…10000
-1250… 10625
°F
J (-210…1200)
-2100…12000
-3460…21920
-210…1200
-346…2192
K (-200…1372)
-2000…13720
-3280…25020
-200…1372
-328…2502
T (-200…400)
-2000…4000
-3280…7520
-200…400
-328…752
E (-200…1000)
-2000…10000
-3280…18320
-200…1000
-328…1832
R (-50…1768)
-500…17680
-580…32140
-50…1768
-58…3214
S (-50…1768)
-500…17680
-580…32140
-50…1768
-58 …3214
B (250…1820)
2500…18200
4820…32767
250…1820
482…3308
N (-200…1300)
-2000…13000
-3280…23720
-200…1300
-328…2372
C (0…2315)
0…23150
320…32767
0…2315
32…4199
-50…50 mV
-5000…5000
0…17202
0…10500
0…16,383
0…10000
-500…500
-100…100 mV
-10000…10000
-1000…1000
0…150
0…15000
0…1500
0…500
0…5000
0…500
0…1000
0…10000
0…1000
0…3000
0…30000
Platinum 385 (-200…850)
-2000…8500
-3280…15620
-200…850
-328…1562
Platinum 3916 (-200…510)
-2000…5100
-3280…9500
-200…510
-328…950
Copper 426 (-70…150)
-700…1500
-940…3020
-70…1500
-94…302
Nickel 618 (-60…250)
-600…2500
-760…4820
-60…250
-76…482
Nickel 672 (-80…260)
-800…2600
-1120…5000
-80…260
-112…500
Nickel-Iron 518 (-100…200)
-1000…2000
-1480…3920
-100…200
-148…392
0…3000
(1) Includes amount over and under normal operating.
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
23
Page 24
CompactLogix Controllers Specifications
Table 15 - Embedded Analog Output Module Data(1) Analog Output Module Range
Input Value Example Data
Output Range State
Raw/Proportional Data
Engineering Unit
Scaled-for-PID
Percent Full Range
Decimal Range
Decimal Range
Decimal Range
Decimal Range
Controller Ordered
Embedded Analog Module Output
Controller Ordered
Controller Ordered
Controller Ordered
Controller Ordered
Embedded Analog Module Output
Over 10.5V
+11.0V
+10.5V
Over
N/A
N/A
11000
+10.5V
+10.5V
+10.5V
Over
32767
32767
10500
10500
16793
16793
10500
10500
+10V
+10.0V
+10.0V
Normal
31207
31207
10000
10000
16383
16383
10000
10000
0.0V
0.0V
Normal
0
0
0
0
8192
8192
0
0
-10.0V
-10.0V
Normal
-31207
-31207
-10000
-10000
0
0
-10000
-10000
-10.5V
-10.5V
-10.5V
Under
-32767
-32767
-10500
-10500
-410
-410
-10500
-10500
Under 10.5V
-11.0V
-10.5V
Under
N/A
N/A
-11000
-10500
-819
-410
-11000
-10500
±10V
Embedded Analog Module Output
Embedded Analog Module Output
17202
Embedded Analog Module Output
11000
Over 5.25V
5.5V
+5.25V
Over
N/A
N/A
5500
5250
18021
17202
11000
10500
5.25V
5.25V
+5.25V
Over
32767
32767
5250
5250
17202
17202
10500
10500
0…5.0V
5.0V
+5.0V
Normal
31207
31207
5000
5000
16383
16383
10000
10000
0.0V
0.0V
Normal
0
0
0
0
0
0
0
0
0…5V -0.5V
-0.5V
-0.5V
Under
-3121
-3121
-500
-500
-1638
-1638
-1000
-1000
Under -0.5V
-1.0V
-0.5V
Under
-6241
-3121
-500
-500
-3277
-1638
-2000
-1000
Over 10.5V
11.0V
+10.5V
Over
N/A
N/A
11000
10500
18021
17202
11000
10500
+10.5V
+10.5V
+10.5V
Over
32767
32767
10500
10500
17202
17202
10500
10500
0…10.0V
+10.0V
+10.0V
Normal
31207
31207
10000
10000
16383
16383
10000
10000
0.0V
0.0V
Normal
0
0
0
0
0
0
0
0
-0.5V
-0.5V
-0.5V
Under
-1560
-1560
-500
-500
-819
-819
-500
-500
Under -5.0V
-1.0V
-0.5V
Under
-3121
-1560
-1000
-500
-1638
-819
-1000
-500
Over 21.0 mA +22.0 mA
21 mA
Over
N/A
N/A
22000
21000
18431
17407
11250
10625
21.0 mA
+21.0 mA
21 mA
Over
32767
32767
21000
21000
17407
17407
10625
10625
4…20.0 mA
+20.0 mA
20 mA
Normal
31207
31207
20000
20000
16383
16383
10000
10000
+4.0 mA
+4.0 mA
Normal
6241
6241
4000
4000
0
0
0
0
0…10V
4…20 mA 3.2 mA
+3.2 mA
+3.2 mA
Under
4993
4993
3200
3200
-819
-819
-500
-500
Under 3.2
0.0 mA
+3.2 mA
Under
0
4993
0
3200
-4096
-819
-2500
-500
Over 5.25V
+5.5V
+5.25V
Over
N/A
N/A
5500
5250
18431
17407
11250
10625
+5.25V
+5.25V
+5.25V
Over
32767
32767
5250
5250
17407
17407
10625
10625
1…5.0V
+5.0V
+5.0V
Normal
31207
31207
5000
5000
16383
16383
10000
10000
+1.0V
+1.0V
Normal
6241
6241
1000
1000
0
0
0
0
0.5V
+0.5V
+0.5V
Under
3121
3121
500
500
-2048
-2048
-1250
-1250
Under 0.5V
0.0V
0.0V
Under
0
3121
0
500
-4096
-2048
-2500
-1250
Over 21.0 mA +22.0 mA
21 mA
Over
N/A
N/A
22000
21000
18201
17202
11000
10500
21.0 mA
21.0 mA
21 mA
Over
32767
32767
21000
21000
17202
17202
10500
10500
0…20.0 mA
20.0 mA
20 mA
Normal
31207
31207
20000
20000
16383
16383
10000
10000
0.0 mA
0.0 mA
Normal
0
0
0
0
0
0
0
0
Under 0.0 mA -1.0 mA
0.0 mA
Under
-1560
0
0
-1000
-819
0
-500
0
1…5V
0…20 mA
(1) If Clamping is enabled, the output value is the clamped value defined in the configuration.
24
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
Page 25
CompactLogix Controllers Specifications
Table 16 - Embedded HSC Input Specifications Attribute
1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B
Input frequency, max
250 kHz
Input current, max
15 mA per channel
Input current, min
6.8 mA
Input voltage range
2.6…30V DC(1)
On-state voltage, max
30V DC
On-state current, min
6.8 mA
Off-state voltage, max
1.0V DC
Off-state current, max
1.5 mA
Off-state leakage current, max
1.5 mA
Input impedance, nom
1950
Pulse width, min
2.5 s
Phase separation, min
1.3 s
Isolation voltage
75V (continuous), reinforced insulation type Type tested at 1200V AC for 60 s; inputs to system backplane and input to input
(1) See Maximum Input Voltage - 24V DC Operation temperature derating.
Table 17 - Embedded HSC Output Specifications Attribute
1769-L24ER-QBFC1B, 1769-L27ERM-QBFC1B
Output voltage range
5…30V DC
On-state voltage, max
User power - 0.1V DC
On-state output current, max
0.25 A per channel
On-state output current, min
1 mA
On-state voltage drop, max
0.5V DC
Off-state leakage current, max
5 μA
Turn-on time, max
400 μs
Turn-off time, max
200 μs
Reverse polarity protection
30V DC
Isolation voltage
75V (continuous), reinforced insulation type Type tested at 1200V AC for 60 s; inputs to system backplane and input to input
Current per channel, max
1.0 A @ 40 °C (104 °F) 0.5 A @ 55 °C (131 °F) 0.25 A @ 60 °C (140 °F)
Current per module, max
4.0 A @ 40 °C (104 °F) 2.0 A @ 55 °C (131 °F) 1.0 A @ 60 °C (140 °F)
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
25
Page 26
CompactLogix Controllers Specifications
Embedded HSC Temperature Derating Figure 3 - Maximum Input Voltage - 24V DC Operation
Volts (DC)
Voltage Derating Based on Temperature 35 30 25 20 15 10 5 0
26.4V DC @ 55 °C (131 °F)
0 (32)
10 (50)
20 (68)
30 (86)
40 (104)
50 (122)
60 (140)
70 (158)
Ambient Temperature °C (°F)
Temperature
Derated Voltage(1)
40 °C (104 °F)
30V DC
55 °C (131 °F)
26.4V DC
60 °C (140 °F)
5V DC
(1) Input voltage derating 55...60 °C (131…140 °F) is achieved by using a dropping resistor. For 24V DC input voltage, use a 2.4 k, 1/2 W resistor. For input voltages other than 24V DC, use a 1/2 W resistor with value: 125 x (Vin - 5V).
Figure 4 - Maximum Output Voltage - 24V DC Operation Voltage Derating Based on Temperature 31
Volts (DC)
30 29 28
26.4V DC @ 55 °C (131 °F) 27 26 0 (32)
10 (50)
20 (68)
30 (86)
40 (104)
50 (122)
60 (140)
70 (158)
Ambient Temperature °C (°F) Temperature
Derated Voltage
40 °C (104 °F)
30V DC
55…60 °C (131…140 °F)
26.4V DC
26
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
Page 27
CompactLogix Controllers Specifications
Figure 5 - Maximum Output Current per Point - 5V DC Operation Current Derating Based on Temperature Current per Point (A)
1.5 1 0.5
0.5 A at 60 °C (131 °F) 0 0 (32)
10 (50)
20 (68)
30 (86)
40 (104)
50 (122)
60 (140)
70 (158)
60 (140)
70 (158)
Ambient Temperature °C (°F)
Temperature
Derated Current
0…40 °C (32…104 °F)
1A
60 °C (140 °F)
0.5 A
Figure 6 - Maximum Output Current per Module - 5V DC Operation Current Derating Based on Temperature
Current per Module (A)
5 4 3 2
2 A at 60 °C (131 °F)
1 0 0 (32)
10 (50)
20 (68)
30 (86)
40 (104)
50 (122)
Ambient Temperature °C (°F)
Temperature
Derated Current
0…40 °C (32…104 °F)
4A
60 °C (140 °F)
2A
Figure 7 - Maximum Output Current per Point - 24V DC Operation Current Derating Based on Temperature Current per Point (A)
1.5 1 0.5
0.25 A at 60 °C (131 °F)
0 0 (32)
10 (50)
20 (68)
30 (86)
40 (104)
50 (122)
60 (140)
70 (158)
Ambient Temperature °C (°F) Temperature
Derated Current
0…40 °C (32…104 °F)
1A
55 °C (131 °F)
0.5 A
60 °C (140 °F)
0.25 A
Rockwell Automation Publication 1769-TD005J-EN-P - September 2015
27