Page 1 of CompactLogix Controllers Specifications

Spec sheet · Allen-Bradley

CompactLogix Controllers Specifications

Spec sheet72 pagesPDF 3.7 MB

Technical data for Allen-Bradley CompactLogix 5370, 1769 packaged and modular, and 1768 CompactLogix controllers: specifications and I/O support.

What this file really is

The old site listed this file as a spec sheet for the Allen-Bradley 1769-IQ6X0W4. Linked as the spec sheet for the 1769-IQ6X0W4 I/O module, this is the CompactLogix controllers specifications technical data and does not mention that module.

Download the PDF3.7 MB

Filed with · 1 model

Also filed with these models on the old site

Summary

What is in it

Rockwell Automation technical data covering the CompactLogix 5370 and Compact GuardLogix 5370 controllers, the 1769 packaged controllers with embedded I/O (1769-L23x), the 1769 modular controllers (1769-L3x) and the 1768 CompactLogix controllers. It lists environmental and technical specifications, real-time clock accuracy, I/O module support and local I/O performance, spacing and dimensions, memory use, compatibility, connection limits and accessories such as memory cards, batteries and cables.

Its parts

  1. CompactLogix 5370 Controllers
  2. 1769 Packaged CompactLogix Controllers with Embedded I/O
  3. 1769 Modular CompactLogix Controllers
  4. 1768 CompactLogix Controllers
  5. Controller Memory Use
  6. Controller Compatibility
  7. Controller Connections
  8. Determine Total Connection Use
  9. CompactLogix Controller Accessories

From the sheet

Key facts from this sheet

Each line names its page in the PDF.

Rockwell Automation technical data (publication 1769-TD005J-EN-P, September 2015) with specifications for CompactLogix controllers: CompactLogix 5370 controllers from the 1769-L16ER-BB1B to the 1769-L36ERMS, 1769 packaged and modular controllers, and 1768 controllers. It does not list the 1769-IQ6X0W4 module itself; it explains how 1769 Compact I/O modules attach to these controllers as local expansion modules. A reader uses it to check expansion limits, I/O banks, scan rates, wiring and accessories.

Read for this summary: pages 1, 5 to 8, 14 to 16, 29 to 31 and 66 to 68 of 72.

Ports
CompactLogix 5370: two EtherNet/IP ports on an embedded switch using one IP address, plus one USB port for temporary connection p. 6
L3 expansion
CompactLogix 5370 L3: up to 8 (1769-L30ER models), 16 (1769-L33ER models) or 30 (1769-L36ERM models) local 1769 Compact I/O modules p. 29
L2 expansion
CompactLogix 5370 L2: as many as 4 local 1769 Compact I/O modules p. 14
I/O banks
CompactLogix 5370 L3: up to three banks; up to 3 modules between controller and power supply; up to 8 right of the power supply in the local bank p. 29
Bank cables
1769-CRL1 and 1769-CRR1 Compact I/O communication bus expansion cables p. 30
End cap
CompactLogix 5370 L2: a 1769-ECR Compact I/O end cap on the right side of the system p. 15
Memory card
CompactLogix 5370: 1784-SD1 SD card installed, 1784-SD2 ordered separately; 1768-L4x and 1769-L3x: CompactFlash card p. 66
Battery
1769-L23x and 1769-L3x: one 1769-BA lithium battery; 1768 and CompactLogix 5370: none needed p. 67
Terminal kits
1769-RTB45 (CompactLogix 5370 L1), 1769-RTB40DIO (CompactLogix 5370 L2 digital I/O), 1769-RTB40AIO (1769-L24ER-QBFC1B and 1769-L27ERM-QBFC1B analog I/O) p. 14, 67
Ethernet wiring
RJ-45 connector, 2 or 4 pair Category 5e minimum cable p. 8
Embedded power
1769-L16ER-BB1B, 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ER-BB1B: 1 A at 5V DC POINTBus backplane current; 3 A max field power at 24V DC p. 14
Thermocouple use
CompactLogix 5370 L2: 1769-CJC sensor needed when the embedded analog input is in Thermocouple mode p. 68
L3 scan rates
CompactLogix 5370 L3, 1769 Compact I/O digital and analog: 1…2 modules in 0.5 ms, 3…4 in 1 ms, 5…30 in 2 ms p. 30, 31
Embedded I/O RPI
CompactLogix 5370 L2 embedded I/O: RPI 0.5…750.0 ms in 0.5 ms steps, default 20 ms p. 14, 15

What this sheet walks you through

  • Planning 1769 Compact I/O expansion on CompactLogix 5370 L2 controllers p. 14, 15
  • Laying out I/O banks on CompactLogix 5370 L3 controllers p. 29, 30
  • Setting RPI rates for embedded and 1769 Compact I/O modules p. 15, 16, 30, 31
  • Choosing memory cards, batteries, terminal kits and cables p. 66, 67, 68
  • Wiring Ethernet, power terminals and embedded I/O p. 8
  • Safety-locking a Compact GuardLogix application p. 6

Good to know

  • CompactLogix 5370 L3: the controller must be the leftmost module in the local bank. p. 29
  • The end of the last bank in a system must be terminated. p. 30
  • Some input modules have a fixed 8 ms filter, so a faster RPI does not help them. p. 31
  • The 1769-L23x packaged controllers have no nonvolatile memory option. p. 66
  • At shutdown, stored energy saves the program to internal memory only, not to the CompactFlash or SD card. p. 67

Questions this sheet answers

How many 1769 Compact I/O modules can a CompactLogix 5370 L3 controller take?

Up to 8 with 1769-L30ER models, 16 with 1769-L33ER models and 30 with 1769-L36ERM models. p. 29

Does a CompactLogix 5370 controller need a battery?

No. The 1768 and CompactLogix 5370 controllers need no battery; the 1769-L23x and 1769-L3x use a 1769-BA lithium battery. p. 67

What end cap does a CompactLogix 5370 L2 system need?

A 1769-ECR Compact I/O end cap on the right side of the system. p. 15

Which memory card comes with a CompactLogix 5370 controller?

A 1784-SD1 SD card comes installed; a 1784-SD2 card can be ordered separately for more nonvolatile memory. p. 66

How are banks of 1769 Compact I/O modules connected?

With expansion cables, such as the 1769-CRL1 and 1769-CRR1 Compact I/O communication bus expansion cables; the last bank must be terminated. p. 29, 30

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. CompactLogix Controllers Specifications Technical Data1
    1. CompactLogix 5370 Controllers5
    2. 1769 Packaged CompactLogix Controllers with Embedded I/O37
    3. 1769 Modular CompactLogix Controllers48
    4. 1768 CompactLogix Controllers52
    5. Controller Memory Use59
    6. Controller Compatibility60
    7. Controller Connections63
    8. Determine Total Connection Use65
    9. CompactLogix Controller Accessories66
  2. Back Cover72

From the PDF’s own bookmarks.

The whole text · 8 parts

Read the sheet here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 91-9
  2. Pages 10 to 1810-18
  3. Pages 19 to 2719-27
  4. Pages 28 to 3628-36
  5. Pages 37 to 4537-45
  6. Pages 46 to 5446-54
  7. Pages 55 to 6355-63
  8. Pages 64 to 7264-72

The file

Revision and size

Part no.1769-TD005J-EN-P
RevisionSeptember 2015
PublisherRockwell Automation
Pages72
PDF3.7 MB
TextText from the PDF itself.
1769-TD005J-EN-P

The first pages · 4 of 72

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 72
Page 2
Page 2of 72
Page 3
Page 3of 72
Page 4
Page 4of 72