Page 55

CompactLogix Controllers Specifications

Figure 10 - 1768-L43 and 1768-L43S Power Dissipation

7.5 W

8

Power Dissipated (Watts)

6

6.3 W

4.0 W 4

1768-L43S

2

2.8 W

1768-L43 5

0

15

10

20

25

30

1768 and 1769 Bus 5.2V Load (Watts)

Figure 11 - 1768-L45 and 1768-L45S Power Dissipation

4.0 W

8

Power Dissipated (Watts)

4

2.8 W

2

9.5 W 8.3 W

6

0

1768-L45S

1768-L45 5

10

15

20

25

30

35

40

1768 and 1769 Bus 5.2V Load (Watts)

Table 37 - Certifications - 1768 CompactLogix Controllers Certification(1)

1768-L43, 1768-L45 c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/EC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

RCM

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: • Article 58-2 of Radio Waves Act, Clause 3

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

55

Page 56

CompactLogix Controllers Specifications

Table 38 - Certifications - 1768 Compact GuardLogix Controllers Certification(1)

1768-L43S, 1768-L45S c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/EC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/42/EC MD, compliant with: • EN 60204-1; Electrical equipment of machines • EN ISO 13849-1; Safety-related parts of control systems • EN 62061; Functional safety of safety-related control systems

RCM

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection ‘n’ • EN60079-0; General Requirements • II 3 G Ex nA nL IIC T4 Gc

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: • Article 58-2 of Radio Waves Act, Clause 3

Functional Safety(2)

Certified by TÜV: capable of SIL 1 to 3, according to IEC 61508; and PLe/Cat. 4 according to ISO 13849-1

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details. (2) When used with specified programming software versions.

1768-L4x Minimum Spacing Requirements 105 mm (4 in.)

90 mm (3.54 in.)

90 mm (3.54 in.) 105 mm (4 in.)

56

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

Page 57

CompactLogix Controllers Specifications

1768 Slot Numbering Slot 2

Slot 1

1768 Modules

Slot 0

Slot 1

Slot 2

1769 Modules

1768-L43, 1768-L45 CompactLogix Dimensions 122.1 mm (4.81 in.) 100.5 mm (3.96 in.)

56.4 mm (2.22 in.)

131.6 mm (5.18 in.)

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

57

Page 58

CompactLogix Controllers Specifications

1768-L43S, 1768-L45S CompactLogix Dimensions 122.1 mm (4.81 in.) 100.5 mm (3.96 in.)

89.6 mm (3.53 in.)

131.6 mm (5.18 in.)

58

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

Page 59

CompactLogix Controllers Specifications

Controller Memory Use These equations provide an estimate of the memory that is needed for a controller. These numbers are rough estimates. Controller tasks

_____ * 4000

=

_____ bytes (minimum 1 task)

Digital I/O points

_____ * 400

=

_____ bytes

Analog I/O points

_____ * 2600

=

_____ bytes

DeviceNet modules(1)

_____ * 7400

=

_____ bytes

Other communication modules(2)

_____ * 2000

=

_____ bytes

Motion axes

_____ * 8000

=

_____ bytes

FactoryTalk alarm instruction

_____ * 1000

=

_____ bytes (per alarm)

FactoryTalk subscriber

_____ * 10000

=

_____ bytes

(1) The first DeviceNet module is 7400 bytes. Additional DeviceNet modules are 5800 bytes each. (2) Count all communication modules in the system, not just the modules in the local chassis. This total includes device connection modules, adapters, and ports on PanelView™ terminals.

Reserve 20…30% of the controller memory for future expansion.

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

59

Page 60

CompactLogix Controllers Specifications

Controller Compatibility Your controller can control and communicate with other devices, including the following: • Control Distributed I/O Modules • Control Safety I/O Modules • Communicate with Display Devices • Communicate with Other Controllers • Communicate with Other Communication Devices

Control Distributed I/O Modules The controller can control these distributed I/O modules. CompactLogix 5370 1768-ENBT 1769-L23Ex 1769-L32E, 1769-L35E EtherNet/IP Network(1)

1768-CNB, 1768-CNBR 1769-L32C, 1769-L35CR ControlNet Network

CompactLogix 5370 L2 and L3 1769-SDN DeviceNet Network(2) (3)

1746 SLC I/O

Yes

No

No

1756 ControlLogix I/O

Yes

Yes

Yes

1769 Compact I/O

No

No

Yes

1771 Universal I/O

No

No

No

1734 POINT I/O

Yes

Yes

Yes

1734D POINTBlock I/O

Yes

Yes

Yes

1790, 1790D, 1790P CompactBlock LDX I/O

No

No

Yes

1791D, 1791P, 1791R CompactBlock I/O

No

No

Yes

1794 FLEX I/O

Yes

Yes

Yes

1797 FLEX Ex I/O

Yes

Yes

No

Yes

No

Yes

Yes

Yes

No

1792D ArmorBlock MaXum I/O

No

No

Yes

1799 Embedded I/O

No

No

Yes

I/O Modules Chassis-based I/O

In-Cabinet I/O

On-Machine I/O 1732 ArmorBlock I/O

1738 ArmorPOINT I/O

(1) A non-EtherNet/IP CompactLogix controller requires a 1761-NET-ENI interface to connect to an EtherNet/IP network. This interface is only a messaging bridge. (2) To control I/O, use a 1769-SDN scanner to connect the controller to the DeviceNet network. (3) The 1769-SDN does not support safety communication to Guard I/O modules on a DeviceNet network.

60

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

Page 61

CompactLogix Controllers Specifications

Control Safety I/O Modules The Compact GuardLogix controller can control these safety I/O modules in a safety system. I/O Modules

EtherNet/IP

ControlNet

1791ES CompactBlock Guard I/O

Yes

No

1734 POINT Guard I/O

Yes

No

Communicate with Display Devices The controller can communicate with these display devices. Display Devices

EtherNet/IP Network(1)

ControlNet Network

DeviceNet Network(2)

RS-232 (DF1) Network

DH-485 Network

Yes

Yes

Yes

Yes

Yes

PanelView Plus and PanelView CE terminals

Yes

Yes

Yes

Yes

Yes

PanelView standard terminals

Yes

Yes

Yes

Yes

Yes

PanelView e terminals

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

Industrial Computers Allen-Bradley® industrial computers (all)(3) Graphic Terminals

Message Displays InView message displays

(1) A non-EtherNet/IP CompactLogix controller requires a 1761-NET-ENI interface to connect to an EtherNet/IP network. This interface is only a messaging bridge. (2) For DeviceNet access, use either a 1769-SDN scanner (control I/O and send/receive messages) or a 1761-NET-DNI interface (messaging bridge). (3) Includes: Allen-Bradley-integrated display rotating media (HDD) and solid-state (SSD) computers, Allen-Bradley non-display computers, and Allen-Bradley-integrated display computers with keypad.

Communicate with Other Controllers The controller can communicate with these programmable controllers. Controller

EtherNet/IP Network(1)

ControlNet Network

DeviceNet Network(2)

RS-232 (DF1) Network

DH-485 Network

1756 ControlLogix 1756 GuardLogix

Yes

Yes

Yes

Yes

Yes

CompactLogix 5370

Yes

No

Yes(3)

Yes(4)

Yes(5)

1768-L4x CompactLogix

Yes

Yes

Yes

Yes

Yes

1769-L3x CompactLogix

Yes

Yes

Yes

Yes

Yes

1769-L23x CompactLogix

Yes

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

Yes

Yes

Yes

Yes

Yes

PowerFlex with DriveLogix

Yes

Yes

Yes

Yes

Yes

1785 PLC-5

Yes(6) (7)

Yes

Yes(8)

Yes, Yes

Yes

(4)

Yes

Yes

Yes

(4)

Yes

Yes

Yes

(4)

Yes

Yes

1789 SoftLogix 5800

1794 FlexLogix

(9)

1747 SLC

Yes

1761 MicroLogix 1762 MicroLogix

Yes Yes

No No

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

61

Page 62

CompactLogix Controllers Specifications

Controller

EtherNet/IP Network(1)

ControlNet Network

DeviceNet Network(2)

RS-232 (DF1) Network

DH-485 Network

1763 MicroLogix

Yes

No

Yes(4)

Yes

Yes

1764 MicroLogix

Yes

No

Yes(4)

Yes

Yes, - - Yes, 1775 PLC-3, - - Yes, 5250 PLC-5/250, - No

Yes, 1772 PLC-2

(1) (2) (3) (4) (5) (6) (7) (8) (9)

A non-EtherNet/IP controller requires a 1761-NET-ENI interface to connect to an EtherNet/IP network. This interface is only a messaging bridge. In the CompactLogix system, use either a 1769-SDN scanner (control I/O and send/receive messages) or a 1761-NET-DNI interface (messaging bridge). The CompactLogix 5370 L1 controllers cannot access a DeviceNet network and, therefore, cannot communicate with other controllers on a DeviceNet network. The CompactLogix 5370 controllers do not have an embedded serial port. You must add external modules to communicate over an RS-232 (DF1) network. The CompactLogix 5370 controllers do not have an embedded serial port. You must add external modules to communicate over a DH-485 network. The Ethernet PLC-5 controller must be series C, firmware revision N.1 or later; series D, firmware revision E.1 or later; or series E, firmware revision D.1 or later. The 1785-ENET Ethernet communication interface module must be series A, firmware revision D or later. The PLC-5, SLC, and MicroLogix processors appear as I/O points to the Logix controller. Use the appropriate DeviceNet interface for the controller. Use a 1747-L55x controller with OS501 or later.

Communicate with Other Communication Devices The controller can communicate with these communication devices. Communication Device

EtherNet/IP Network(1)

ControlNet Network

DeviceNet Network(2)

Linking device (only ControlLogix controllers)

1788-EN2DN

1788-CN2DN 1788-CN2FF

1788-EN2DN(3) 1788-CN2DN

PCMCIA card, 1784-PCC

1784-PCD

PCI card, 1784-PCIC 1784-PCICS

1784-PCID 1784-PCIDS 1784-CPCIDS

Drives SCANport module, 1203-FM1 1203-FB1(4), Communication module, 1203-CN(5) 1770-KFC15 1770-KFCD15 1747-KFC15

1770-KFD 1770-KFG

Communication card, 1784-PKTCS 1784-KTCS 1784-KTCX15

1784-PKTX 1784-PKTXD

USB communication device, 1784-U2CN

1784-U2DN

(1) (2) (3) (4)

A non-EtherNet/IP controller requires a 1761-NET-ENI interface to connect to an EtherNet/IP network. This interface is only a messaging bridge. In the CompactLogix system, use either a 1769-SDN scanner (control I/O and send/receive messages) or a 1761-NET-DNI interface (messaging bridge). The 1788-EN2DN does not support safety communication (CIP Safety). Use a CIP generic MSG instruction to communicate with the 1203-FM1 SCANport module on a DIN rail that is remote to the controller. The remote DIN rail also requires a 1794-ACN15 or 1794-ACNR15 ControlNet adapter. (5) Use the generic module configuration to configure the 1203-CN1 module and a CIP generic MSG instruction to communicate with the module.

62

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

Page 63

CompactLogix Controllers Specifications

Controller Connections A CompactLogix system uses the connection types to establish communication links between devices: • Controller-to-local I/O modules or local communication modules • Controller-to-remote I/O or remote communication modules • Controller-to-remote I/O (rack-optimized) modules • Produced and consumed tags • Messages • Controller access by the programming software • Controller access by RSLinx® Classic software for HMI or other applications You indirectly determine the number of connections the controller uses by configuring the controller to communicate with other devices in the system. The limit of connections can ultimately reside in the communication module you use for the connection. If a message path routes through a communication module, the connection that is related to the message also counts toward the connection limit of that communication module.

CompactLogix 5370 Controller Ethernet Node Limits and Connections When designing a CompactLogix 5370 control system, you must consider the following: • Maximum number of Ethernet nodes available for the project of your controller • Connections The controller that you select determines the number of Ethernet nodes available. Cat. No.

Ethernet Nodes Supported

1769-L16ER-BB1B

4

1769-L18ER-BB1B

8

1769-L18ERM-BB1B 1769-L19ER-BB1B 1769-L24ER-QB1B

8

1769-L24ER-QBFC1B 1769-L27ERM-QBFC1B

16

1769-L30ER

16

1769-L30ERM 1769-L30ER-NSE 1769-L33ER

32

1769-L33ERM 1769-L36ERM

48

All CompactLogix 5370 controllers support 256 CIP connections and 120 TCP/IP connections.

Rockwell Automation Publication 1769-TD005J-EN-P - September 2015

63